Permit Information
Permit NumberBLD18-03486
StatusFinaled
Name BILTMORE COMPANY
Site Address 11703 W KING ST
Project NameFairview Apartments - Bldg D3
Customer Number 
ePlanReviewYes
Description
(FAIRVIEW APARTMENTS) (BLDG D3) (DRH17-00532) (GRD18-00035) Permit for the construction of Building D3, a 8,737 sq ft, 2-story, 8-unit apartment building. This building is one of six buildings within a multi-family development, which includes (3) three-story, 24-unit multi-family buildings and (3) two-story, 8-unit buildings for a total of 96 units on the site. Work to include general site work and the construction of the new building per the approved plans. Special inspections are required for post installed anchors into concrete when used per Sheet S-001.1 and Form 310. All buildings are to be fully fire sprinklered with an NFPA 13-R system as required for residential occupancy and story increase. **JAR**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final10/16/201910/16/201910/16/2019PPASS
DetailsTell Riley
PAT Phone #: ###-####//all trades passed and life safety//all signatures required complete//final complete//
Zoning Approval10/16/201910/16/201910/16/2019 PASS
DetailsKatelyn Menuge
Permanent Occupancy  10/16/2019 DONE
BLD-Final10/14/201910/15/201910/15/2019PCANC
DetailsTell Riley
Pat Phone #: ###-####
FIRE-Final Inspection10/14/201910/15/201910/15/2019APASS
DetailsTroy Cobbley
Life safety passed. Phone #: ###-####
PubWorks Occupancy Approval10/14/201910/14/201910/14/2019 DONE
DetailsTiffany Lowery
BLD-Aging Inspection9/16/20199/16/20199/16/2019 PASS
DetailsTell Riley
WIP....
Temporary Occupancy7/18/201910/16/20197/18/2019 DONE
DetailsBrittany Hill
PubWorks Temp Occupancy Appr7/18/20197/18/20197/18/2019 DONE
DetailsTiffany Lowery
PubWorks Temp Occupancy Appr7/18/20197/18/20197/18/2019 DONE
DetailsBrian Murphy
per brian murphy bond is in place.
BLD-Final7/16/20197/16/20197/16/2019PPASS
DetailsTell Riley
Bill Phone #: ###-####//corrections made//ok for temp occupancy//
Zoning Approval Temp7/11/20197/11/20197/11/2019 DONE
DetailsAndrea Tuning
BLD-Final7/10/20197/10/20197/10/2019PFAIL
DetailsTell Riley
Matt Phone #: ###-####//need to seal penetrations in storage rooms//label fire riser room//anchor railings at stairway//will call for re-isnpection//
BLD-Energy code compliance4/3/20194/4/20194/4/2019APASS
DetailsJim Sly
Bill Phone #: ###-####
BLD-Framing/Rough-in4/1/20194/1/20194/1/2019PPASS
DetailsJim Sly
Bill Phone #: ###-####
BLD-Wall Bracing3/19/20193/19/20193/19/2019PPASS
DetailsJim Sly
Bill Phone #: ###-####
BLD-Foundation1/16/20191/17/20191/17/2019PPASS
DetailsJim Storey
Dane Phone #: ###-####
BLD-Footing1/15/20191/16/20191/16/2019PPASS
DetailsJim Sly
Dean Phone #: ###-####
BLD-Footing1/14/20191/15/20191/16/2019PCANC
DetailsJim Sly
Dean Phone #: ###-####
Issue PAID IN FULL permit  1/11/2019 DONE
emailed Jeremy the permits to sign and send back
Print Occupancy Form  1/11/2019 DONE
OVERRIDE  1/3/2019  
Plan assigned to (JAR)10/12/201810/12/20181/3/2019 DONE
DetailsJulie Romig
1st Rev Comp - 2nd Comp - 506 Fairview Apts Bldg D3
Routing - Addressing10/12/2018 1/3/2019 PASS
DetailsDoug Chausow
Routing - PLAN CHECK1/3/2019 1/3/2019 PASS
DetailsJulie Romig
Form 310 Deferred. Special Inspections required for post installed anchors into concrete if used.
PLANS/APPL TAKEN TO FRONT DESK  1/3/2019 DONE
Permit Ready to Issue  1/3/2019 DONE
need
Revised Cert of Value (need correct address)
MET
ACHD
GC Form (need an updated form)
Routing - PLANNING12/14/2018 12/21/2018 PASS
DetailsLeon Letson
Routing Off Site - STRUCTURAL12/14/2018 12/21/2018 PASS
DetailsJulie Romig
Routing - PLAN CHECK12/14/2018 12/20/2018 FAIL
DetailsJulie Romig
Routing - PLANNING10/12/2018 12/14/2018 FAIL
DetailsLeon Letson
Bond must be recorded for sidewalks, landscaping, amenities before building permits can be issued.
Route to Impact Fee Review11/21/201811/24/201811/23/2018 PASS
DetailsEric Bilimoria
Review requested for Commercial Permit
Routing - PLAN CHECK10/12/2018 11/21/2018 FAIL
DetailsJulie Romig
1st review completed  11/21/2018 FAIL
DetailsJulie Romig
Routing - FIRE10/12/201810/12/201811/20/2018 PASS
DetailsErika Akin
Attached comments to case
Routing Off Site - STRUCTURAL10/12/2018 10/25/2018 FAIL
DetailsJulie Romig
AHJ
Routing - MECHANICAL10/12/2018 10/23/2018 PASS
DetailsTroy James
Routing - PLUMBING10/12/2018 10/16/2018 PASS
DetailsDan Ediger
Per ISPC. See redline note
Routing - Erosion and Sediment10/12/2018 10/16/2018 PASS
DetailsAndy J. Long
SWPPP approved. Valid stormwater team designated. Site already started under GRD18-00035, no site prep required.
Routing - PUBLIC WORKS10/12/2018 10/15/2018 PASS
DetailsMorgan Webb
Routing PW Drainage10/15/2018 10/15/2018 PASS
DetailsBrian Murphy
Routing PW Street Lights10/15/2018 10/15/2018 PASS
DetailsTom Marshall
Street lights being tracked under BLD18-03485.
Routing PW Sewer Design10/15/2018 10/15/2018 PASS
DetailsDeAnn Brown
Routing PW Solid Waste10/15/2018 10/15/2018 PASS
DetailsEvan Carpenter
Routing - Design Review10/12/2018 10/15/2018 PASS
DetailsAndrea Tuning
Intake Approval  10/12/2018 PASS
Intake Approval  9/25/2018 FAIL
DetailsJoe Bruce
Provide the following items to complete the prescreen process:
1) Missing stamped/signed Structural Calculations. Provide per checklist.
2) Missing Special Inspections (Form #310) Provide per checklist.
3) Drawing sheets do not have required space reserved for City approval stamps as specified in the Electronic Plans Submittal Standards. Revise sheets with a blank 4” x 2” space located 3” off the right sheet edge to allow for the title block. Verify all sheets have the required space for city approval stamp. Cover sheet needs a 4"x4" space.
4) Portions of interior finish schedule appear to be missing - Sheet A-105
5) It's unclear who signed the Structural Sheets since the engineer and architect stamp overlap. Provide a clear engineer stamp/signature on the structural drawings.
6) REScheck Building Envelope Compliance Certificate utilizes the 2012 IECC. The City of Boise has adopted the 2015 IECC. Revise the Compliance Certificate with current code. - Sheet G-6
Application received  9/23/2018 DONE
Application submitted via PDS Online on Sep 23 2018 1:00AM
First Notice 10/26/2019