Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberBLD18-03877
StatusTemporary Occupancy
Name WRIGHT BROTHERS THE BLDG CO EAGLE
Site Address 2162 E SUMMERSWEET DR
Project NameFalcon One Storage Condos #1
Customer NumberBLD18-04070-04076,19-00314-00317
ePlanReviewYes
Description
(FALCON ONE STORAGE CONDOS) (BUILDING # 1) (12 PERMITS FILED UNDER BLD18-03877) **PLAN MODIFICAITON 6-21-19, TO SWITCH FROM LIGHT GAUGE METAL FRAMING TO A PRE-FABRICATED METAL BUILDING** Permit is for Building #1A that totals 5,197 SF with (4) four storage units and the construction of the 658 sq. ft. clubhouse with two single user restrooms. There is a total of 8 storage building areas located on a single parcel. The entire scope of work includes construction of 12 individual storage buildings with a total of 107 storage units, a 658 sq. ft. clubhouse space with two single user restrooms, and a small counter with a sink. These buildings are not fire sprinklered. The buildings are divided into fire areas that shall not exceed 12,000 sq. ft. Special inspections required per attached Form 310. Approval is contingent upon adhering to the approved plans on file and attached engineering. **JHB**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Aging Inspection8/3/20208/3/20208/3/2020 PASS
DetailsJim Storey
Change Expiration Date Only  7/14/2020 DONE
BLD-Aging Inspection6/1/20206/1/20206/1/2020 PASS
DetailsJim Storey
Zoning Approval4/28/20204/28/20204/28/2020 PASS
DetailsKatelyn Menuge
BLD-Aging Inspection3/30/20203/30/20203/30/2020 PASS
DetailsJim Storey
Temporary Occupancy1/30/20204/29/20201/30/2020 DONE
DetailsGemma Flores
BLD-Final1/28/20201/29/20201/29/2020PPASS
DetailsJim Storey
I have fire life and safety also scheduled for the afternoon. Phone #: ###-#### Inspection requested via web by chad stradley final ok pending others
FIRE-Final Inspection1/28/20201/29/20201/29/2020PPASS
DetailsTroy Cobbley
Life safety passed for Bldg #1/Club House.

Final inspection is also scheduled for today. We should be ready anytime. Phone #: ###-#### Inspection requested via web by chad stradley
BLD-Ceiling Grid Inspection1/23/20201/24/20201/24/2020PPASS
DetailsJim Storey
ACT inspection at the clubhouse. Phone #: ###-#### Inspection requested via web by chad stradley ok pending ele
BLD-Framing/Rough-in1/2/20201/3/20201/3/2020APASS
DetailsJim Storey
exterior framing inspection Phone #: ###-#### Inspection requested via web by chad stradley c/n perviously table 602 not a issue.
BLD-Framing/Rough-in12/20/201912/23/201912/23/2019AFAIL
DetailsMike Jordan
Clubhouse framing. Phone #: ###-#### Inspection requested via web by chad stradley. Noted Type II construction. exterior OSB and wood siding does not meet criteria for type II construction.
BLD-Framing/Rough-in12/18/201912/19/201912/19/2019PCANC
DetailsTell Riley
clubhouse framing inspection. Phone #: ###-#### >> Inspection requested via web by chad stradley Inspection cancelled from web by: chad stradley
BLD-Framing/Rough-in11/26/201911/27/201911/27/2019APART
DetailsDave Hannah
Cody Phone #: ###-#### bldg 1a south end ok to insulate
Zoning Approval Temp10/18/201910/18/201910/18/2019 DONE
DetailsKatelyn Menuge
BND19-00190
BLD-Footing8/14/20198/19/20198/19/2019PPASS
DetailsBrandon Shaw
rebar inspection for rest of building 1A.
Work in progress...
BLD-Footing8/12/20198/13/20198/13/2019PPART
DetailsTell Riley
rebar inspection for clubhouse. would like to have inspection done at 2pm they would like to pour at 2:30 PM Phone #: ###-#### Inspection requested via web by chad stradley//club house footings ok per plans//pending special inspections//rebar installed per plans//
BLD-Footing8/9/20198/12/20198/12/2019PCANC
DetailsJim Storey
rebar inspection for footer at clubhouse. We want to pour at 230 if we could get inspection at 2 pm that would be great. Phone #: ###-#### >> Inspection requested via web by chad stradley Inspection cancelled from web by: chad stradley
BLD-Footing8/8/20198/9/20198/8/2019PCANC
DetailsJim Storey
Rebar inspection for footer Phone #: ###-#### >> Inspection requested via web by chad stradley Inspection cancelled from web by: chad stradley
Change Expiration Date Only  7/17/2019 DONE
permit reissued by mistake on 7/16/19
Print Occupancy Form  7/16/2019 DONE
CHANGE STATUS TO (ISS)  7/16/2019 DONE
Permit Ready to Issue  7/15/2019 DONE
DO NOT REISSUE - PLAN MOD
Plan assigned to (JHB)6/13/20196/13/20197/12/2019 PASS
DetailsJoe Bruce
(plan mod) Falcon One, Bldg 1A
Routing Off Site - STRUCTURAL7/11/2019 7/12/2019 PASS
DetailsJoe Bruce
Plan resubmittals received  7/11/2019 DONE
DetailsJoe Bruce
Plan resubmittals requested  7/8/2019 DONE
DetailsJoe Bruce
Emailed structural comments to architect.
Routing - PLAN CHECK6/19/2019 7/8/2019 PASS
DetailsJoe Bruce
Received revised foundation drawings showing office foundation.
Routing Off Site - STRUCTURAL6/21/2019 7/3/2019 FAIL
DetailsJoe Bruce
Plan Modification Accepted  6/13/2019 DONE
Plan mod accepted in e plan-changing footing & framing design -assigned to Joe B
Meeting  3/22/2019 DONE
Plan mod started in e plan-changing buildings design including footing and framing design for building 7, 8A & 8B - sheets-permit numbers BLD18-04075 BLD18-04076 & BLD19-00317. 3 plan mod apps uploaded in e plan for review-assigned to Joe B
Telephone call  3/21/2019 DONE
plan mod request came in but they need to resubmitt using 1 plan mod app for each permit-emailed Matt back letting him know
Issue PAID IN FULL permit  2/13/2019  
Print Occupancy Form  2/13/2019 DONE
CHANGE ISSUED DATE  2/13/2019 DONE
permit reissued by mistake on 7/16/19
Permit Ready to Issue  2/12/2019 DONE
met
Revised Value- (for each building)

(DO NOT ISSUE WITHOUT ALL PERMITS, BLD18-03877, BLD18-04070 TO BLD18-04076, BLD19-00314 TO BLD19-000317)

All met -
Need GC
Need ACHD
Plan assigned to (JHB)11/14/201811/14/20182/11/2019 PASS
DetailsJoe Bruce
(3rd Rev Comp) 12/07 - (502) Falcon One Storage Condos Bldg 1(A) (Struc, Sewer)
Routing Off Site - STRUCTURAL2/8/2019 2/11/2019 PASS
DetailsJoe Bruce
PLANS/APPL TAKEN TO FRONT DESK  2/11/2019 DONE
Plan resubmittals received  2/8/2019 DONE
DetailsJoe Bruce
Plan resubmittals requested  2/6/2019 FAIL
DetailsJoe Bruce
Structural resubmittal required.
Routing Off Site - STRUCTURAL1/30/2019 2/6/2019 FAIL
DetailsJoe Bruce
See structural comment in the Agency Comments folder for remaining issue to address. Provide a complete written response outlining the analysis method you are taking responsibility for.
Routing PW Sewer Design1/30/2019 1/30/2019 PASS
DetailsDeAnn Brown
Plan resubmittals requested  1/30/2019 FAIL
DetailsJoe Bruce
PW Sewer and Structutral have additional comments. **JHB**
Plan resubmittals received  1/30/2019 DONE
DetailsJoe Bruce
Routing - FIRE1/17/20191/17/20191/29/2019 PASS
DetailsErika Akin
Attached comments to case
Routing Off Site - STRUCTURAL1/17/2019 1/28/2019 FAIL
DetailsJoe Bruce
AHJ
Routing - PLAN CHECK1/17/2019 1/28/2019 PASS
DetailsJoe Bruce
Routing PW Sewer Design1/17/2019 1/23/2019 FAIL
DetailsDeAnn Brown
Sewer service plan alteration is not allowed per the IDEQ and Plumbing Bureau MOU. Please review changemarks and revise.
Routing - Design Review1/17/2019 1/18/2019 PASS
DetailsKatelyn Menuge
Plan resubmittals received  1/17/2019 DONE
DetailsJoe Bruce
Plan Reviewer's activity  1/16/2019 DONE
DetailsJoe Bruce
Had applicant upload corrected resubmittal drawings with architect stamp, city approval stamp area, and remove NOT FOR PERMIT language from drawings. **JHB**
Plan Reviewer's activity  1/15/2019 FAIL
DetailsJoe Bruce
The resubmittal is being returned for the following reasons:
1) Provide a stamped, signed and dated by the Idaho licensed architect all plan sheets and remove the “NOT FOR PERMIT” statement.
2) Uploaded sheets shall have the same filename in order to overwrite the prior sheets. Several plan sheets are not named correctly and need to be revised.
3) Sheets that have been resubmitted are missing the required space reserved for City approval stamps as specified in the Electronic Plans Submittal Standards. Revise sheets with a blank 4” x 2” (4"x4" on cover) space located 3” off the right sheet edge to allow for the title block. Verify ALL plan sheets have the required space for city approval stamp.
Plan resubmittals received  1/15/2019 FAIL
DetailsJoe Bruce
Route to Impact Fee Review12/12/201812/15/201812/12/2018 PASS
DetailsEric Bilimoria
Review requested for Commercial Permit
Routing - FIRE11/14/201811/14/201812/12/2018 FAIL
DetailsErika Akin
Attached comments to case and emailed architect
1st review completed  12/12/2018 FAIL
DetailsJoe Bruce
Plan resubmittals requested  12/12/2018 DONE
DetailsJoe Bruce
Routing - PLAN CHECK11/14/2018 12/7/2018 FAIL
DetailsJoe Bruce
Routing Off Site - STRUCTURAL11/14/2018 11/29/2018 FAIL
DetailsJoe Bruce
AHJ - Dave Haugland
Routing - MECHANICAL11/14/2018 11/26/2018 PASS
DetailsChad Schwendiman
Routing PW Drainage11/14/2018 11/20/2018 PASS
DetailsBrian Murphy
plan mod
Routing - PLUMBING11/14/2018 11/19/2018 PASS
DetailsDan Ediger
Per ISPC and Plans. See notes
Routing - Design Review11/14/2018 11/16/2018 FAIL
DetailsKatelyn Menuge
See Changemarks
Routing - PLANNING11/14/2018 11/15/2018 PASS
DetailsLeon Letson
Storage is an allowed use in the M-1D zone.
Routing PW Street Lights11/14/2018 11/15/2018 PASS
DetailsTom Marshall
Routing PW Sewer Design11/14/2018 11/15/2018 FAIL
DetailsDeAnn Brown
Please add tap permit language described in changemarks.
Routing PW Solid Waste11/14/2018 11/14/2018 PASS
DetailsEvan Carpenter
Routing - Addressing11/14/2018 11/14/2018 PASS
DetailsDoug Chausow
Facility address: 2140 E Summerset Dr
Routing - PUBLIC WORKS11/14/2018 11/14/2018 PASS
DetailsAngela Hardy
Routing - Erosion and Sediment11/14/2018 11/14/2018 CANC
DetailsAndy J. Long
No review required, ESC permit for project already issued, see ESC18-01289. This permit VOID
Telephone call  11/7/2018 DONE
emailed Matt (mmcanulty@neudesignarch.com) that all 8 permits are in and that he can go pay the fees for all 8
Intake Approval  11/7/2018 PASS
Intake Approval  10/30/2018 FAIL
DetailsJavier Guzman
Previous request not addressed Provide and upload the following:
• Provide an Erosion & Sediment Control (ESC) Narrative. Narrative must be designed for the specific project, and be prepared and signed by a plan designer certified by Boise City.
Intake Approval  10/25/2018 FAIL
DetailsJavier Guzman
Provide and upload the following:
• Provide and upload an application for each of the buildings with information corresponding to each of those building such as square footage, value, etc... on the application (the current uploaded application you will need to revise to correspond to one of these individual buildings) we will then in-house crate a building permit for each of the buildings.
• Provide a completed #304 form
• Provide a Verification of Legal Lot or Parcel form signed and approved by PDS Subdivision Staff
• Provide a Site specific fire flow at hydrants letter from Suez Water
• Provide a completed Form #310 – Statement of Special Inspections must be completed by the design engineer
• Provide a Shallow Injection Well Inventory form Drainage plans with seepage beds must submit a “Shallow Injection Well Inventory” form from the Idaho Department of Water Resources available at: http://www.idwr.idaho.gov/wells/shallow-injection-wells.html
• Provide a Drainage System Operation & Maintenance Plan stamped and signed by Idaho licensed design professional
• Mark “yes” on the checklist that you have mailed the Permanent Operation & Maintenance Agreement form or dropped off the original signed and notarized document from the landowner to the Public Works Drainage Coordinator.
• Provide an Erosion & Sediment Control (ESC) Narrative. Narrative must be designed for the specific project, and be prepared and signed by a plan designer certified by Boise City.
• Provide a stamped, signed and dated by the Idaho licensed architect all plan sheets with four digit numbers behind the letter “A” (A####) and remove the “NOT FOR PERMIT” statement
• On checklist list the sheet number where to find the door schedule, door hardware, window schedule.
• Provide building envelope Comcheck for the clubhouse
Application received  10/22/2018 DONE
Application submitted via PDS Online on Oct 22 2018 2:57PM