Permit Information
Permit NumberBLD19-00637
StatusFinaled
Name KNIGHT CONSTRUCTION LLC
Site Address 2141 W AIRPORT WAY Unit: 900
Project NameCardinal Health USP 797
Customer Number 
ePlanReviewYes
Description
(CARDINAL HEALTH) **5/8/2019 PLAN MODIFICATION TO REVISE THE RESTROOM LAYOUT SHOWN ON THE FLOORPLAN** *SPECIAL INSPECTIONS* required per the attached Form #310 for the post-installed concrete anchors for the laboratory panel system. Permit is for the construction of a clean room within an existing 2,079 sq. ft. pharmacy that was permitted under BLD00-00342 by Syncor International Corporation. Work is to include a new accessible restroom, new prefabricated laboratory panel walls, new non-bearing interior partitions, new accessible doors, laboratory equipment, new suspended ceiling, electrical, mechanical, plumbing, and finishes in compliance with Ch. 8 of the 2015 IBC. There is an existing 1-hour tenant wall noted on the drawings. NOTE: This building is fully fire sprinklered for area increase. Racking or storage that exceeds 8 ft. in height requires a separate Building Permit. Any alterations or modifications to the building’s Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT as regulated by the Boise Fire Department. **JHB**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice 8/7/20198/5/2019 DONE
This permit finaled on the web by Joseph knight
Second Notice 7/20/20198/2/2019 DONE
mailed out 8/5/19
First Notice 6/30/20197/10/2019 DONE
mailed 7-11
Permanent Occupancy  6/20/2019 DONE
BLD-Final6/13/20196/13/20196/13/2019PPASS
DetailsJim Storey
Phone #: ###-#### Inspection requested via web by Joseph knight
BLD-Final6/13/20196/13/20196/13/2019APASS
DetailsJim Storey
Phone #: ###-#### Inspection requested via web by Joseph knight
FIRE-Final Inspection6/13/20196/13/20196/13/2019PPASS
DetailsJim Page
Fire sprinkler inspection complete, no fire alarm modifications, fire extinguisher is placed with a current inspection tag. Final life fire safety inspection for area of work complete.
Zoning Approval6/13/20196/13/20196/13/2019 PASS
DetailsKayCee Babb
Rooftop mechanical equipment not visible, complying with CZC19-00061.
BLD-Framing/Rough-in6/12/20196/12/20196/12/2019PPASS
DetailsJim Storey
Have revised set og plans showing no changes to the bathroom. Building closes at 3pm Phone #: ###-#### Inspection requested via web by Joseph knight final ok pending fire.
FIRE-Final Inspection6/12/20196/12/20196/12/2019PCANC
DetailsJim Page
Inspection request will be rescheduled to coincide with fire sprinkler inspection. This request is cancelled per conversation with point of contact.

Joe Phone #: ###-####
Inspection Record Card- Bld  5/10/2019 DONE
CHANGE STATUS TO (ISS)  5/10/2019 DONE
Print Occupancy Form  5/10/2019 DONE
Plan assigned to (JHB)5/8/20195/8/20195/9/2019 PASS
DetailsJoe Bruce
(plan mod) Cardinal Health
Routing - PLAN CHECK5/9/2019 5/9/2019 PASS
DetailsJoe Bruce
Permit Ready to Issue  5/9/2019 DONE
PLAN MOD
Plan Modification Accepted  5/8/2019 DONE
Bathroom floorplan was updated to reflect correct orientation on the plan. no changes to the proposed work are being made
BLD-Ceiling Grid Inspection5/2/20195/3/20195/3/2019APASS
DetailsJim Storey
Phone #: ###-#### Inspection requested via web by Joseph knight
BLD-Framing/Rough-in4/28/20194/29/20194/29/2019APART
DetailsJim Sly
Phone #: ###-#### Inspection requested via web by Joseph knight
Inspection of Curb on roof for HVAC.....OK to cover.
Issue PAID IN FULL permit  4/26/2019 DONE
Print Occupancy Form  4/26/2019 DONE
(F) Reprint permit  4/26/2019 DONE
Print Occupancy Form  4/26/2019 DONE
Permit Ready to Issue  4/25/2019 DONE
ALL MET-Need-
GC form
Revised certificate of value
Plan assigned to (JHB)3/28/20193/28/20194/24/2019 PASS
DetailsJoe Bruce
(2nd Rev Comp) 04/10 (L2) Cardinal Health USP 797 ePlan
Plan resubmittals received  4/24/2019 DONE
DetailsJoe Bruce
Routing - Design Review4/24/2019 4/24/2019 PASS
DetailsKatelyn Menuge
Per CZC19-00061. Screening to be nonreflective and painted or naturally finished in a neutral color that complements the existing building.
PLANS/APPL TAKEN TO FRONT DESK  4/24/2019 DONE
Routing - Design Review4/15/2019 4/16/2019 FAIL
DetailsKayCee Babb
Rooftop screening for the new equipment is required, per CZC19-00061. Screening material, location, and dimensions are required for Design Review.
Plan resubmittals received  4/15/2019 DONE
DetailsJoe Bruce
Route to Impact Fee Review4/10/20194/13/20194/11/2019 PASS
DetailsShannon Cade
Review requested for Commercial Permit
Routing - FIRE3/28/20193/28/20194/10/2019 PASS
DetailsMark Scharfen
IFC review 04.10.2019.pdf uploaded.
1st review completed  4/10/2019 FAIL
DetailsJoe Bruce
Plan resubmittals requested  4/10/2019 DONE
DetailsJoe Bruce
CZC Appeal Period to end on Friday, April 12 @ 5:00pm.
Routing - PLAN CHECK3/28/2019 4/9/2019 PASS
DetailsJoe Bruce
Routing PW Environmental3/28/2019 4/1/2019 PASS
DetailsRick Christenson
Routing - PLUMBING3/28/2019 4/1/2019 PASS
DetailsDaryl Spivey
Per plan and ISPC.
Routing - MECHANICAL3/28/2019 3/29/2019 PASS
DetailsTroy James
Routing - Design Review3/28/2019 3/28/2019 FAIL
DetailsKayCee Babb
Design Review approval is required. CZC19-00061 has been submitted, but is still under review. No DR approval has been issued yet and no appeal period has occurred.
Intake Approval  3/28/2019 PASS
DetailsJavier Guzman
Routing - Addressing3/28/2019 3/28/2019 PASS
DetailsDoug Chausow
Routing - PUBLIC WORKS3/28/2019 3/28/2019 PASS
DetailsMorgan Webb
Intake Approval  3/27/2019 FAIL
DetailsJoe Bruce
03/27/2019 - Joe Bruce (Please address the items below) Please provide the following to complete you prescreen:
1) The structural engineering calculations are missing a stamp/signature by the engineer. Provide stamp/signature on the calculations.
2) Engineers stamp is not legible on sheet G001. Provide a legible stamp/signature on this sheet.
3) A majority of the plan sheets are missing a stamp/signature by the registered design professional. Please have ALL sheets stamped and signed by an engineer or architect.
4) New rooftop units require a certificate of zoning compliance including the air handling unit, condensing unit, and exhaust fan. Please contact Katelyn Menuge at ###-#### for more information on the application requirements. This certificate must be obtained prior to permit submittal.
5) Provide Form #310 - Statement of Special Inspections for the special inspections noted on sheet G002. The form can be downloaded from the City of Boise's website here: https://pds.cityofboise.org/media/104147/final310_special_inspections.pdf
6) Plan sheets (A501, A502, CRA-1, CRA-2, CRA-3, CRAD-1, CRM-1, CRM-2, CRM-3, and G004) do not have the required space reserved for City approval stamps as specified in the Electronic Plans Submittal Standards. Revise sheets with a blank 4” x 2” (4"x4" on cover) space located 3” off the right sheet edge to allow for the title block. Verify ALL plan sheets have the required space for city approval stamp. See electronic submittal standards at this link: https://pds.cityofboise.org/media/464072/pdox86_electronic_standards_full_050718.pdf
7) COMCheck reports are required to be signed and printed on the plans as stated in the checklist. Please place these forms on a plan sheet and upload into the "drawings" folder.
Intake Approval  3/5/2019 FAIL
DetailsJoe Bruce
Please provide the following to complete you prescreen:
1) The structural engineering calculations are missing a stamp/signature by the engineer. Provide stamp/signature on the calculations.
2) Engineers stamp is not legible on sheet G001. Provide a legible stamp/signature on this sheet.
3) A majority of the plan sheets are missing a stamp/signature by the registered design professional. Please have ALL sheets stamped and signed by an engineer or architect.
4) New rooftop units require a certificate of zoning compliance including the air handling unit, condensing unit, and exhaust fan. Please contact Katelyn Menuge at ###-#### for more information on the application requirements. This certificate must be obtained prior to permit submittal.
5) Provide Form #310 - Statement of Special Inspections for the special inspections noted on sheet G002. The form can be downloaded from the City of Boise's website here: https://pds.cityofboise.org/media/104147/final310_special_inspections.pdf
6) Plan sheets (A501, A502, CRA-1, CRA-2, CRA-3, CRAD-1, CRM-1, CRM-2, CRM-3, and G004) do not have the required space reserved for City approval stamps as specified in the Electronic Plans Submittal Standards. Revise sheets with a blank 4” x 2” (4"x4" on cover) space located 3” off the right sheet edge to allow for the title block. Verify ALL plan sheets have the required space for city approval stamp. See electronic submittal standards at this link: https://pds.cityofboise.org/media/464072/pdox86_electronic_standards_full_050718.pdf
7) COMCheck reports are required to be signed and printed on the plans as stated in the checklist. Please place these forms on a plan sheet and upload into the "drawings" folder.
Application received  2/28/2019 DONE
Application submitted via PDS Online on Feb 28 2019 2:45PM