Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberBLD18-03381
StatusFinaled
Name DATUM CONSTRUCTION MANAGEMENT INC
Site Address 7048 W STATE ST
Project NameNorthgate - Workout Anytime
Customer NumberEARLY START BLD18-04479
ePlanReviewYes
Description
(NORTHGATE SHOPPING CENTER) (WORKOUT ANYTIME) (CZC18-00236) Permit for tenant improvements to an existing 7,015 sq ft retail space within the existing Northgate Shopping Center for a new fitness center. The building was previously a video rental store. Work to include: demo of interior non-structural partitions; minor exterior improvements to storefront; new interior non-bearing walls; exterior doors; restrooms and locker rooms with new plumbing; new ceiling; lighting and power; mechanical including new roof top unit and structural reinforcement of roof; and interior finishes in compliance with Ch. 8 of the 2015 IBC. The fire sprinkler system is used for building area increase and for fire area. Any alterations to the sprinkler system will require a separate permit and shall comply with NFPA 13 as regulated by the fire department. **JAR**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Second Notice 4/18/20195/6/2019 DONE
mailed 5-10-19
First Notice 4/1/20194/8/2019 DONE
mailed 4-11-19
BLD-Final3/22/20193/22/20193/22/2019PPASS
DetailsTony Young
Fire Life Safety final requested.
Final Building inspection requested for late afternoon, after/during Fire Life Safety. Phone #: ###-#### Inspection requested via web by Greg Hedin
FIRE-Final Inspection3/22/20193/22/20193/22/2019PPASS
DetailsJim Page
Previously noted items have been corrected, final life fire safety inspection complete.

Fire Life Safety final requested. Phone #: ###-#### Inspection requested via web by Greg Hedin
Permanent Occupancy  3/22/2019 DONE
BLD-Final3/14/20193/15/20193/15/2019ACANC
DetailsTony Young
Greg Phone #: ###-####
FIRE-Final Inspection3/14/20193/14/20193/14/2019PFAIL
DetailsJim Page
Mag lock access control needs to be integrated with the fire alarm system for door release under general water flow alarm. Ceiling fan on main floor needs to be integrated with the fire alarm panel to shut down on general water flow alarm per manufacture instructions. Provide emergency egress lighting for exit discharge as shown on city approved drawings. Verfiy CFM of newly installed HVAC unit, if unit moves more than 2000CFM then an in-duct smoke detector will be required for unit shutdown. Modifications to the fire alarm system requires a permit.

Greg Phone #: ###-####
BLD-Ceiling Grid Inspection3/5/20193/5/20193/5/2019PPASS
DetailsTony Young
Request ceiling grid inspection for cover, this afternoon. Phone #: ###-#### Inspection requested via web by Greg Hedin
BLD-Framing/Rough-in2/4/20192/5/20192/5/2019PPART
DetailsTony Young
request rough framing inspection for cover. Phone #: ###-#### Inspection requested via web by Greg Hedin,, walls ok
(F) Reprint permit  12/27/2018 DONE
Place hold on job12/26/2018 12/26/2018 DONE
DetailsBrittany Hill
NEED TO PAY $46.31 ON BLD18-04479
***NO INSPECTION ALLOWED UNTIL COMPLETED ^^^^****
Telephone call  12/26/2018 DONE
Spoke with Jim informing him that we still need the 302 and 306 for the early start permit on BLD18-04479 and the fee of $46.31 needs to be paid. State a hold will be put on this permit and no inspection can be called in until those items are sent in and fee paid
Issue PAID IN FULL permit  12/21/2018 DONE
emailed jimraines@datumconstruction.com; keithjones@datumconstruction.com to sign permit
both emails came back so called John-left message on his cell-the other number on file has a mail box that is full-sent Brice the permit to sign and send back 12-27-18 CAN
Print Occupancy Form  12/21/2018 DONE
(F) Reprint permit  12/21/2018 DONE
(F) Reprint permit  12/21/2018 DONE
Plan assigned to (JAR)11/4/201811/4/201812/20/2018 DONE
DetailsJulie Romig
1st Rev Comp - L3 Workout Anytime TI
Routing - PLAN CHECK12/19/2018 12/20/2018 PASS
DetailsJulie Romig
Routing - PLUMBING12/19/2018 12/20/2018 PASS
DetailsDaryl Spivey
Install ASSE 1070 tempering device on lavs per 403.7 ISPC.
PLANS/APPL TAKEN TO FRONT DESK  12/20/2018  
Permit Ready to Issue  12/20/2018 DONE
need:
ACHD
GC - met
Cert. Value- met
Routing - PLAN CHECK12/14/2018 12/19/2018 FAIL
DetailsJulie Romig
Plan review report emailed to applicant
Routing - MECHANICAL12/14/2018 12/18/2018 PASS
DetailsTroy James
Need mechanical Comcheck.
Routing - PLUMBING12/14/2018 12/18/2018 PASS
DetailsDaryl Spivey
1) provide ASSE 1070 tempering device on lavs.
2) May require additional water service protection.
Routing - Design Review12/14/2018 12/17/2018 PASS
DetailsJosh Wilson
Ok per CZC18-00236
Routing - PUBLIC WORKS12/14/2018 12/17/2018 PASS
DetailsMorgan Webb
Route to Impact Fee Review12/3/201812/6/201812/3/2018 PASS
DetailsEric Bilimoria
Review requested for Commercial Permit
Routing - FIRE11/4/201811/4/201812/3/2018 PASS
DetailsErika Akin
Attached comments to case
Routing - PLAN CHECK11/4/2018 11/26/2018 FAIL
DetailsJulie Romig
IBC Plan Review Report emailed to architect.
1st review completed  11/26/2018 FAIL
DetailsJulie Romig
Routing - PLUMBING11/8/2018 11/8/2018 PASS
DetailsDan Ediger
Per plans and ISPC
Routing - PLANNING11/4/2018 11/6/2018 PASS
DetailsLeon Letson
Routing - Design Review11/6/2018 11/6/2018 FAIL
DetailsJosh Wilson
Certificate of Zoning Compliance required for exterior building modifications
Routing - PUBLIC WORKS11/4/2018 11/6/2018 PASS
DetailsAngela Hardy
Routing - Addressing11/4/2018 11/5/2018 PASS
DetailsDoug Chausow
Intake Approval  10/31/2018 PASS
Plan Reviewer's activity  9/19/2018 DONE
DetailsAdele J Schaffeld-Griffin
sending back to pre screen No DR approval
Intake Approval  9/19/2018 FAIL
DetailsMichael Hanson
This permit has failed prescreen due to the following:
1. Provide design review approval letter for exterior modifications.
Application received  9/17/2018 DONE
Application submitted via PDS Online on Sep 17 2018 1:47PM