Permit Information
Permit NumberBLD18-03987
StatusFinaled
Name Jeffery Calhoun
Site Address 1099 E EXCHANGE ST
Project NameKnife River Lab Inprovement
Customer Number 
ePlanReviewYes
Description
(KNIFE RIVER) Permit for a minor remodel to an existing 4980 s.f. space previously occupied by ASML under BLD00-00800. Scope of work to include construction of a new equipment room located in the warehouse area which will include: 60 LF of new interior non-bearing wood-framed walls, plywood wall covering, new door & hardware, and minor electrical work. No racking over 8 feet in height is allowed under this permit. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JHB**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Second Notice 1/18/20192/7/2019 DONE
mailed 2-11-19
First Notice 12/23/20181/8/2019 DONE
mailed 1-11-19
FIRE-Final Inspection12/12/201812/13/201812/13/2018APASS
DetailsTroy Cobbley
Life safety passed.

Jeff Phone #: ###-####
Permanent Occupancy  12/13/2018 DONE
FIRE-Final Inspection12/5/201812/5/201812/5/2018PFAIL
DetailsTroy Cobbley
Repair the exit sign and provide sticker at the main exit. Provide fire extinguishers as discussed. Provide plans and small documents.

Jeff Phone #: ###-####
BLD-Final12/4/201812/5/201812/5/2018APASS
DetailsJim Storey
Jeffery Phone #: ###-#### final ok pending fire
BLD-Conference11/19/201811/20/201811/20/2018APART
DetailsDave Hannah
Working/occupying with out CO and permit. occ will pick up permit and schedule final inspection
Print Occupancy Form  11/20/2018 DONE
Issue PAID IN FULL permit  11/20/2018 DONE
Routing - FIRE11/14/201811/14/201811/19/2018 PASS
DetailsErika Akin
Attached comments to case
Plan assigned to (JHB)11/14/201811/14/201811/19/2018 PASS
DetailsJoe Bruce
11/19 L1 Knife River Lab ePlan
1st review completed  11/19/2018 DONE
DetailsJoe Bruce
PLANS/APPL TAKEN TO FRONT DESK  11/19/2018 DONE
Permit Ready to Issue  11/19/2018 DONE
NEED
GC form- MET
verification on who is the GC-may need rev cert of val
Routing - PLAN CHECK11/14/2018 11/16/2018 PASS
DetailsJoe Bruce
Routing - Addressing11/14/2018 11/14/2018 PASS
DetailsDoug Chausow
Routing - PUBLIC WORKS11/14/2018 11/14/2018 PASS
DetailsAngela Hardy
Intake Approval  11/14/2018 PASS
DetailsJavier Guzman
Intake Approval  11/8/2018 FAIL
DetailsJoe Bruce
1) Upload the completed #518-checklist in the documents folder. Items that do not pertain to your project can be checked "N/A." Upload this into the documents folder.
2) A dimension to show the ceiling height on the plans is required.
Intake Approval  11/1/2018 FAIL
DetailsJoe Bruce
1) Upload the completed #518-checklist in the documents folder. Items that do not pertain to your project can be checked "N/A."
2) Upload new building plans that meet the minimum requirements.. Page 2 of the checklist notes that plans must be drawn to scale on 18"x24" minimum sheet size. The scale could not be located and the sheet size is 8.5" x 5.7" and 7.3" x 15.5".
3) Building plans that have been created by another architect are subject to copyright laws. The vicinity map and floorplan drawing submitted appear to be copied from another design professional. Unless you have consent from this architect, this is a violation of copyright law. Resubmit with checklist items that you have created by tracing or utilizing the copyrighted drawings as reference.
4) Provide door hardware information. The knob style hardware does not comply with the building code.
5) Provide the wall finish information. Wall sheathing and finish could not be located.
6) Provide stair details. I see tread and riser height, but no information on the handrail and guard requirements.
7) Provide structural calculations, floor framing plans, guard rail engineering/design, wall bracing details, and lateral force design requirements. The structural work shall be stamped and signed by and Idaho licensed engineer.
8) Since an engineer is required for this work: provide Form #304 - Registered Design Professional form
Application received  10/31/2018 DONE
Application submitted via PDS Online on Oct 31 2018 2:39PM