BLD-Final | 5/13/2020 | 5/13/2020 | 5/13/2020 | P | PASS |
Jim Storey
|
|
|
|
DOC - Permit Finaled | 5/13/2020 | 5/13/2020 | 5/13/2020 | P | PASS |
Jim Storey
|
|
|
|
BLD-Framing/Rough-in | 5/12/2020 | 5/13/2020 | 5/13/2020 | A | PASS |
Jim Storey
|
|
|
ccall all half hour to meet // kaleb Phone #: ###-####
|
BLD-Final | 5/13/2020 | 5/13/2020 | 5/13/2020 | A | PASS |
Jim Storey
|
|
|
ccall all half hour to meet // kaleb Phone #: ###-####
|
BLD-Framing/Rough-in | 5/4/2020 | 5/4/2020 | 5/4/2020 | P | PART |
Jim Storey
|
|
|
Caleb Phone #: ###-#### framing ok pending gyp insp.
|
BLD-Framing/Rough-in | 5/1/2020 | 5/4/2020 | 5/4/2020 | A | DEFR |
Jim Storey
|
|
|
Caleb Phone #: ###-#### need call back
|
BLD-Aging Inspection | 4/7/2020 | 4/7/2020 | 4/9/2020 | | PART |
Jim Storey
|
|
|
caller working on submital for 2hr details to go to planreview.
|
BLD-Aging Inspection | 4/6/2020 | 4/6/2020 | 4/9/2020 | | PART |
Jim Storey
|
|
|
caller working on submital for 2hr details to go to planreview.
|
BLD-Conference | 2/3/2020 | 2/4/2020 | 2/4/2020 | A | FAIL |
Dave Hannah
|
|
|
call 1 hour prior for access // Kaleb Phone #: ###-#### they ran conduit in two hr stair tower with no plans or two hr protection need to resubit plans
|
Issue PAID IN FULL permit | | | 5/23/2019 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 5/23/2019 | | DONE |
|
|
|
|
Expiration Notice | 5/21/2019 | 6/12/2019 | 5/21/2019 | | DONE |
Brittany Hill
|
|
|
|
Permit Ready to Issue | | | 4/26/2019 | | DONE |
|
|
|
MET DOUGLAS.KOFFORD@SMARTLINKLLC.COM
Need
GC form
Revised Value
|
Plan assigned to (M_H) | 1/9/2019 | | 4/24/2019 | | DONE |
Michael Hanson
|
|
|
3rd review completed - 01/22 #518 L2 ePlan
|
Routing Off Site - STRUCTURAL | 4/16/2019 | | 4/24/2019 | | PASS |
Michael Hanson
|
|
|
Passed per D. Haugland AHJ engineering
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/24/2019 | | DONE |
Michael Hanson
|
|
|
Please upload additional review fee form. 5 reviews with off site structural.
|
Permit Ready to Issue | | | 4/24/2019 | | DONE |
|
|
|
Need
GC form
Revised Value
(need 5th review fee total from M_H)
|
Routing Off Site - STRUCTURAL | 3/26/2019 | | 4/10/2019 | | FAIL |
Michael Hanson
|
|
|
See comments in ePlan for corrections required. D. Haugland AHJ engineering
|
Routing Off Site - STRUCTURAL | 2/15/2019 | | 3/26/2019 | | FAIL |
Michael Hanson
|
|
|
See comments in ePlan for corrections required. D. Haugland AHJ engineering
|
Route to Impact Fee Review | 2/14/2019 | 2/17/2019 | 2/15/2019 | | PASS |
Eric Bilimoria
|
|
|
Review requested for Commercial Permit
|
Routing Off Site - STRUCTURAL | 2/8/2019 | | 2/15/2019 | | FAIL |
Michael Hanson
|
|
|
See changemarks in ePlan for corrections required by D. Haugland AHJ engineering.
|
Routing - FIRE | 2/1/2019 | 2/1/2019 | 2/1/2019 | | PASS |
Erika Akin
|
|
|
Total electrolyte capacity 29.64 gallons for 12 batteries, IFC 608 not applicable.
|
1st review completed | | | 1/28/2019 | | FAIL |
Michael Hanson
|
|
|
|
Routing Off Site - STRUCTURAL | 1/9/2019 | | 1/28/2019 | | FAIL |
Michael Hanson
|
|
|
Corrections required per D. Haugland AHJ engineering. MDH
|
Routing - FIRE | 1/9/2019 | 1/9/2019 | 1/23/2019 | | FAIL |
Erika Akin
|
|
|
01/22 L2 Cell Requested electrolyte capacity for batteries via email 1-16. No response as of 1-23-19. Resent email
|
Routing - PLAN CHECK | 1/9/2019 | | 1/18/2019 | | PASS |
Michael Hanson
|
|
|
|
Routing - PLANNING | 1/9/2019 | | 1/14/2019 | | PASS |
Nicolette Womack
|
|
|
|
Routing - Design Review | 1/9/2019 | | 1/10/2019 | | PASS |
Andrea Tuning
|
|
|
No Design Review required per Cody Riddle.
|
Intake Approval | | | 1/9/2019 | | PASS |
Javier Guzman
|
|
|
|
Intake Approval | | | 1/7/2019 | | FAIL |
Michael Hanson
|
|
|
518 checklist must list the sheet in which the required information is listed on. Revise and resubmit.
Minimum sheet size is 18"x24". Revise and resubmit drawing files.
A-4.2 New antenna feed line schedule is blacked out. Revise and resubmit.
|
Intake Approval | | | 12/20/2018 | | FAIL |
Michael Hanson
|
|
|
Provide completed and signed 518 checklist and 304 form.
|
Application received | | | 12/18/2018 | | DONE |
|
|
|
Application submitted via PDS Online on Dec 18 2018 8:25PM
|