Permit Information
Permit NumberBLD18-03106
StatusFinaled
Name BENCHMARK CONSTRUCTION INC
Site Address 3629 S BANNER AVE
Project NameVibraPro2 Paint Booth
Customer Number 
ePlanReviewYes
Description
(VIBRAPRO2) **Permit for installation of a new paint booth and rooftop mechanical unit. Work to include: enclosing a 1,540 sq. ft. portion of a pre-fabricated metal building, installation of a new paint booth, mechanical rooftop unit, and new interior finishes in compliance with Ch. 8 of the 2012 IBC. This building is not Fire Sprinklered. All work to be done per the approved plans and applicable codes and ordinances. **JHB*
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Second Notice 4/18/20194/22/2019 DONE
This permit finaled on the web by Clayn Sonderegger
First Notice3/20/20193/20/20194/8/2019 DONE
DetailsMike Jordan
mailed 4-11-19
BLD-Final3/20/20193/20/20193/20/2019PPASS
DetailsMike Jordan
DOC - Permit Finaled3/20/20193/20/20193/20/2019PPASS
DetailsMike Jordan
BLD-Final3/18/20193/19/20193/19/2019PPEND
DetailsMike Jordan
Ask for Stacie at the front desk. Plans are on the shelf by the new foundation Phone #: ###-#### Inspection requested via web by Clayn Sonderegger. Structural final ok. Will fianl when public works finals, mech and electrical finals.
FIRE-Final Inspection3/18/20193/18/20193/18/2019PPASS
DetailsTroy Cobbley
Life safety passed
FIRE-Final Inspection3/14/20193/15/20193/15/2019AFAIL
DetailsJim Page
Waiting for verification of class 1 wiring and need suppression permit finaled.

Ask for Aaron or Mike at the front desk when you arrive. Phone #: ###-#### Inspection requested via web by Clayn Sonderegger
FIRE-Final Inspection3/13/20193/14/20193/14/2019PFAIL
DetailsTroy Cobbley
Waiting for verification of class 1 wiring and need suppression permit finaled.
FIRE-Final Inspection3/4/20193/5/20193/5/2019AFAIL
DetailsTroy Cobbley
See the city approved notes for items marked that need corrected. Items included exhaust clearance from hvac intake, 3' housekeeping clearance, signage, class 1 electrical and ventilation interlock.....ect.


Plans are on-site. Ask for Stacie at the front desk. Phone #: ###-#### Inspection requested via web by Clayn Sonderegger
BLD-Energy code compliance2/14/20192/15/20192/15/2019APASS
DetailsJim Sly
Plans are on rack by new foundation. Ask for Stacie at the front desk. We infilled the ceiling and exterior walls with insulation. Phone #: ###-#### Inspection requested via web by Clayn Sonderegger
BLD-Final2/14/20192/15/20192/15/2019ANR
DetailsJim Sly
Plans are on rack by new foundation. Ask for Stacie at the front desk. We infilled the ceiling and exterior walls with insulation. Ready for final. Phone #: ###-#### Inspection requested via web by Clayn Sonderegger
Talked to Clayn.........Gave him the list ......For finals to be completed, prior to calling for Structural final.
BLD-Foundation1/28/20191/29/20191/29/2019APASS
DetailsMike Jordan
We have concrete scheduled for 1:00pm. We should have the rebar in place by 10:00am. We do have MTI scheduled for rebar and cylinders, if required. This inspection is for one column footing. Phone #: ###-#### Inspection requested via web by Clayn Sonderegger
Inspection Record Card- Bld  1/16/2019 DONE
Issue PAID IN FULL permit  1/16/2019 DONE
emailed curtis@brsarchitects.com (GC doens't have an email on file) to see if he'll have the GC sign and send back the permit
Plan assigned to (JHB)9/4/20189/4/201811/13/2018 PASS
DetailsJoe Bruce
*(2nd Rev Comp) 09/18 (L2) - VibraPro2 ePlan (Struc)
Routing Off Site - STRUCTURAL11/5/2018 11/13/2018 PASS
DetailsJoe Bruce
AHJ - Dave Haugland
PLANS/APPL TAKEN TO FRONT DESK  11/13/2018 DONE
Permit Ready to Issue  11/13/2018 DONE
MET clayn@benchmarkconstruction.com
NEED
GC FORM
REVISED VALUE
Plan resubmittals received  11/5/2018 DONE
DetailsJoe Bruce
Received additional structural information. **JHB**
Routing - FIRE10/10/201810/10/201810/24/2018 PASS
DetailsErika Akin
Attached revised comments to case
Plan resubmittals requested  10/24/2018 FAIL
DetailsJoe Bruce
Returned to applicant in Eplan. Need Structural info. **JHB**
Routing Off Site - STRUCTURAL10/10/2018 10/22/2018 FAIL
DetailsJoe Bruce
AHJ Engineers - Dave Haugland
Routing - Design Review10/10/2018 10/10/2018 PASS
DetailsKatelyn Menuge
DRH18-00259
Plan resubmittals received  10/9/2018 DONE
Route to Impact Fee Review9/19/20189/22/20189/19/2018 PASS
DetailsEric Bilimoria
Review requested for Commercial Permit
Routing - FIRE9/4/20189/4/20189/19/2018 FAIL
DetailsErika Akin
Attached comments to case and emailed architect
1st review completed  9/19/2018 DONE
DetailsJoe Bruce
Plan resubmittals requested  9/19/2018 DONE
DetailsJoe Bruce
Routing - PLAN CHECK9/4/2018 9/19/2018 PASS
DetailsJoe Bruce
Routing Off Site - STRUCTURAL9/4/2018 9/17/2018 FAIL
DetailsJoe Bruce
Dave Haugland - AHJ Engineers
Routing - Design Review9/4/2018 9/4/2018 FAIL
DetailsKatelyn Menuge
Screening of new mechanical/rooftop equipment is required.
Routing - MECHANICAL9/4/2018 9/4/2018 PASS
DetailsTroy James
Routing - Addressing9/4/2018 9/4/2018 PASS
DetailsDoug Chausow
Routing - PUBLIC WORKS9/4/2018 9/4/2018 PASS
DetailsRachael Beierle
Intake Approval  8/30/2018 PASS
DetailsJavier Guzman
Intake Approval  8/27/2018 FAIL
DetailsJoe Bruce
To complete your application, provide the following:
1. Provide Planning & Zoning Letters of approval
2. Architectural plans must be stamped and signed by an Architect.
3. Provide portable fire extinguisher locations on the plans
4. Provide form #310 Statement of Special Inspections form completed by structural engineer.
5. Each plan must have a space reserved for City approval stamps as specified in the "Electronic Plan Review Submittal Standards" document.
6. Sheet M2 denotes flammable storage cabinets. Please submit a list identifying all expected quantities of hazardous / flammable materials to be stored for this use.
Intake Approval  8/27/2018 FAIL
DetailsJoe Bruce
To complete your application, provide the following:
1. Provide Planning & Zoning Letters of approval
2. Architectural plans must be stamped and signed by an Architect.
3. Provide portable fire extinguisher locations on the plans
4. Provide form #310 Statement of Special Inspections form completed by structural engineer.
5. Each plan must have a space reserved for City approval stamps as specified in the "Electronic Plan Review Submittal Standards" document.
6. Sheet M2 denotes flammable storage cabinets. Please submit a list identifying all expected quantities of hazardous / flammable materials to be stored for this use.
Thank you,
Joe Bruce
Application received  8/24/2018 DONE
Application submitted via PDS Online on Aug 24 2018 2:11PM
Zoning Approval1/31/20191/31/2019  PASS
No inspection required.