Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberBLD18-03669
StatusFinaled
Name ACCURATE CORPORATE IMAGES INC
Site Address 6663 S EISENMAN RD Unit: 110
Project NameRacking - Romanoff Renovations
Customer Number 
ePlanReviewYes
Description
(ROMANOFF RENOVATIONS SUITE #110 **RACKING**) Permit to add storage racking for carpet rolls and carpet padding rolls. Work to include: Installation of prefabricated 16 ft tall storage racking including seismic bolting to slab for all racking. Anticipated maximum storage height to be 16 feet. Tenant Permit under BLD18-03110. Approval of this permit is contingent on adhering to approved plans and engineering. The design, testing and utilization of industrial steel storage racks shall be in accordance with the RMI Specification for the Design, Testing and Utilization of Industrial Steel Storage Racks. Special inspections required per attached form 310. The structural design by Rack Design and Engineering Co. is attached. This is a fully fire sprinklered building. Any alterations to the sprinkler system will require a separate permit and shall comply with NFPA 13 as regulated by the fire department. **MDH**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice 2/12/20193/7/2019 DONE
mailed 3-11
Second Notice 1/17/20192/7/2019 DONE
mailed 2-11-19
First Notice12/18/201812/18/20181/7/2019 DONE
DetailsJim Sly
MAILED 1-11-19
BLD-Final12/17/201812/18/201812/18/2018PPASS
DetailsJim Sly
Joe Phone #: ###-####
AllWest special inspection approved.
DOC - Permit Finaled12/18/201812/18/201812/18/2018PPASS
DetailsJim Sly
FIRE-Final Inspection12/17/201812/18/201812/18/2018APASS
DetailsJim Page
Final life fire safety inspection for racking permit complete.

Joe Phone #: ###-####
Inspection Record Card- Bld  12/14/2018 DONE
Issue PAID IN FULL permit  12/14/2018 DONE
Routing - FIRE12/10/201812/10/201812/10/2018 PASS
DetailsErika Akin
Attached comments to case
PLANS/APPL TAKEN TO FRONT DESK  12/10/2018 DONE
DetailsMichael Hanson
Permit Ready to Issue  12/10/2018 DONE
Need:- all met
Certificate of Value- met
Verify GC, form in ePlan, but name not listed anywhere on app
Plan assigned to (M_H)11/4/2018 12/10/2018 DONE
DetailsMichael Hanson
11/21 #516 L2 ePlan. 1st review completed - See fire plan review for corrections. MDH
Routing - FIRE11/4/201811/4/201811/19/2018 FAIL
DetailsErika Akin
Attached comments to case and emailed applicant
1st review completed  11/19/2018 DONE
DetailsMichael Hanson
CHANGE STATUS TO (REV)  11/15/2018 DONE
status was changed to FEE by mistake
Routing - PLAN CHECK11/4/2018 11/15/2018 PASS
DetailsMichael Hanson
Intake Approval  11/2/2018 PASS
Intake Approval  10/17/2018 FAIL
DetailsJoe Bruce
1) Missing owner's signature on form #310. Have the owner sign the form and upload.
2) Pages noting the required special inspections are missing on form #310. Fill out the entire special inspections form #310 and upload.
2) Signature on form #304 does not appear to be the owner's signature. If an authorized owner's agent/representative is signing the form, they must be identified on the form. Provide a valid signature on this form and upload.
3) Missing form #302 Contractor Registration Declaration form.
4) Missing the ICC-ES Evaluation Services Reports for the concrete anchors specified. Upload the ESR reports noted on the plans and calculations (ESR-2818) into the documents folder.
5) Site plan does not identify the existing/new fire hydrant locations. Note their locations on the site plan.
6) Identify the required special inspections on Details 1 of 1.
Application received  10/4/2018 DONE
Application submitted via PDS Online on Oct 4 2018 1:47PM