Permit Information
Permit NumberBLD19-00358
StatusFinaled
Name BERLUM DEVELOPMENT CO
Site Address 2184 E PARKSIDE DR
Project Name2184 Parkside
Customer Number 
ePlanReviewYes
Description
CAT II Hillside Permit. PLAN MOD 3-18-19 NEW SUEZ FIRE FLOW REPORT INDICATES THERE IS ADEQUATE GPM.SPRINKLERS ARE NOT REQUIRED. LGM **HILLSIDE** **WUI FOOTHILLS ZONE A REQUIREMENTS** **SPECIAL INSPECTIONS REQUIRED** **PRESCRIPTIVE ENERGY REQUIREMENTS** Permit for the construction of a new 2450 sq. ft., two story (first story 1209 sq. ft., second story 1241 sq. ft.) single family dwelling with 3 bedrooms, 2.5 bathrooms, and a 1108 sq. ft. attached garage per the approved plans and any notations. R-1B zoning and setbacks per planning. JJN A letter from the applicant’s geotechnical engineer indicating that the footing/column subgrade is acceptable must be approved by Public Works prior to scheduling a footing inspection. Please e-mail the stamped inspection approval letter to mjannusch@cityofboise.org and allow 24 hours for subgrade approval processing. Call Melissa Jannusch at 208-608-7168 with questions.

Prior to obtaining a final for the permit, the roof storm drainage system must be inspected by Public Works. Call Melissa Jannusch at 208-608-7168.

The final inspection of the site grading and drainage work shall be done by the design engineer. Written approval shall be submitted to Boise Public Works prior to the issuance of the building final.

An erosion and sediment control site preparation inspection is required for this site. The site preparation inspection takes place after all required erosion and sediment control best management practices have been installed and BEFORE any earthwork takes place. Call 208-608-7070 to schedule an inspection.



All disturbed slopes included in the construction of this project must be stabilized and approved by Public Works before a Final Occupancy Permit is granted. If weather conditions prohibit revegetation and stabilization activities, the contractor shall provide a bond/surety agreement or an irrevocable letter of credit in the amount of 110% of the cost estimated by the project engineer to enable stabilization of the site. Call 208-608-7168 for an inspection.
SPRINKLERS ARE BEING PROVIDED, AS NOTED ON SITE PLAN. LGM
Contact Information
See Activities list for contact information
Color Key
Current location of plans being reviewed:  
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final11/14/201911/14/201911/14/2019PPASS
DetailsBrandon Shaw
James Phone #: ###-####
DOC - Permit Finaled11/14/201911/14/201911/14/2019PPASS
DetailsBrandon Shaw
BLD-Blower Door Test Results11/14/201911/14/201911/14/2019PDONE
DetailsBrandon Shaw
ACH50- 4.83
PubWorks Occupancy Approval11/13/201911/13/201911/13/2019 DONE
DetailsMelissa Jannusch
A bond has been post for the site final stabilization.Occupancy may be approved by the building department. Melissa Jannusch ###-####.


BLD-Final11/8/201911/8/201911/8/2019PFAIL
DetailsBrandon Shaw
Need PW grading approval...
BLD-Final11/6/201911/7/201911/7/2019ANR
DetailsBrandon Shaw
Pre final walk thru...
BLD-Energy code compliance7/25/20197/25/20197/25/2019PPEND
DetailsBrandon Shaw
4 additional lights being added to stairs, need ELE rough-in cover approval.
Per Engineering- DF #1 to be used for bearing end of cut trusses...
BLD-Framing/Rough-in7/23/20197/23/20197/23/2019PPEND
DetailsBrandon Shaw
Provide Engineering approval/ revised fix for floor trusses, F6, F7, F19. Bearing end has been cut and/or modified...
BLD-Framing/Rough-in7/23/20197/23/20197/23/2019PPASS
DetailsBrandon Shaw
James Phone #: ###-####
DOC - Permit Finaled7/23/20197/23/20197/23/2019PPASS
DetailsBrandon Shaw
CHANGE STATUS TO (ISS)  7/23/2019 DONE
Brandon S. inpector doc final accidently- put back in ISS status
BLD-Wall Bracing7/17/20197/17/20197/17/2019PCANC
DetailsBrandon Shaw
James Phone #: ###-####
BLD-Framing/Rough-in6/19/20196/20/20196/20/2019APASS
DetailsJim Storey
Call ahead // James Phone #: ###-#### ok to remove tub fur out walls.
BLD-Wall Bracing6/13/20196/14/20196/14/2019APASS
DetailsDave Hannah
Jay Phone #: ###-####
BLD-Wall Bracing6/11/20196/11/20196/12/2019PNR
DetailsDave Hannah
James Phone #: ###-#### no plans on site
BLD-Foundation4/24/20194/24/20194/25/2019PPASS
DetailsDave Hannah
As early as possible Phone #: 2089656103 >> Inspection requested via mobile web by Alvaro
BLD-Footing4/12/20194/12/20194/12/2019PPASS
DetailsDave Hannah
Alvalo Phone #: ###-####
PubWorks Subgrade Approval4/12/20194/12/20194/12/2019 DONE
DetailsMelissa Jannusch
A letter from the applicant’s geotechnical engineer indicating that the footing/column subgrade is acceptable has been received by Public Works. Footing inspection may be scheduled with the Building Department. Melissa Jannusch ###-####.
CHANGE STATUS TO (ISS)  4/12/2019 DONE
OVERRIDE  3/18/2019  
Routing - FIRE3/15/20193/15/20193/18/2019 PASS
DetailsLee G Meredith
03/22 2184 E Parkside Hillside 404

Applicant's plan mod included a SUEZ provided fire flow statement that was adequate. Sprinklers are no longer required.
Routing - Erosion and Sediment3/15/2019 3/18/2019 PASS
DetailsMichael Zawacki
Permit Ready to Issue  3/18/2019 DONE
PLAN MOD
Plan assigned to (J_N)3/13/2019 3/18/2019 DONE
DetailsJenny Nelson
Plan Mod - no longer installing sprinklers fire flow adequate
Routing - PLAN CHECK3/15/2019 3/18/2019 PASS
DetailsJenny Nelson
1 hour plan mod fee
Routing - PLANNING3/15/2019 3/18/2019 PASS
DetailsKarla Nelson
Driveway is not to exceed 33' in the front setback.
Plan Modification Accepted  3/13/2019 DONE
Spoke with Arrow, the applicant. She informed me she needs to upload a new site plan and fire flow letter. Started new work flow i eplan
Issue PAID IN FULL permit  3/5/2019 DONE
Inspection Record Card- Bld  3/5/2019 DONE
OVERRIDE  3/4/2019  
Plan assigned to (J_N)2/19/20192/19/20193/4/2019 DONE
DetailsJenny Nelson
03/08 sfd L2 ePlan. 1st complete 2/21, waiting for esc and mech reviews. Needs full special inspections form uploaded.
Routing - PLANNING3/4/2019 3/4/2019 PASS
DetailsKarla Nelson
Revised plans ok
PLANS/APPL TAKEN TO FRONT DESK  3/4/2019 DONE
DetailsJenny Nelson
Permit Ready to Issue  3/4/2019 DONE
need RP-the one on file is expired-Met
Telephone call  3/4/2019  
Email sent to arrow@berlum.com requesting a current license for the ESC responsible person before issuing BLDpermit
Routing - FIRE2/19/20192/19/20193/1/2019 PASS
DetailsLee G Meredith
Inadequate fire flow for size of residence. Emailed a copy of the review comments to Arrow Tallman.

3-1-19 Resubmittal passed. Contractor is going to supply an NFPA 13D sprinkler system.

3-18-19 Plan mod. New fire flow report from SUEZ provided. Sprinklers are not required.
1st review completed  3/1/2019 DONE
DetailsJenny Nelson
Routing - PLAN CHECK3/1/2019 3/1/2019 PASS
DetailsJenny Nelson
Routing - MECHANICAL2/19/2019 3/1/2019 PASS
DetailsChad Schwendiman
Routing - Erosion and Sediment2/19/2019 2/25/2019 PASS
DetailsMichael Zawacki
Hillside lot, site prep inspection required.
Routing - PLAN CHECK2/19/2019 2/22/2019 FAIL
DetailsJenny Nelson
Need special inspections form
Routing PW Grading-Hillside2/19/2019 2/21/2019 PASS
DetailsMelissa Jannusch
A letter from the applicant’s geotechnical engineer indicating that the footing/column subgrade is acceptable must be approved by Public Works prior to scheduling a footing inspection. Please e-mail the stamped inspection approval letter to mjannusch@cityofboise.org and allow 24 hours for subgrade approval processing. Call Melissa Jannusch at ###-#### with questions.

Prior to obtaining a final for the permit, the roof storm drainage system must be inspected by Public Works. Call Melissa Jannusch at ###-####.

The final inspection of the site grading and drainage work shall be done by the design engineer. Written approval shall be submitted to Boise Public Works prior to the issuance of the building final.

An erosion and sediment control site preparation inspection is required for this site. The site preparation inspection takes place after all required erosion and sediment control best management practices have been installed and BEFORE any earthwork takes place. Call ###-#### to schedule an inspection.



All disturbed slopes included in the construction of this project must be stabilized and approved by Public Works before a Final Occupancy Permit is granted. If weather conditions prohibit revegetation and stabilization activities, the contractor shall provide a bond/surety agreement or an irrevocable letter of credit in the amount of 110% of the cost estimated by the project engineer to enable stabilization of the site. Call ###-#### for an inspection.

Route to Impact Fee Review2/19/20192/22/20192/20/2019 PASS
DetailsKarina Myles
Initial residential review of new SFD permits requested for now.
Routing - Addressing2/19/2019 2/19/2019 PASS
DetailsDoug Chausow
Routing - PUBLIC WORKS2/19/2019 2/19/2019 PASS
DetailsMorgan Webb
Intake Approval  2/19/2019 PASS
CFH date Feb 8th
Recd Pcfee & Taken To Pln CK  2/19/2019 DONE
Intake Approval  2/14/2019 PASS
Failed per Melissa - CAT II hillside permit approved under CFH19-000001. Please upload Site suitability letter by Materials Testing and Inspection dated January 24, 2019 prior to acceptance for building permit review. Melissa ###-####
Application received  2/4/2019 DONE
Application submitted via PDS Online on Feb 4 2019 10:58AM
Routing - PLANNING2/19/2019   FAIL
Please show the entire driveway. Not to excede 33 ft. in width in front setback.