BLD-Aging Inspection | 2/14/2020 | 2/14/2020 | 2/19/2020 | | DONE |
Tony Young
|
|
|
|
BLD-Aging Inspection | 2/13/2020 | 2/13/2020 | 2/14/2020 | | DONE |
Tony Young
|
|
|
|
BLD-Final | 9/30/2019 | 10/2/2019 | 10/2/2019 | A | PASS |
Tony Young
|
|
|
Steve Phone #: ###-####
|
FIRE-Final Inspection | 9/30/2019 | 10/1/2019 | 10/1/2019 | P | PASS |
Jim Page
|
|
|
Prevously noted items have been corrected, per IBC definition, the area of work is defined as a platform and not a stage, per the 2015 edition of NFPA 13, platforms do not require sprinklers as long as the items listed under 8.15.6.2 are met, walls and lid of little mech room under the platform have been sheetrocked and taped, this meets the requirements of the mentioned NFPA 13 section. No fire alarm modifications, fire sprinkler inspection is complete, fire extinguihsers are placed with current inspection tags. Final life fire safety inspection for area of work complete.
.Steve Phone #: ###-####
|
BLD-Final | 9/25/2019 | 9/27/2019 | 9/27/2019 | A | CANC |
Tony Young
|
|
|
Steve Phone #: ###-####
|
BLD-Final | 9/26/2019 | 9/26/2019 | 9/26/2019 | P | NR |
Tony Young
|
|
|
Steve Phone #: ###-####
|
FIRE-Final Inspection | 9/25/2019 | 9/26/2019 | 9/26/2019 | A | FAIL |
Jim Page
|
|
|
Provide fire sprinklers under stage area per NFPA, section 8.15.17 or meet the exceptions listed under 8.15.1 of NFPA 13.
Steve Phone #: ###-####
|
BLD-Framing/Rough-in | 7/1/2019 | 7/2/2019 | 7/2/2019 | A | PART |
Tony Young
|
|
|
Steve Phone #: ###-####,, deck sheeting,, work in progress,, ok
|
BLD-Energy code compliance | 6/24/2019 | 6/26/2019 | 6/26/2019 | A | PART |
Tony Young
|
|
|
Steve- dry wall inspection Phone #: ###-####,, ok to re-cover soffit areas,, no changes made
|
BLD-Framing/Rough-in | 6/24/2019 | 6/26/2019 | 6/26/2019 | A | PART |
Tony Young
|
|
|
Steve Phone #: ###-####,, stage frame ok
|
Inspection Record Card- Bld | | | 6/24/2019 | | DONE |
|
|
|
|
BLD-Conference | 5/15/2019 | 5/16/2019 | 5/16/2019 | P | PART |
Tony Young
|
|
|
Steve-please call with a meet time Phone #: ###-####,, site review,,
|
BLD-Conference | 5/16/2019 | 5/16/2019 | 5/16/2019 | A | PART |
Tony Young
|
|
|
Steve-please call with a meet time Phone #: ###-####,, ?s on stage
|
Place hold on job | 4/19/2019 | | 5/15/2019 | | DONE |
Candy A. Nichols
|
|
|
waiting for signed permit
|
Meeting | | | 4/22/2019 | | DONE |
|
|
|
Emailed a reminder email to cwhitt@petrainc.net, to please print and sign on the building permit and email it back to us.
|
Permit Ready to Issue | | | 4/19/2019 | | DONE |
|
|
|
all met-NEED
GC FORM -met
REVISED VALUE-met
emailed cwitt@petrainc.net
|
Inspection Record Card- Bld | | | 4/19/2019 | | DONE |
|
|
|
|
Issue PAID IN FULL permit | | | 4/19/2019 | | DONE |
|
|
|
|
Routing - FIRE | 4/17/2019 | 4/17/2019 | 4/18/2019 | | PASS |
Mark Scharfen
|
|
|
IFC Review complete. 04.18.2019.pdf
|
Plan assigned to (JHB) | 4/11/2019 | 4/11/2019 | 4/18/2019 | | PASS |
Joe Bruce
|
|
|
(1st Rev Comp) 04/15 - L2 First Presbyterian Church (Fire, Plan Check)
|
PLANS/APPL TAKEN TO FRONT DESK | | | 4/18/2019 | | DONE |
|
|
|
|
Plan resubmittals received | | | 4/17/2019 | | DONE |
Joe Bruce
|
|
|
|
Routing - PLAN CHECK | 4/17/2019 | | 4/17/2019 | | PASS |
Joe Bruce
|
|
|
|
Route to Impact Fee Review | 4/15/2019 | 4/18/2019 | 4/16/2019 | | PASS |
Karina Myles
|
|
|
Review requested for Commercial Permit
|
Plan resubmittals requested | | | 4/15/2019 | | DONE |
Joe Bruce
|
|
|
|
Routing - FIRE | 4/3/2019 | 4/3/2019 | 4/12/2019 | | FAIL |
Mark Scharfen
|
|
|
IFC 1st review 04.12.2019.pdf uploaded and emailed to architect.
|
Routing - PLAN CHECK | 4/3/2019 | | 4/12/2019 | | FAIL |
Joe Bruce
|
|
|
|
1st review completed | | | 4/12/2019 | | FAIL |
Joe Bruce
|
|
|
|
Plan assigned to (JAR) | 4/3/2019 | 4/3/2019 | 4/11/2019 | | DEFR |
Julie Romig
|
|
|
04/12 - L2 First Presbyterian Church
|
Intake Approval | | | 4/2/2019 | | FAIL |
Michael Hanson
|
|
|
Provide completed #310 form.
|
Intake Approval | | | 4/2/2019 | | PASS |
Michael Hanson
|
|
|
Prescreen approved by M_H
|
Application received | | | 3/28/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Mar 28 2019 5:53PM
|