Permit Information
Permit NumberBLD19-00326
StatusIssued
Name KW HOMES INC
Site Address 3023 N COLE RD
Project NameOmbu 3 Korean BBQ
Customer NumberBLD19-00541 DEMO
ePlanReviewYes
Description
(OMBU 3 KOREAN BBQ) **PLAN MODIFICATION 9-30-19 To modify truss reinforcing for fire sprinkler pipe between trusses, SEE SHEET S-1.00.** This building is adding a fire sprinkler system for building area increase and for fire area. Building to the east (Sockeye Brewing) shall also be retrofitted with fire sprinklers through an upgrade agreement at a later date. Permit to remodel an existing 4,510 square foot mercantile space into a restaurant. Work is to include new non-bearing interior walls, two multi-user toilet rooms to be accessible to the disabled, dining area, salad bar, plumbing, electrical, and mechanical work; and interior finishes in compliance with Ch. 8 of the 2015 IBC. A new kitchen with a new Type I Hood, 39 Type I exhaust hoods and cooking griddles at each dining table, new UL listed kitchen equipment, and a portion of the concrete slab will be saw cut and removed to facilitate underslab plumbing and a new concrete slab on grade will be placed to patch the concrete after the plumbing is complete. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any installation work on such systems. **JHB**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Aging Inspection7/15/20207/15/20207/17/2020 PEND
DetailsTell Riley
BLD-Aging Inspection7/14/20207/14/20207/15/2020 PEND
DetailsTell Riley
BLD-Framing/Rough-in2/28/20203/2/20203/2/2020APASS
DetailsJim Storey
Kent- please call for access 30 before Phone #: ###-#### walls ok to cover c/n made ok.
BLD-Framing/Rough-in2/3/20202/4/20202/4/2020PFAIL
DetailsTell Riley
call ahead // Ken Phone #: ###-####//need fire sprinkler roug in completed//add backing for Accessibility//secure demising wall studs//provide wall assembly for 1 hr room at fire riser//
Telephone call  2/4/2020 DONE
marcus called to change address on permit to 3023 N cole rd.
BLD-Framing/Rough-in12/26/201912/26/201912/26/2019PNR
DetailsTell Riley
metal stem wall // Kent Phone #: ###-####// Ken had questions on demising wall--plans show to underside of roof sheathing--wall stops at roof insulation--refered him to architect//some walls have been one sided--asked him to leave uncovered until all trades passed and framing is approved//
BLD-Framing/Rough-in11/21/201911/21/201911/21/2019PPART
DetailsTell Riley
Call ahead 30 minutes - truss bracing // Kent Phone #: ###-####//engineering and engineers letter from site visit and approval onsite dated Nov 20, 2019 stamped and signed reviewed onsite//trusses ok per engineer//
BLD-Wall Bracing11/19/201911/19/201911/19/2019PCANC
DetailsTell Riley
call for keycode access // Kim Phone #: ###-####//CN still onsite--corrections have not been completed//updated engineering will be needed to reflect what has been completed onsite--see correction notice//no wall bracing inspection needed at this time//
BLD-Framing/Rough-in11/6/201911/7/201911/7/2019AFAIL
DetailsTell Riley
Call for access //

ken Phone #: ###-####
//CN posted--truss fixes to dont reflect engineering--see CN//
CHANGE STATUS TO (ISS)  11/6/2019 DONE
plan mod
Plan assigned to (JHB)9/30/20199/30/201910/2/2019 PASS
DetailsJoe Bruce
10/07 (plan mod) Korean BBQ
Routing - PLAN CHECK10/2/2019 10/2/2019 PASS
DetailsJoe Bruce
Plan Modification passed. - Truss modification to accomodate fire sprinklers.
Permit Ready to Issue  10/2/2019 DONE
plan mod accepted
Plan Modification Accepted  9/30/2019 DONE
Print Occupancy Form  6/13/2019 DONE
Issue PAID IN FULL permit  6/13/2019 DONE
Plan assigned to (JHB)3/14/20193/14/20195/22/2019 PASS
DetailsJoe Bruce
* 04/26 (4th Rev) 03/13 - (L3) Ombu 3 Korean BBQ (Bldg, DR, Mech, Fire)
PLANS/APPL TAKEN TO FRONT DESK  5/22/2019 DONE
Permit Ready to Issue  5/22/2019 DONE
MET gwalker@adpboise.com
Need
ACHD
GC form
Revised certificate of value
Routing - FIRE4/22/20194/22/20195/20/2019 PASS
DetailsMark Scharfen
04/29 OMBU MS Resubmittal-sprinkler agreement recorded. Permit approved.
Routing - MECHANICAL4/22/2019 4/23/2019 PASS
DetailsTroy James
Plan resubmittals received  4/22/2019 DONE
DetailsJoe Bruce
Routing - FIRE4/3/20194/3/20194/8/2019 FAIL
DetailsMark Scharfen
04/08-The sprinkler upgrade agreement has not been submitted and approved yet. Resubmit plans when upgrade agreement plan has been submitted and approved.
Routing - MECHANICAL4/3/2019 4/8/2019 FAIL
DetailsTroy James
Plan Reviewer's activity  4/8/2019 DONE
DetailsJoe Bruce
Still need upgrade agreement letter for fire sprinklers in the adjacent building.
Plan resubmittals requested  4/8/2019 DONE
DetailsJoe Bruce
Sent email to Glenn regarding additional items required for resubmittal. **JHB**
Routing - PLAN CHECK4/3/2019 4/8/2019 PASS
DetailsJoe Bruce
Plan resubmittals received  4/3/2019 DONE
DetailsJoe Bruce
Routing - Design Review4/3/2019 4/3/2019 PASS
DetailsKatelyn Menuge
Routing - FIRE3/25/20193/25/20194/1/2019 FAIL
DetailsMark Scharfen
04/01 Waiting on sprinkler agreement before issuing permit. Resubmittal required.
Plan resubmittals requested  4/1/2019 DONE
DetailsJoe Bruce
Routing - PLAN CHECK3/25/2019 3/28/2019 FAIL
DetailsJoe Bruce
Routing - MECHANICAL3/25/2019 3/26/2019 FAIL
DetailsTroy James
Previous corrections have not been addressed.
Routing - PLANNING3/25/2019 3/25/2019 PASS
DetailsDavid Moser
Routing - Design Review3/25/2019 3/25/2019 FAIL
DetailsKatelyn Menuge
Provide height of new rooftop equipment vs height of existing parapet to demonstrate new equipment will be screened from view, or provide additional screening.
Plan resubmittals received  3/25/2019 DONE
DetailsJoe Bruce
Route to Impact Fee Review3/14/20193/17/20193/15/2019 PASS
DetailsEric Bilimoria
Review requested for Commercial Permit
Plan assigned to (JAR)2/19/20192/19/20193/14/2019 DEFR
DetailsJulie Romig
03/13 - L3 Ombu 3 Korean BBQ
Routing - FIRE2/19/20192/19/20193/14/2019 FAIL
DetailsMark Scharfen
IFC final review 03.14.2019.pdf.
Routing - Design Review2/20/2019 3/14/2019 FAIL
DetailsKatelyn Menuge
Please add new rooftop mechanical equipment and any other exterior changes to one of your open DR applications and obtain approval prior to building permit submittal.



1st review completed  3/14/2019 FAIL
DetailsJoe Bruce
Plan resubmittals requested  3/14/2019 DONE
DetailsJoe Bruce
Emailed plan review report to architect.
Routing - PLAN CHECK2/19/2019 3/13/2019 FAIL
DetailsJulie Romig
Routing - MECHANICAL2/19/2019 2/26/2019 FAIL
DetailsTroy James
See eplan for corrections
Routing - Erosion and Sediment2/19/2019 2/26/2019 PASS
DetailsMichael Zawacki
TI, no esc plan required.
Routing PW Environmental2/20/2019 2/26/2019 PASS
DetailsTerry Alber
Grease abatement approved.
Routing PW Solid Waste2/20/2019 2/25/2019 PASS
DetailsEvan Carpenter
Plan Reviewer's activity  2/25/2019 DONE
Spoke with architect, Glenn Walker, regarding proximity of Sockeye Restaurant building to the east at 3019 N Cole. Both buildings were considered one building for building area and there is no separation between the two. The owner plans to build out this west building, 3021 N Cole, and fire sprinkler it, then will add fire sprinklers to the east bldg. Both buildings will be reclassified as Type VB construction. Told Glenn that anupgrade agreement will be required.
Routing - PLUMBING2/19/2019 2/20/2019 PASS
DetailsDaryl Spivey
Vent floor drains as required and provide tempered water to lavs per ISPC 407.3.
Routing - PLANNING2/19/2019 2/20/2019 FAIL
DetailsKatelyn Menuge
Please add new rooftop mechanical equipment and any other exterior changes to one of your open DR applications and obtain approval prior to building permit submittal.
Routing - Addressing2/19/2019 2/20/2019 PASS
DetailsDoug Chausow
Suite 110
Routing - PUBLIC WORKS2/19/2019 2/20/2019 PASS
DetailsAngela Hardy
Intake Approval  2/14/2019 PASS
Intake Approval  1/31/2019 FAIL
DetailsJoe Bruce
1) Exit signs could not be located on sheet A1.20 as noted on the checklist.
2) COMcheck reports are required to be printed on the plans per the checklist. Upload additional plans with COMcheck reports that are stamped and signed by design professional.
3) Either provide and Erosion and Sediment Control waiver request or provide Erosion and Sediment Control Plans & Narrative for the installation of the grease interceptor in the parking lot. Contact Andy Long ###-#### AJLong@cityofboise.org
4) Provide structural drawings in addition to the submitted structural calculations that reflect the scope of work defined in the calculations. These drawings must be stamped/signed by the structural engineer.
5) Provide approved health department plans and application that shows the Central District Health approval stamp and signature. Upload these documents into the documents folder.
6) Sheet index on the cover page does not include sheet P-1.01. Revise sheet index to include all sheets included in the plans set.
7) Provide a demolition plan.
8) Incorrect codes are noted on the cover sheet for the Mechanical Code and Fuel/Gas Code. See currently adopted codes on our website: https://pds.cityofboise.org/media/1951/currently-adopted-building-codes-12-27-17.pdf
9) Since fire sprinklers are to be installed, provide location of fire sprinkler riser room and fire riser location on the plans.
Application received  1/29/2019 DONE
Application submitted via PDS Online on Jan 29 2019 2:43PM