Third Notice | | 12/1/2019 | 12/30/2019 | | DONE |
|
|
|
This permit finaled on the web by Ronald Van Auker
|
Third Notice | | 11/3/2019 | 11/26/2019 | | DONE |
|
|
|
mailed 12-2-19
|
Second Notice | | 9/30/2019 | 10/29/2019 | | DONE |
|
|
|
mailed 11-1
|
First Notice | 8/19/2019 | 8/19/2019 | 9/20/2019 | | DONE |
Brandon Shaw
|
|
|
mailed 9-23-19
|
BLD-Final | 8/16/2019 | 8/19/2019 | 8/19/2019 | A | PASS |
Brandon Shaw
|
|
|
Corrections SAT
|
DOC - Permit Finaled | 8/19/2019 | 8/19/2019 | 8/19/2019 | P | PASS |
Brandon Shaw
|
|
|
|
PubWorks Occupancy Approval | 8/14/2019 | 8/14/2019 | 8/14/2019 | | DONE |
Tiffany Lowery
|
|
|
Engineer letter received 08/08/19. Project ok to sign off
|
BLD-Final | 8/8/2019 | 8/9/2019 | 8/9/2019 | A | PART |
Jim Storey
|
|
|
Jake Phone #: ###-#### need 2-exit signs// handrails at exterior stairs three risers.
|
FIRE-Final Inspection | 8/8/2019 | 8/9/2019 | 8/9/2019 | A | PASS |
Jim Page
|
|
|
Previously noted items have been corrected, sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are placed with current inspection tags, paint booth fan shut down tested with fire alarm interface. Final life fire safety inspection for area of work complete.
Jake Phone #: ###-####
|
FIRE-Final Inspection | 8/7/2019 | 8/8/2019 | 8/8/2019 | A | FAIL |
Jim Page
|
|
|
Need exhaust fan on paint booth to shut down when fire alarm activates. Repair emergency lighting that did not work on the exterior whip emergency light and fix the inop light on the interior middle door egress lighting.
JAKE- Phone #: ###-####
|
BLD-Energy code compliance | 6/26/2019 | 6/26/2019 | 6/26/2019 | P | PASS |
Jim Storey
|
|
|
ron Phone #: ###-####
|
BLD-Framing/Rough-in | 6/21/2019 | 6/24/2019 | 6/24/2019 | A | PASS |
Jim Storey
|
|
|
Ron Phone #: ###-####
|
BLD-Foundation | 5/30/2019 | 5/30/2019 | 5/30/2019 | P | PASS |
Jim Storey
|
|
|
rebar // Ron Phone #: ###-####
|
BLD-Foundation | 5/14/2019 | 5/15/2019 | 5/15/2019 | P | PASS |
Jim Storey
|
|
|
Ron Phone #: ###-####
|
BLD-Foundation | 5/10/2019 | 5/13/2019 | 5/13/2019 | A | PASS |
Jim Storey
|
|
|
partial // Ron Phone #: ###-#### s/w wall ok
|
BLD-Footing | 5/7/2019 | 5/8/2019 | 5/8/2019 | P | PASS |
Jim Storey
|
|
|
Ron Phone #: ###-####
|
Plan Reviewer's activity | | | 5/6/2019 | | DONE |
|
|
|
Uploaded revised Sheet A-1 showing an additional door to the outside.
|
Issue PAID IN FULL permit | | | 4/25/2019 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 4/25/2019 | | DONE |
|
|
|
|
OVERRIDE | | | 4/24/2019 | | |
|
|
|
|
Permit Ready to Issue | | | 4/24/2019 | | DONE |
|
|
|
NEED ACHD (WAITING TO HEAR FROM MITCH BLH 4-24)
MET GJENSEN@VANAUKER.COM
NEED GC
NEED Rev Val
|
Routing - FIRE | 4/18/2019 | 4/18/2019 | 4/23/2019 | | PASS |
Mark Scharfen
|
|
|
IFC Review Complete. IFC review 04.23.2019.pdf uploaded. Passed.
|
Plan assigned to (CJW) | 2/20/2019 | 2/26/2019 | 4/23/2019 | | PASS |
Carl Westfall
|
|
|
(1st done) 03/26/19 (new building - 25 days) (eplan - 38 sheets) Trimco Millwork Addition (routed to staff)
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/23/2019 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 4/17/2019 | | 4/18/2019 | | PASS |
Carl Westfall
|
|
|
|
Routing PW Drainage | 4/18/2019 | | 4/18/2019 | | PASS |
Brian Murphy
|
|
|
|
Plan resubmittals requested | | | 4/17/2019 | | DONE |
|
|
|
|
Plan resubmittals received | | | 4/17/2019 | | DONE |
|
|
|
|
Routing PW Drainage | 4/9/2019 | | 4/16/2019 | | FAIL |
Brian Murphy
|
|
|
NEEDS SIW FORM GEOTECH AND APENDEX J
|
Routing Off Site - STRUCTURAL | 4/9/2019 | | 4/16/2019 | | PASS |
Carl Westfall
|
|
|
Dave Haugland (AHJ)
|
Routing - FIRE | 4/9/2019 | 4/9/2019 | 4/12/2019 | | FAIL |
Mark Scharfen
|
|
|
IFC 2nd review 04.12.2019.pdf uploaded and emailed to applicant.
|
Routing PW Sewer Rating | 4/9/2019 | | 4/10/2019 | | PASS |
Morgan Webb
|
|
|
A "high" and a "low" drinking fountain will be installed. There may have been a single drinking fountain at that location earlier.
|
Plan resubmittals received | | | 4/9/2019 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 4/9/2019 | | 4/9/2019 | | FAIL |
Carl Westfall
|
|
|
|
Route to Impact Fee Review | 4/1/2019 | 4/4/2019 | 4/2/2019 | | PASS |
Karina Myles
|
|
|
Review requested for Commercial Permit
|
Routing - FIRE | 2/26/2019 | 2/26/2019 | 4/1/2019 | | FAIL |
Mark Scharfen
|
|
|
IFC 1st review 04.01.2019.pdf uploaded and emailed to applicant.
|
1st review completed | | | 4/1/2019 | | DONE |
|
|
|
|
Plan resubmittals requested | | | 4/1/2019 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 2/26/2019 | | 3/22/2019 | | FAIL |
Carl Westfall
|
|
|
|
Routing Off Site - STRUCTURAL | 2/26/2019 | | 3/11/2019 | | FAIL |
Carl Westfall
|
|
|
Dave Haugland (AHJ)
|
Routing PW Drainage | 2/26/2019 | | 3/5/2019 | | FAIL |
Brian Murphy
|
|
|
NEED SIW FORM GEO TECH 10 FEET FOUNATION, APDX J
|
Routing - PLUMBING | 2/26/2019 | | 3/5/2019 | | PASS |
Dan Ediger
|
|
|
Per ISPC
|
Routing PW Environmental | 2/26/2019 | | 3/5/2019 | | PASS |
Rick Christenson
|
|
|
|
Routing - Erosion and Sediment | 2/26/2019 | | 3/4/2019 | | PASS |
Michael Zawacki
|
|
|
Site prep inspection required.
|
Routing - MECHANICAL | 2/26/2019 | | 2/28/2019 | | PASS |
Troy James
|
|
|
Future dust collection system to be submitted at later date.
|
Routing PW Street Lights | 2/26/2019 | | 2/27/2019 | | PASS |
Tom Marshall
|
|
|
|
Routing PW Solid Waste | 2/26/2019 | | 2/27/2019 | | PASS |
Evan Carpenter
|
|
|
|
Routing PW Sewer Design | 2/26/2019 | | 2/26/2019 | | PASS |
DeAnn Brown
|
|
|
|
Routing - Design Review | 2/26/2019 | | 2/26/2019 | | PASS |
Katelyn Menuge
|
|
|
DRH18-00271
|
Routing - PLANNING | 2/26/2019 | | 2/26/2019 | | PASS |
David Moser
|
|
|
See DRH18-00271
|
Routing - Addressing | 2/26/2019 | | 2/26/2019 | | PASS |
Doug Chausow
|
|
|
|
Routing - PUBLIC WORKS | 2/26/2019 | | 2/26/2019 | | PASS |
Morgan Webb
|
|
|
|
Intake Approval | | | 2/20/2019 | | PASS |
Julie Romig
|
|
|
Prescreen approved per JAR
|
Intake Approval | | | 2/13/2019 | | FAIL |
Julie Romig
|
|
|
1. ESC Narrative (indicated on checklist but not found in small docs or on ESC plan)
2. Rotate all "Trimco PEMB" sheets to horizontal.
3. On all sheets, in the bottom right corner, leave a blank 4"x2" space located 3" off the right sheet edge for the city stamp.
|
Application received | | | 2/11/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Feb 11 2019 4:34PM
|