Permit Information
Permit NumberBLD18-04131
StatusFinaled
Name TVR INC
Site Address 7552 W VICTORY RD
Project NameIsostore, INC
Customer Number 
ePlanReviewYes
Description
(ISOSTORE, INC - VICTORY BUILDING) The fire sprinkler system is used for building area increase and for fire area. Permit is to remodel an existing 2,800 sq. ft. tenant space by adding mechanical work within the fabrication area. Approval is contingent upon adhering to the approved plans on file and attached engineering. Work to include: new MAU, structural roof support framing per the attached engineering, gas piping, paint booth and fabrication area duct work, exhaust fans and a dust collection system, electrical work and mechanical work. Note: 332 sq. ft. new paint booth 1-hour rating was constructed under BLD18-02579 and paint booth shall comply with section 416 of the IBC as well as requirements of the IFC. This building is fully Fire Sprinklered. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JG**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice 8/19/20199/20/2019 DONE
mailed 9-23-19
Permanent Occupancy  8/9/2019 DONE
BLD-Final8/5/20198/6/20198/6/2019APASS
DetailsMike Jordan
You will need to call Dave ###-#### AND code 0688 for the front door lock box. Phone #: ###-#### Inspection requested via web by Brandon Sorensen. OK for perm occ.
FIRE-Final Inspection8/5/20198/5/20198/5/2019PPASS
DetailsTroy Cobbley
life safety passed. The contractor, TVR, stated all wiring was explosion proof.

You will need to call Dave ###-#### AND code 0688 for the front door lock box. Phone #: ###-#### Inspection requested via web by Brandon Sorensen
BLD-Final8/2/20198/5/20198/5/2019ACANC
DetailsMike Jordan
You will need to call Dave ###-#### AND door code 0688 for access. Phone #: ###-#### >> Inspection requested via web by Brandon Sorensen Inspection cancelled from web by: Brandon Sorensen
FIRE-Final Inspection8/2/20198/2/20198/2/2019PFAIL
DetailsTroy Cobbley
I need verification that all electrical in the FInishing Room is explosion proof. Need a racking permit for the rack that exceeds 8'-0".

You will need to call Dave ###-#### AND door code 0688 for access. Phone #: ###-#### Inspection requested via web by Brandon Sorensen
BLD-Final8/1/20198/2/20198/2/2019ANR
DetailsMike Jordan
For access, call Dave ###-#### AND door code 0688 for front door lock box. Phone #: ###-#### Inspection requested via web by Brandon Sorensen. Needs life/safet final first.
Print Occupancy Form  6/26/2019 DONE
Routing - FIRE4/2/20194/2/20194/5/2019 PASS
DetailsMark Scharfen
IFC Final Report 04.05.2019.pdf uploaded.
Plan assigned to (JG)2/5/20192/5/20194/5/2019 PASS
DetailsJavier Guzman
3rd rev, 2/15 L2 Isostore ePlan, pend fire
PLANS/APPL TAKEN TO FRONT DESK  4/5/2019 DONE
Permit Ready to Issue  4/5/2019 DONE
Need
GC Form
Telephone call  4/5/2019 DONE
Spoke with Brandon to inform him we need a GC Form filled out. Give the permits@cityofboise.org email.
Issue PAID IN FULL permit  4/5/2019 DONE
Print Occupancy Form  4/5/2019 DONE
Routing - PLAN CHECK4/2/2019 4/5/2019 PASS
DetailsJavier Guzman
Routing - FIRE3/25/20193/25/20193/28/2019 FAIL
DetailsMark Scharfen
IFC 2nd review 03.28.2019.pdf uploaded and emailed to applicant.
Routing Off Site - STRUCTURAL3/25/2019 3/28/2019 PASS
DetailsJavier Guzman
Signed off in ePlan by AHJ Engineers Chris Holladay

Routing - PLAN CHECK3/25/2019 3/28/2019 PASS
DetailsJavier Guzman
Routing - MECHANICAL3/25/2019 3/26/2019 PASS
DetailsTroy James
Route to Impact Fee Review2/20/20192/23/20192/20/2019 PASS
DetailsKarina Myles
Review requested for Commercial Permit
Routing Off Site - STRUCTURAL2/5/2019 2/20/2019 FAIL
DetailsJavier Guzman
Failed in ePlan by AHJ Engineers Chris Holladay

1st review completed  2/20/2019 FAIL
DetailsJavier Guzman
Routing - FIRE2/5/20192/5/20192/15/2019 FAIL
DetailsMark Scharfen
iFC Fire review 02.15.2019.pdf uploaded and emailed to applicant.
Routing - PLAN CHECK2/5/2019 2/14/2019 PASS
DetailsJavier Guzman
Routing PW Environmental2/5/2019 2/13/2019 PASS
DetailsRick Christenson
Routing - MECHANICAL2/5/2019 2/8/2019 PASS
DetailsTroy James
Routing - Addressing2/5/2019 2/5/2019 PASS
DetailsDoug Chausow
Routing - PUBLIC WORKS2/5/2019 2/5/2019 PASS
DetailsMorgan Webb
Routing - Design Review2/5/2019 2/5/2019 PASS
DetailsKatelyn Menuge
Intake Approval  2/4/2019 PASS
DetailsJavier Guzman
Intake Approval  1/31/2019 FAIL
DetailsJoe Bruce
Provide the following items to complete your prescreen:
I could not locate a newly uploaded cover sheet. Form #304 is not signed by the building owner. Please upload those items.

5. NEW - Provide another drawing sheet with the following items from the checklist: Vicinity Map, Key Plan, Code Analysis, Fire extinguisher locations, exit signage ,etc... This sheet can be stamped by and Idaho licensed engineer or architect.
6. NEW - The new form #304 that was uploaded does not have the building owners signature. Provide owner's signature if switching design professional.
Intake Approval  1/8/2019 FAIL
DetailsJoe Bruce
5. NEW - Provide another drawing sheet with the following items from the checklist: Vicinity Map, Key Plan, Code Analysis, Fire extinguisher locations, exit signage ,etc... This sheet can be stamped by and Idaho licensed engineer or architect.
Intake Approval  1/4/2019 FAIL
DetailsJoe Bruce
1. RESOLVED - It appears from the prior permits that a new exterior louver is being installed which would require a zoning certificate. A certificate of zoning compliance is required for any exterior changes to the building. Please contact Katelyn Menuge the Zoning department to verify if this project will require a CZC. Phone: ###-####
2. PROVIDE (still need to structural calculations from the engineer) - No structural engineering stamp was provided on the detail for the MAU and no attachment details or structural calculations were submitted. Provide structural details and calculations for the mechanical unit that is being suspended from the roof structure. These details and calculations must be stamped and signed by and Idaho licensed Structural Engineer.
3. RESOLVED - These could not be located. Provide elevations for the exterior changes being made. The sidewall louver, rooftop equipment, and exhaust flue/vents must be shown.
4. RESOLVED, Larson drawings/titleblock deleted from case. - The architectural drawings appear to be from a prior permit submittal and do not appear to be specifically generated for this permit. Provide written consent from Larson Architects for utilization and modification of their drawings for this project.
5. NEW - Provide another drawing sheet with the following items from the checklist: Vicinity Map, Key Plan, Code Analysis, Fire extinguisher locations, exit signage ,etc... This sheet can be stamped by and Idaho licensed engineer or architect.
Intake Approval  1/4/2019 FAIL
DetailsJoe Bruce
Spoke with Brandon on the phone about requirements. **JHB** See last intake note.
Intake Approval  12/13/2018 FAIL
DetailsJoe Bruce
1. RESOLVED - It appears from the prior permits that a new exterior louver is being installed which would require a zoning certificate. A certificate of zoning compliance is required for any exterior changes to the building. Please contact Katelyn Menuge the Zoning department to verify if this project will require a CZC. Phone: ###-####
2. PROVIDE (still need to pass prescreen) - No structural engineering stamp was provided on the detail for the MAU and no attachment details or structural calculations were submitted. Provide structural details and calculations for the mechanical unit that is being suspended from the roof structure. These details and calculations must be stamped and signed by and Idaho licensed Structural Engineer.
3. RESOLVED - These could not be located. Provide elevations for the exterior changes being made. The sidewall louver, rooftop equipment, and exhaust flue/vents must be shown.
4. RESOLVED, Larson drawings/titleblock deleted from case. - The architectural drawings appear to be from a prior permit submittal and do not appear to be specifically generated for this permit. Provide written consent from Larson Architects for utilization and modification of their drawings for this project.
5. NEW - When revised drawings are uploaded they need to have the same file name as the original drawing that were uploaded. The files with REV1 added to them have been deleted from this case. Upload the drawings with identical filenames. Reference the ePlanReview Submittal Standards (page 4) https://pds.cityofboise.org/media/464072/pdox86_electronic_standards_full_050718.pdf
6) NEW - Provide items from the checklist that were provided on Larson's architectural drawings that cannot be used for this submittal. (i.e. Vicinity Map, Key Plan, Code Analysis, etc... - see checklist)
Intake Approval  12/10/2018 FAIL
DetailsJoe Bruce
1. It appears from the prior permits that a new exterior louver is being installed which would require a zoning certificate. A certificate of zoning compliance is required for any exterior changes to the building. Please contact Katelyn Menuge the Zoning department to verify if this project will require a CZC. Phone: ###-####
2. No structural engineering stamp was provided on the detail for the MAU and no attachment details or structural calculations were submitted. Provide structural details and calculations for the mechanical unit that is being suspended from the roof structure. These details and calculations must be stamped and signed by and Idaho licensed Structural Engineer.
3. These could not be located. Provide elevations for the exterior changes being made. The sidewall louver, rooftop equipment, and exhaust flue/vents must be shown.
4. The architectural drawings appear to be from a prior permit submittal and do not appear to be specifically generated for this permit. Provide written consent from Larson Architects for utilization and modification of their drawings for this project.
Intake Approval  11/29/2018 FAIL
DetailsJoe Bruce
1. Complete and upload form #304 – Registered Design Professional Form.
2. A certificate of zoning compliance is required for any exterior changes to the building. Please contact Katelyn Menuge the Zoning department to verify if this project will require a CZC. Phone: ###-####
3. Provide structural details and calculations for the mechanical unit that is being suspended from the roof structure. These details and calculations must be stamped and signed by and Idaho licensed Structural Engineer.
4. Provide a roof plan as noted on the checklist. The roof plan could not be located on sheet M-2 as the checklist noted.
5. Provide elevations for the exterior changes being made. The sidewall louver, rooftop equipment, and exhaust flue/vents must be shown.
Intake Approval  11/15/2018 FAIL
DetailsJoe Bruce
Provide the following items to complete your prescreen:
1. Complete and upload form #518 – Minor TI Submittal Checklist. Fill out locations of all required information and list the page number for each.
2. Sheets M-1 and M-2 need to be uploaded into the drawings folder. Refer to our ePlan drawings standards located on our website. https://pds.cityofboise.org/media/464072/pdox86_electronic_standards_full_050718.pdf
3. A certificate of zoning compliance is required for any exterior changes to the building. Please contact the Zoning department to verify if this project will require a CZC. Phone: ###-####
4. Provide a vicinity map and key plan.

Since a checklist was not completed with this application a thorough prescreen review could not be completed.
Application received  11/13/2018 DONE
Application submitted via PDS Online on Nov 13 2018 11:41AM