Permit Information
Permit NumberBLD18-04518
StatusFinaled
Name J & L DEVELOPMENT LTD CORP
Site Address 2675 W MAIN ST
Project NameRevolution 22 Church TI
Customer Number 
ePlanReviewYes
Description
(REVOLUTION 22) CZC19-00012 Permit is for the change of occupancy of an existing building from an office to a church on the main floor and offices/classrooms in the basement level that are classified as part of the assembly occupancy. This building is adding fire sprinklers within the entire building due to the requirements of 2015 IBC section 903.2.1.3 for occupants exceeding 300. Work is to include removal of interior non-bearing walls, new interior nonbearing partitions, new multi-user restrooms, new classrooms, new office space, plumbing, electrical, and mechanical work; and interior finishes in compliance with Ch. 8 of the 2015 IBC. Approval is contingent upon adhering to the approved plans on file and attached engineering. This building shall be a fully sprinklered building, and installation of the sprinkler system will require a separate fire sprinkler permit and will be required to comply with NFPA #13 as regulated by the Boise City Fire Department. **JHB**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice 7/25/20198/13/2019 DONE
mailed 8-14-19
Permanent Occupancy  7/15/2019 DONE
BLD-Final7/10/20197/11/20197/11/2019PPASS
DetailsDave Hannah
Please call 30min ahead to allow time to meet you. Thanks Phone #: ###-#### Inspection requested via web by Ron Douthit
FIRE-Final Inspection7/8/20197/11/20197/11/2019PPASS
DetailsJim Page
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are placed with current inspection tags, knox box is located by west exit, this door is fire riser access. Final life fire safety inspection complete.

We would like Life Safety paired with he alarm final Thursday. Thanks. RON Phone #: ###-#### Inspection requested via web by Ron Douthit
Zoning Approval7/11/20197/11/20197/11/2019 DONE
DetailsJeff Lowe
FIRE-Final Inspection7/2/20197/3/20197/3/2019AFAIL
DetailsJim Page
Need FIR permits for fire sprinkler and fire alarm finaled before life fire safety inspection can be performed.

Ron Phone #: ###-####
BLD-Framing/Rough-in4/30/20195/1/20195/1/2019APASS
DetailsDave Hannah
Re inspection for sealing around plumbing pipes Phone #: ###-#### Inspection requested via web by Ron Douthit
BLD-Framing/Rough-in4/29/20194/30/20194/30/2019APEND
DetailsDave Hannah
Phone #: ###-#### Inspection requested via web by Ron Douthit walls ok but need to foam holes in floor
Place hold on job3/28/2019 4/1/2019 DONE
DetailsTiffany Carson-Herker
waiting for signed permit
Telephone call  4/1/2019 DONE
emailed GC a reminder to print and sign on building permit and email it back.
Print Occupancy Form  3/28/2019 DONE
Issue PAID IN FULL permit  3/28/2019 DONE
Telephone call  3/26/2019 DONE
emailed them informing them that the RCE number they included on the GC form they emailed to permits on 3-26-2019 is invalid. Requested a valid RCE number
Plan assigned to (JHB)2/14/20192/14/20193/25/2019 PASS
DetailsJoe Bruce
03/22 (1st Resub) 03/14 (L3) Revolution 22 (Bldg, Mech, Plumb, Fire, Struc, DR)
Routing Off Site - STRUCTURAL3/18/2019 3/25/2019 PASS
DetailsJoe Bruce
AHJ
PLANS/APPL TAKEN TO FRONT DESK  3/25/2019 DONE
Permit Ready to Issue  3/25/2019 DONE
NEED=all met
ACHD-met
GC FORM
REVISED VALUE - met
Routing - FIRE3/18/20193/18/20193/22/2019 PASS
DetailsMark Scharfen
IFC Final review 03.22.2019.pdf uploaded.
Routing - Design Review3/18/2019 3/21/2019 PASS
DetailsKayCee Babb
Per CZC19-00012. No exterior alterations beyond rooftop mechanical equipment and parking approved through this permit.
Routing - PLAN CHECK3/18/2019 3/20/2019 PASS
DetailsJoe Bruce
Routing - MECHANICAL3/18/2019 3/18/2019 PASS
DetailsTroy James
Routing - PLUMBING3/18/2019 3/18/2019 PASS
DetailsDaryl Spivey
Per ISPC 407.3 install tempering device on lavs as required.
Plan resubmittals received  3/18/2019 DONE
DetailsJoe Bruce
Route to Impact Fee Review3/14/20193/17/20193/15/2019 PASS
DetailsShannon Cade
Review requested for Commercial Permit
Routing - FIRE2/14/20192/14/20193/14/2019 FAIL
DetailsMark Scharfen
IFC 1st review 03.14.2019.pdf uploaded and emailed to architect.
1st review completed  3/14/2019 FAIL
DetailsJoe Bruce
Plan resubmittals requested  3/14/2019 DONE
DetailsJoe Bruce
Routing - PLAN CHECK2/14/2019 3/14/2019 FAIL
DetailsJoe Bruce
Routing Off Site - STRUCTURAL2/14/2019 2/28/2019 FAIL
DetailsJoe Bruce
AHJ - Corrections Required.
Routing - MECHANICAL2/14/2019 2/21/2019 FAIL
DetailsTroy James
See eplan for corrections
Routing - PLANNING2/14/2019 2/15/2019 PASS
DetailsJeff Lowe
Per CZC19-00012.
Routing - Addressing2/14/2019 2/15/2019 PASS
DetailsDoug Chausow
Routing - Design Review2/15/2019 2/15/2019 PASS
DetailsKayCee Babb
Per CZC19-00012. Change of Use Zoning Certificate to stand in for Design Review. ADA parking stall alterations and mechanical units are approved. Any other exterior alterations shall require additional review.
Routing - PUBLIC WORKS2/14/2019 2/14/2019 PASS
DetailsAngela Hardy
Routing - Design Review2/14/2019 2/14/2019 FAIL
DetailsKayCee Babb
A Zoning Certificate is required for all exterior alterations, including rooftop mechanical equipment and new parking lot layout. Additionally, site requires a parking reduction or permanent parking agreement for use/proposed seating. A temporary parking lease is not sufficient. If you have any questions, you can reach KayCee Babb at ###-####.
Routing - PLUMBING2/14/2019 2/14/2019 FAIL
DetailsDaryl Spivey
Need service protection on water and increase cold water pipe sizing to 1 1/2 in for upstairs plumbing.
Intake Approval  2/14/2019 PASS
Intake Approval  2/5/2019 FAIL
DetailsJoe Bruce

5) Provide shared access and parking agreement with legal description of shared property that is signed and notarized. Upload this document into the "documents" folder.
6) Provide design review approval for new mechanical unit RTU-4 located on rooftop. Contact: Kaycee Babb - ###-####

9) Provide structural plans for the modification to the floor / roof framing and rooftop unit. Plans must be stamped by a structural engineer.
Intake Approval  12/26/2018 FAIL
DetailsJoe Bruce
1) Form #304 needs to be completely filled out with design professional and owner information.
2) Structural calculations must have the engineers stamp on the cover page with signature and date.
3) Last page of structural calculations states "NOT FOR PERMIT." This is required to be removed and affixed with the structural engineers stamp and signature.
4) Provide site specific flow at hydrants letter from Suez water for this address.
5) Provide shared access and parking agreement with legal description of shared property that is signed and notarized. Upload this document into the "documents" folder.
6) Provide design review approval for new mechanical unit RTU-4 located on rooftop. Contact: Kaycee Babb - ###-####
7) Show portable fire extinguishers on plan. Sheet G-002 makes mention in the notes, but does not locate them on the plan.
8) Exit signs could not be located on the lower level lighting plan. Locate all exit signs including new and existing.
9) Provide structural plans for the modification to the floor framing. Plans must be stamped by a structural engineer.
Application received  12/20/2018 DONE
Application submitted via PDS Online on Dec 20 2018 2:51PM