Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberBLD18-03083
StatusFinaled
Name IDAHO PROPERTY MAINTENANCE LLC
Site Address 7855 W EMERALD ST
Project NameGolftec Boise
Customer NumberBLD18-03690
ePlanReviewYes
Description
(2 PERMITS FILED UNDER BLD18-03083 IN EPLANREVIEW)(GOLFTECH) This building is NOT fire sprinklered or alarmed. Permit for tenant improvements to an existing 2,159 sq ft tenant space and to expand 177 sq ft into the adjacent tenant space for a total 2,500 sq ft tenant space. Work to include: demo of existing interior non-bearing walls, sinks, and cabinetry; new non-bearing interior walls and doors, putting green, plumbing for drinking fountain and restroom, new ceiling, new lights and electrical, minor mechanical, and new interior finishes in compliance with Ch. 8 of the 2015 IBC. All work to be done per the approved plans and applicable codes and ordinances. **JAR**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Second Notice 2/17/20193/8/2019 DONE
This permit finaled on the web by Will Thomason
First Notice 1/21/20192/7/2019 DONE
mailed 2-11-19
BLD-Final1/11/20191/11/20191/11/2019PPASS
DetailsMike Jordan
Will Phone #: ###-####. Ok for prm occ.
Permanent Occupancy  1/11/2019 DONE
BLD-Final1/9/20191/9/20191/9/2019PPEND
DetailsBrandon Shaw
Need MECh final...
Temp C. of O. is OK...
FIRE-Final Inspection1/8/20191/9/20191/9/2019APASS
DetailsTroy Cobbley
life safety passed
FIRE-Final Inspection1/4/20191/7/20191/7/2019AFAIL
DetailsJim Page
Could not find city approved drawings, emergency illumination for exit discharge needs to be installed on main entry on the north side as well as desiganted exit on the south side. Fire extinguisher needs to be inspected and tagged as well as lowered to below 48 inches to be code compliant.

Phone #: ###-#### Inspection requested via web by Will Thomason
BLD-Final1/4/20191/7/20191/7/2019PCANC
DetailsMike Jordan
Phone #: ###-#### >> Inspection requested via web by Will Thomason
BLD-Ceiling Grid Inspection12/28/201812/28/201812/28/2018PPASS
DetailsBrandon Shaw
Will Phone #: ###-####
BLD-Framing/Rough-in11/19/201811/20/201811/20/2018APASS
DetailsMike Jordan
Phone #: ###-#### Inspection requested via web by Will Thomason. Inteior steel stud framed walls only ok.
BLD-Framing/Rough-in11/19/201811/19/201811/19/2018PNR
DetailsMike Jordan
Phone #: ###-#### Inspection requested via web by Will Thomason. Needs to provide the city approved plans.
Print Occupancy Form  10/29/2018 DONE
Issue PAID IN FULL permit  10/29/2018  
Plan assigned to (JAR)9/1/20189/1/201810/15/2018 DONE
DetailsJulie Romig
10/19 - 4th Rev - 1st Rev Comp - L3 Golftech
Routing - PLAN CHECK10/15/2018 10/15/2018 PASS
DetailsJulie Romig
Routing - Design Review10/15/2018 10/15/2018 PASS
DetailsKatelyn Menuge
Per KayCee CZC18-00237
PLANS/APPL TAKEN TO FRONT DESK  10/15/2018 DONE
Permit Ready to Issue  10/15/2018 DONE
Need- all met
GC Form
Revised Cert of Value
(DO NOT ISSUE WITHOUT BLD18-03690)
Routing - PLAN CHECK10/8/2018 10/10/2018 PASS
DetailsJulie Romig
Passed pending design review approval.
Routing - Design Review10/8/2018 10/8/2018 FAIL
DetailsKatelyn Menuge
Please submit proposal for meeting DR conditions to Design Review Planner KayCee Babb (kbabb@cityofboise.org) and obtain approval prior to resubmitting for building permit.
Routing - PLAN CHECK10/2/2018 10/6/2018 FAIL
DetailsJulie Romig
Routing - Design Review10/2/2018 10/2/2018 FAIL
DetailsKatelyn Menuge
Submit proposal for storefront graphics to Design Review per Zoning Certificate conditions.
Route to Impact Fee Review9/29/201810/2/201810/1/2018 PASS
DetailsEric Bilimoria
Review requested for Commercial Permit
1st review completed  9/29/2018 FAIL
DetailsJulie Romig
Routing - PLAN CHECK9/1/2018 9/29/2018 FAIL
DetailsJulie Romig
Routing - FIRE9/1/20189/1/20189/28/2018 PASS
DetailsErika Akin
Attached comments to case
Routing - PLANNING9/1/2018 9/26/2018 PASS
DetailsKatelyn Menuge
No review required.
Routing - Design Review9/26/2018 9/26/2018 FAIL
DetailsKatelyn Menuge
Update sheets to show north correctly. A Zoning Certificate is required prior to building permit issuance.
Routing - Addressing9/1/2018 9/4/2018 PASS
DetailsDoug Chausow
Routing - PUBLIC WORKS9/1/2018 9/4/2018 PASS
DetailsRachael Beierle
Plan Reviewer's activity  9/1/2018 DONE
Katie, as this is a change in use for this space please contact ACHD to verify if any impact fees are due an provide documentation of fees due or not. If ACHD fees are due provide a receipt of fees paid or fees can be paid at the time of permit issuance. Building permits cannot be issued without documentation of fees or that no fees are due.
Intake Approval  8/28/2018 PASS
Intake Approval  8/24/2018 FAIL
DetailsJoe Bruce
This prescreen has failed due to the following:
1.Drawing files must be uploaded individually and follow the electronic plan submittal standards.
2.Complete and upload form #520 – Major TI Submittal Checklist
3.Provide site specific fire flow at hydrants letter from Suez Water or other public water provider.
4.Provide a key plan on the plans showing the tenant space location within the existing building.
5.Show exit signs and emergency lighting locations on plans.
6.Show portable fire extinguisher locations on plans.
7.Provide mechanical plans if new unit(s) are being installed.
8.Show exhaust fan locations, CFM, for restroom.
Application received  8/23/2018 DONE
Application submitted via PDS Online on Aug 23 2018 3:46PM