BLD-Final | 10/16/2019 | 10/16/2019 | 10/16/2019 | P | PASS |
Tell Riley
|
|
|
PAT Phone #: 208-941-829//trades finals complete//all signatures complete//final complete//
|
Zoning Approval | 10/16/2019 | 10/16/2019 | 10/16/2019 | | PASS |
Katelyn Menuge
|
|
|
|
Permanent Occupancy | | | 10/16/2019 | | DONE |
|
|
|
|
BLD-Final | 10/14/2019 | 10/15/2019 | 10/15/2019 | P | CANC |
Tell Riley
|
|
|
Pat Phone #: ###-####
|
PubWorks Occupancy Approval | 10/14/2019 | 10/14/2019 | 10/14/2019 | | DONE |
Tiffany Lowery
|
|
|
|
BLD-Aging Inspection | 10/7/2019 | 10/7/2019 | 10/7/2019 | | PASS |
Tell Riley
|
|
|
working on finishing all permits
|
Temporary Occupancy | 9/25/2019 | 12/24/2019 | 9/25/2019 | | DONE |
Candy A. Nichols
|
|
|
Jason Blais ok'd Temp C of O extension good for 30 days from 9/16/19
|
BLD-Aging Inspection | 8/5/2019 | 8/5/2019 | 8/5/2019 | | PASS |
Tell Riley
|
|
|
|
Temporary Occupancy | 6/18/2019 | 9/16/2019 | 6/18/2019 | | DONE |
Brittany Hill
|
|
|
|
Zoning Approval Temp | 6/13/2019 | 6/13/2019 | 6/13/2019 | | DONE |
Andrea Tuning
|
|
|
Bond has been placed
|
BLD-Final | 6/4/2019 | 6/4/2019 | 6/4/2019 | P | PART |
Tony Young
|
|
|
Bill Phone #: ###-#### temp occ. ok pending trades.
|
FIRE-Final Inspection | 6/3/2019 | 6/4/2019 | 6/4/2019 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed. Life safety/Egress plan provided and letter of intent to be scaned to case file. This life safety plan to be provided by the Apartment Leasing Office to each tenant at move in. Bill Phone #: ###-####
|
FIRE-Final Inspection | 5/28/2019 | 5/29/2019 | 5/29/2019 | A | FAIL |
Troy Cobbley
|
|
|
Need project related fire alarm permit finaled, both fire sprinkler permits finaled, need clarification/add the emergency lighting and additional smoke alarms as per the approved plans and fire dept access implemented as discussed.
Bill Phone #: ###-####
|
BLD-Other | 3/14/2019 | 3/14/2019 | 3/14/2019 | P | PASS |
Jim Sly
|
|
|
RCChannnel inspection- Bill Phone #: ###-####
|
BLD-Energy code compliance | 3/12/2019 | 3/12/2019 | 3/13/2019 | P | PASS |
Jim Sly
|
|
|
Bill Phone #: ###-####
|
BLD-Energy code compliance | 3/11/2019 | 3/11/2019 | 3/11/2019 | P | NR |
Jim Sly
|
|
|
bill Phone #: ###-####
|
BLD-Framing/Rough-in | 3/8/2019 | 3/8/2019 | 3/9/2019 | P | PASS |
Jim Sly
|
|
|
Bill Phone #: ###-####
|
BLD-Wall Bracing | 3/8/2019 | 3/8/2019 | 3/8/2019 | P | PASS |
Jim Sly
|
|
|
Bill Phone #: ###-####
|
BLD-Conference | 3/7/2019 | 3/6/2019 | 3/7/2019 | A | DONE |
Bob Archibald
|
|
|
Review of rated floor/ceiling penetrations.
|
BLD-Framing/Rough-in | 3/5/2019 | 3/5/2019 | 3/5/2019 | P | NR |
Jim Sly
|
|
|
Bill Phone #: ###-#### Need Mech rough in approval.......
|
BLD-Conference | 3/1/2019 | 3/4/2019 | 3/5/2019 | A | CANC |
Jim Sly
|
|
|
Pat Phone #: ###-####
|
BLD-Foundation | 1/9/2019 | 1/10/2019 | 1/10/2019 | P | PASS |
Jim Sly
|
|
|
wall // dane Phone #: ###-####
|
BLD-Footing | 1/8/2019 | 1/9/2019 | 1/10/2019 | P | PASS |
Jim Sly
|
|
|
Dane Phone #: ###-####
|
Print Occupancy Form | | | 1/8/2019 | | DONE |
|
|
|
|
Issue PAID IN FULL permit | | | 1/8/2019 | | DONE |
|
|
|
|
OVERRIDE | | | 1/3/2019 | | |
|
|
|
|
Plan assigned to (JAR) | 11/21/2018 | 11/21/2018 | 1/3/2019 | | DONE |
Julie Romig
|
|
|
1st Rev Comp - 2nd Comp - 506 Farivew Apts Bldg D2
|
Routing - PLAN CHECK | 1/3/2019 | | 1/3/2019 | | PASS |
Julie Romig
|
|
|
Form 310 Deferred. Special Inspections required for post installed anchors into concrete if used.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/3/2019 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 1/3/2019 | | DONE |
|
|
|
need - met
Revised Cert of Value (need correct address)
MET
ACHD
GC Form (need an updated form)-met
|
Routing - PLAN CHECK | 12/14/2018 | | 12/21/2018 | | FAIL |
Julie Romig
|
|
|
|
Routing Off Site - STRUCTURAL | 12/14/2018 | | 12/21/2018 | | PASS |
Julie Romig
|
|
|
AHJ
|
Routing - PLANNING | 12/14/2018 | | 12/18/2018 | | PASS |
Nicolette Womack
|
|
|
|
Routing - PLANNING | 10/12/2018 | | 12/18/2018 | | PASS |
Susan Riggs
|
|
|
|
Route to Impact Fee Review | 11/21/2018 | 11/24/2018 | 11/23/2018 | | PASS |
Eric Bilimoria
|
|
|
Review requested for Commercial Permit
|
Plan assigned to (JG) | 10/12/2018 | 10/12/2018 | 11/21/2018 | | DEFR |
Javier Guzman
|
|
|
11/08 Fairview Apartments New ePlan
|
Routing - PLAN CHECK | 10/12/2018 | | 11/21/2018 | | FAIL |
Julie Romig
|
|
|
|
1st review completed | | | 11/21/2018 | | FAIL |
Julie Romig
|
|
|
|
Routing - FIRE | 10/12/2018 | 10/12/2018 | 11/20/2018 | | PASS |
Erika Akin
|
|
|
Attached comments to case
|
Routing Off Site - STRUCTURAL | 10/12/2018 | | 10/25/2018 | | FAIL |
Julie Romig
|
|
|
AHJ
|
Routing - MECHANICAL | 10/12/2018 | | 10/23/2018 | | PASS |
Troy James
|
|
|
|
Routing - PLUMBING | 10/12/2018 | | 10/16/2018 | | PASS |
Dan Ediger
|
|
|
Per ISPC. See redline note
|
Routing - Erosion and Sediment | 10/12/2018 | | 10/16/2018 | | PASS |
Andy J. Long
|
|
|
SWPPP approved. Valid stormwater team designated. Site already started under GRD18-00035, no site prep required.
|
Routing - Design Review | 10/12/2018 | | 10/15/2018 | | PASS |
Andrea Tuning
|
|
|
|
Routing PW Drainage | 10/15/2018 | | 10/15/2018 | | PASS |
Brian Murphy
|
|
|
|
Routing PW Street Lights | 10/15/2018 | | 10/15/2018 | | PASS |
Tom Marshall
|
|
|
Street lights will be tracked on this case.
|
Routing PW Sewer Design | 10/15/2018 | | 10/15/2018 | | PASS |
DeAnn Brown
|
|
|
|
Routing PW Solid Waste | 10/15/2018 | | 10/15/2018 | | PASS |
Evan Carpenter
|
|
|
|
Routing - Addressing | 10/12/2018 | | 10/15/2018 | | PASS |
Doug Chausow
|
|
|
Address changed to 11740 W King St
Parcel # updated to: S1103336611
|
Routing - PUBLIC WORKS | 10/12/2018 | | 10/15/2018 | | PASS |
Morgan Webb
|
|
|
|
Intake Approval | | | 10/12/2018 | | PASS |
|
|
|
|
Intake Approval | | | 10/11/2018 | | FAIL |
Joe Bruce
|
|
|
Jeremy, There are just a few additional sheets that need the space reserved for the stamp that look like they were missed.
This document on our website illustrates these requirements: https://pds.cityofboise.org/media/464072/pdox86_electronic_standards_full_050718.pdf
1) Drawing sheets (C1.0, EC-101, A-103, S-105.10, and SE-1) do not have required space reserved for City approval stamps as specified in the Electronic Plans Submittal Standards. Revise sheets with a blank 4” x 2” space located 3” off the right sheet edge to allow for the title block. Verify all sheets have the required space for city approval stamp.
|
Intake Approval | | | 9/25/2018 | | FAIL |
Joe Bruce
|
|
|
Provide the following items to complete the prescreen process:
1) Missing stamped/signed Structural Calculations. Provide per checklist.
2) Missing Special Inspections (Form #310) Provide per checklist.
3) Drawing sheets do not have required space reserved for City approval stamps as specified in the Electronic Plans Submittal Standards. Revise sheets with a blank 4” x 2” space located 3” off the right sheet edge to allow for the title block. Verify all sheets have the required space for city approval stamp. Cover sheet needs a 4"x4" space.
4) Portions of interior finish schedule appear to be missing - Sheet A-105
5) It's unclear who signed the Structural Sheets since the engineer and architect stamp overlap. Provide a clear engineer stamp/signature on the structural drawings.
6) REScheck Building Envelope Compliance Certificate utilizes the 2012 IECC. The City of Boise has adopted the 2015 IECC. Revise the Compliance Certificate with current code. - Sheet G-6
|
Application received | | | 9/23/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Sep 23 2018 12:55AM
|
First Notice | | 10/26/2019 | | | |
|
|
|
|