Permit Information
Permit NumberBLD18-03563
StatusFinaled
Name ARBOR FINISH CARPENTRY INC
Site Address 204 N CAPITOL BLVD
Project NameRammaPong
Customer Number 
ePlanReviewYes
Description
(RAMMAPONG – BASEMENT BAR, RESTAURANT, AND PING PONG – NORTHWEST CORNER) The fire sprinkler system is used to substitute for 1-hr construction. To remodel an existing 1,700 square foot area in the basement of the Adelmann Building for a bar and restaurant tenant with ping pong tables. Work is to include a new interior entry stairway with guards and handrails, a fixed bench, a 3 riser stairway to access elevated seating, a bar, an elevated floor area behind the bar served by a ramp, tables, chairs, and finishes. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Second Notice 6/17/20197/10/2019 DONE
mailed 7-11
Telephone call  6/14/2019 DONE
Left a message to Chris at ###-#### to get an updated address for Arbor Finish Carpentry because the 1st notice for final request was returned to us.
First Notice 6/1/20196/7/2019 DONE
mailed 6-10
Print Occupancy Form  5/22/2019 DONE
BLD-Final5/7/20195/9/20195/9/2019PPASS
DetailsJim Sly
Call Chris Eby (General Contractor) 30 minutes prior to inspection. Phone #: ###-#### Inspection requested via web by Chris Eby
FIRE-Final Inspection5/9/20195/9/20195/9/2019PPASS
DetailsTroy Cobbley
Life safety passed. Corrections have been addressed. Chris Phone #: ###-####
Per Troy N/A for fire Alarm & Sprinkle work
FIRE-Final Inspection5/7/20195/9/20195/9/2019AFAIL
DetailsTroy Cobbley
Provide small documents, provide annual inspection for Kitchen Hood suppression system, remove doors as discussed between dining area and kitchen, remove lever hardware or provide panic on the doors between the kitchen and the rear exit corridor, provide verification of annual inspection for the fire sprinkler system.

Call Chris Eby (General Contractor) 30 minutes prior to inspection. Phone #: ###-#### Inspection requested via web by Chris Eby
Print Occupancy Form  3/7/2019 DONE
Issue PAID IN FULL permit  3/7/2019 DONE
Expiration Notice3/6/20193/27/20193/6/2019 DONE
DetailsBrittany Hill
Route to Impact Fee Review3/1/20193/4/20193/4/2019 PASS
DetailsKarina Myles
Review requested for Commercial Permit
Plan assigned to (CJW)2/7/20192/7/20193/4/2019 PASS
DetailsCarl Westfall
(1st done) 02/22/19 (L3 - 15 days) (ePlan - 5 sheets) Ramma Pong (l-3) (routed back to applicant)
Plan resubmittals received  3/4/2019 DONE
Routing - PLAN CHECK3/4/2019 3/4/2019 PASS
DetailsCarl Westfall
2nd IBC plan review approved
PLANS/APPL TAKEN TO FRONT DESK  3/4/2019 DONE
Permit Ready to Issue  3/4/2019 DONE
MET MIRA@RAMAPONG.COM
Need gc
need rev cert of val
Routing - PLAN CHECK2/7/2019 3/1/2019 FAIL
DetailsCarl Westfall
1st review completed  3/1/2019 DONE
Plan resubmittals requested  3/1/2019 DONE
Routing - FIRE2/7/20192/7/20192/28/2019 PASS
DetailsMark Scharfen
IFC Fire Code Review 02.28.2019.pdf uploaded.
Routing - PUBLIC WORKS2/7/2019 2/13/2019 PASS
DetailsMorgan Webb
Routing PW Environmental2/8/2019 2/13/2019 PASS
DetailsRick Christenson
Routing - MECHANICAL2/7/2019 2/11/2019 PASS
DetailsTroy James
Field verify.
Routing - PLANNING2/7/2019 2/11/2019 PASS
DetailsNicolette Womack
No exterior modifications approved.
Routing - Addressing2/7/2019 2/8/2019 PASS
DetailsDoug Chausow
Corrected address to match drawings.
Routing - PLUMBING2/8/2019 2/8/2019 PASS
DetailsDaryl Spivey
All fixtures to drain seperately to floor sink and increase water pipe sizing to 3/4 inch. Ice maker may require backflow protection.
Intake Approval  2/4/2019 PASS
Intake Approval  1/24/2019 FAIL
DetailsJoe Bruce
1) Sheets do not have the required space reserved for City approval stamps as specified in the Electronic Plans Submittal Standards. Revise sheets with a blank 4” x 2” space (4"x4" on the cover sheet) located 3” off the right sheet edge to allow for the title block. Submittal requirements can be found at: https://pds.cityofboise.org/media/464072/pdox86_electronic_standards_full_050718.pdf
2) RESOLVED - Upload a current Central District Health Dept. plan review form. The uploaded form is from 6/1/16 and is no longer current. CDHD will need to review the current plans. A food menu will also be required to be uploaded for public works approval.
3) RESOLVED - The required plumbing fixtures are existing, but no plumbing fixture calculations were provided showing how the existing occupants and the new added occupant load will adequately serve the occupant load. Provide the plumbing fixture calculation for all occupants on the plans per IBC table 2902.1.
4) No fire resistive details provided on sheet A2.1 per checklist. It appears from the plans that new lighting is being installed in the rated floor/ceiling assembly. Provide details for all penetrations in the rated floor/ceiling assembly.
5) RESOLVED - Provide mechanical plans & calculations showing the increase demand for fresh air. The occupant load is being significantly increased and additional fresh air ventilation will need to be provided per checklist.
6) Provide plumbing plans with all required elements on the checklist. Several plumbing fixtures are being added. Since this is a food service occupancy, these plans will be required to be stamped by an engineer unless the applicant gets prior approval to have the architect stamp the plumbing plans.
7) Sheet index is incorrect and does not include the newly added mechanical plan. Revised cover sheet to include all sheets in plan set.
Intake Approval  10/12/2018 FAIL
DetailsJoe Bruce
1) Sheets do not have the required space reserved for City approval stamps as specified in the Electronic Plans Submittal Standards. Revise sheets with a blank 4” x 2” space (4"x4" on the cover sheet) located 3” off the right sheet edge to allow for the title block. Submittal requirements can be found at: https://pds.cityofboise.org/media/464072/pdox86_electronic_standards_full_050718.pdf
2) Upload a current Central District Health Dept. plan review form. The uploaded form is from 6/1/16 and is no longer current. CDHD will need to review the current plans. A food menu will also be required to be uploaded for public works approval.
3) The required plumbing fixtures are existing, but no plumbing fixture calculations were provided showing how the existing occupants and the new added occupant load will adequately serve the occupant load. Provide the plumbing fixture calculation for all occupants on the plans per IBC table 2902.1.
4) No fire resistive details provided on sheet A2.1 per checklist. It appears from the plans that new lighting is being installed in the rated floor/ceiling assembly. Provide details for all penetrations in the rated floor/ceiling assembly.
5) Provide mechanical plans & calculations showing the increase demand for fresh air. The occupant load is being significantly increased and additional fresh air ventilation will need to be provided per checklist.
6) Provide plumbing plans with all required elements on the checklist. Several plumbing fixtures are being added. Since this is a food service occupancy, these plans will be required to be stamped by an engineer unless the applicant gets prior approval to have the architect stamp the plumbing plans.
Application received  9/27/2018 DONE
Application submitted via PDS Online on Sep 27 2018 8:52AM