Print Occupancy Form | | | 8/8/2019 | | DONE |
|
|
|
|
Print Occupancy Form | | | 8/8/2019 | | DONE |
|
|
|
|
Print Occupancy Form | | | 8/8/2019 | | DONE |
|
|
|
|
Permanent Occupancy | | | 8/8/2019 | | DONE |
|
|
|
|
FIRE-Final Inspection | 7/19/2019 | 7/19/2019 | 7/19/2019 | P | PASS |
Jim Page
|
|
|
Fire sprinkler modifications have been completed (Annual inspection for fire sprinklers is current), no fire alarm modifications, fire extinguishers are placed with current inspection tags, knox box is located by the main entry, refer previous note entered by Joe Bruce for racking, slide bolt on door btween warehouse and sales floor was rem oved at time of inspection. Final life fire safety inspection complete.
tamra Phone #: ###-####
|
Plan Reviewer's activity | | | 7/18/2019 | | DONE |
Joe Bruce
|
|
|
Spoke with Tim (appicant) regarding the steps to finalize this Occupancy Approval Permit. Since racks were installed under the original building constructed 1981, no additional racking permit shall be required to final permit. Verfiied the racking requirement with Assistant Fire Marshall. **JHB**
|
BLD-Aging Inspection | 6/12/2019 | 6/12/2019 | 6/17/2019 | | PEND |
Tony Young
|
|
|
|
BLD-Aging Inspection | 6/11/2019 | 6/11/2019 | 6/12/2019 | | PEND |
Tony Young
|
|
|
|
FIRE-Final Inspection | 2/12/2019 | 2/13/2019 | 2/13/2019 | A | CANC |
Troy Cobbley
|
|
|
I spoke to Tammy about racking permit requirements and that I could not find a fire sprinkler permit for the work done. Will be rescheduled.
Call for Tammy, she has the plans Phone #: ###-####
|
FIRE-Final Inspection | 1/28/2019 | 1/28/2019 | 1/28/2019 | P | FAIL |
Jim Page
|
|
|
Point of contact was not on site when inspection could be performed, spoke with assistant manager on the phone an she did not know where the city approved documentation was, inspection will need to rescheduled.
Tim or Terry @ ###-#### Phone #: ###-####
|
BLD-Final | 1/18/2019 | 1/22/2019 | 1/22/2019 | A | PASS |
Dave Hannah
|
|
|
Terry or ###-#### Tim Phone #: ###-####
|
BLD-Final | 9/10/2018 | 9/17/2018 | 9/17/2018 | P | NR |
Tony Young
|
|
|
Terry //// Or Tim at ###-#### Phone #: ###-####
|
FIRE-Final Inspection | 9/10/2018 | 9/17/2018 | 9/17/2018 | A | FAIL |
Mike Jordan
|
|
|
Terry //// Or Tim at ###-#### Phone #: ###-####. Provide adequate sprinkler head clearancee in warehouse due to fallen insulation. Sprinkler head coverage requirded at overhead door on warehouse to store. rear exits from warehouse is gated and locked. Need to exit to pyblic way. Provide sticker over main exits this door to remain unlocked..... Provide yeraly inspections for fire extinguishers at paints desk and by brroms and gloves. Show the aditional mezzanines in warehouse on the plans and resubmit to plan review or remove. A racking permit is required for the racks over 8ft. in the warehouse. Repair all non functioning emergency lights.
|
Issue PAID IN FULL permit | | | 9/10/2018 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/7/2018 | | DONE |
|
|
|
All met, fees due
|
Print Occupancy Form | | | 9/7/2018 | | DONE |
|
|
|
|
Telephone call | | | 9/7/2018 | | DONE |
|
|
|
Called Richard to advise permit is ready and gave fees due
|
Plan assigned to (BJM) | 8/31/2018 | 8/31/2018 | 9/6/2018 | | DONE |
Brian McGowan
|
|
|
09/07 Occupancy
|
Routing - PLAN CHECK | 8/31/2018 | | 9/6/2018 | | PASS |
Brian McGowan
|
|
|
|
1st review completed | | | 9/6/2018 | | DONE |
Brian McGowan
|
|
|
|
Case Summary (BLD) | | | 9/6/2018 | | DONE |
Brian McGowan
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/6/2018 | | DONE |
Brian McGowan
|
|
|
|
Intake Approval | | | 8/31/2018 | | PASS |
|
|
|
per BJM/CDM
|
Plans ACCEPTED BY PLAN TECH | | | 8/31/2018 | | DONE |
|
|
|
|
First Notice | | 8/18/2019 | | | |
|
|
|
|
Application received | | 8/31/2018 | | | |
|
|
|
|