BLD-Final | 3/29/2019 | 4/1/2019 | 4/1/2019 | A | PASS |
Dave Hannah
|
|
|
Tina-(works with Nick) Phone #: ###-####
|
FIRE-Final Inspection | 3/29/2019 | 4/1/2019 | 4/1/2019 | A | PASS |
Jim Page
|
|
|
Fire sprinkler modifications completye (FIR19-00177), no fire alarm modifications, fire extinguishers are placed with current inspection tags, emergency lighting has been repaired since previous comments. Final life fire safety inspection complete.
830 // tina Phone #: ###-####
|
Permanent Occupancy | | | 4/1/2019 | | DONE |
|
|
|
|
Permanent Occupancy | | | 4/1/2019 | | DONE |
|
|
|
|
FIRE-Final Inspection | 3/29/2019 | 3/29/2019 | 3/29/2019 | P | CANC |
Jim Page
|
|
|
Spoke with point of contact, life fire safety inspection will be rescheduled to coincide with fire sprinkler inspection. This request is cancelled.
Tina-(works with Nick) Phone #: ###-####
|
BLD-Final | 3/1/2019 | 3/4/2019 | 3/4/2019 | A | CANC |
Dave Hannah
|
|
|
call ahead // Tina Phone #: ###-####
|
FIRE-Final Inspection | 3/1/2019 | 3/1/2019 | 3/1/2019 | P | FAIL |
Jim Page
|
|
|
Service or replace exit signs and emergency lighting that is inoperable as discussed. Provide annual inspections for fire extinguishers, last inspection for extinguishers was 2016. Fire sprinkler system has a current inspection tag. Preaction fire sprinkler system riser is still in place but has been disconnected and removed from service, fire sprinkler piping on the preaction system has been converted to a wet system but valve trim is still in place. Change pendant fire sprinkler that is to close to wall to a vertical sidewall to be code compliant.
call ahead // Nick Phone #: ###-####
|
Issue PAID IN FULL permit | | | 2/28/2019 | | DONE |
|
|
|
|
Plan assigned to (BJM) | 2/26/2019 | 2/26/2019 | 2/27/2019 | | DONE |
Brian McGowan
|
|
|
03/4 528 - (L1) Foothills School CofO
|
Routing - PLAN CHECK | 2/26/2019 | | 2/27/2019 | | PASS |
Brian McGowan
|
|
|
|
1st review completed | | | 2/27/2019 | | DONE |
Brian McGowan
|
|
|
|
Case Summary (BLD) | | | 2/27/2019 | | DONE |
Brian McGowan
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/27/2019 | | DONE |
Brian McGowan
|
|
|
|
Print Occupancy Form | | | 2/27/2019 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/27/2019 | | DONE |
|
|
|
met
|
Telephone call | | | 2/27/2019 | | DONE |
|
|
|
Left voicemail for Nick to inform him the permit is ready.
|
Intake Approval | | | 2/26/2019 | | PASS |
Brian McGowan
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 2/26/2019 | | DONE |
|
|
|
|
Application received | | 2/26/2019 | | | |
|
|
|
|