Permit Information
Permit NumberBLD19-01074
StatusFinaled
Name MJT CONSTRUCTION INC
Site Address 7100 W STATE ST
Project NameAlbertsons
Customer Number 
ePlanReviewYes
Description
(ALBERTSONS – NORTHGATE SHOPPING CENTER) Fire sprinklers used for building area increase. To remodel the exterior wall finish of an existing retail sales building. Work it to include new exterior storefront and new exterior masonry walls that encloses 195 sq. ft. of area to the entry that is currently located underneath the existing roof canopy, new automatic sliding doors, new exterior masonry walls, construction of a new canopy, new exterior finishes will be installed including an Exterior Insulation and Finish System. The work is required to comply with the approved drawings, with the plan review report, with the Structural design, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department including fire sprinkler protection within concealed combustible spaces. **JHB**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Second Notice 9/29/20199/26/2019 DONE
This permit finaled on the web by Michele Rodgers
First Notice9/4/20199/4/20199/19/2019 DONE
DetailsTony Young
mailed 9-20-19
BLD-Final9/3/20199/4/20199/4/2019APASS
DetailsTony Young
building final inspection please call 30 minutes ahead so I can meet you at the site. Mike Teeter ###-####

thanks
Mike Phone #: ###-#### Inspection requested via web by Mike Teeter
DOC - Permit Finaled9/4/20199/4/20199/4/2019PPASS
DetailsTony Young
FIRE-Final Inspection9/4/20199/4/20199/4/2019PPASS
DetailsJim Page
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in common areas with current inspection tags. Final life fire safety inspection for are of work complete.

per 415
BLD-Final8/28/20198/29/20198/29/2019PPEND
DetailsTony Young
if you could please call 30 minutes ahead of time for the inspection that would be greatly appreciated Mike Teeter ###-####

Thanks
Mike Teeter
Phone #: ###-#### Inspection requested via web by Mike Teeter
BLD-Final8/27/20198/28/20198/28/2019APEND
DetailsTony Young
if you could please call 30 minutes ahead of time for the inspection that would be greatly appreciated Mike Teeter ###-####

Thanks
Mike Teeter
Phone #: ###-#### Inspection requested via web by Mike Teeter,, needs trades, final letter from engineer
BLD-Other6/18/20196/18/20196/19/2019PPART
DetailsTony Young
Tom- shear nail front tower on roof Phone #: ###-####,, pending special inspection
BLD-Wall cover6/17/20196/17/20196/18/2019PPART
DetailsTony Young
nails on roof // Tom Phone #: ###-####,, hold down straps,, lower roof sheathing ok
BLD-Wall cover6/13/20196/14/20196/14/2019APART
DetailsTony Young
shear nailing, exterior right tower // Tom Phone #: ###-####,, work in progress.. ok
BLD-Framing/Rough-in6/12/20196/13/20196/13/2019APART
DetailsTony Young
Tom Phone #: ###-####,, front facia framing on east side ok,, work in progress,, also will have special inspection
BLD-Framing/Rough-in5/28/20195/29/20195/30/2019PPART
DetailsTony Young
Tom Phone #: ###-####,, front area for sign,, special inspector on site,, pending report
Issue PAID IN FULL permit  5/9/2019 DONE
emailed michele@mjtconstruction.com to sign permit
Inspection Record Card- Bld  5/9/2019 DONE
Plan assigned to (JHB)4/11/20194/11/20195/8/2019 PASS
DetailsJoe Bruce
05/07 (2nd Rev) 04/23 (L2) Albertsons ePlan (Bldg, Fire, DR)
Routing Off Site - STRUCTURAL5/1/2019 5/8/2019 PASS
DetailsJoe Bruce
PLANS/APPL TAKEN TO FRONT DESK  5/8/2019 DONE
Permit Ready to Issue  5/8/2019 DONE
Need GC-met
Need Rev Val-met
Routing - PLAN CHECK5/1/2019 5/7/2019 PASS
DetailsJoe Bruce
Routing - Design Review5/1/2019 5/2/2019 PASS
DetailsKayCee Babb
Per DRH19-00089 and sheets A0.1 and A3.2 submitted April 30, 2019. To comply with all conditions of approval and redlines, including providing 14 bicycle parking stalls on site.
Plan resubmittals received  5/1/2019 DONE
DetailsJoe Bruce
Route to Impact Fee Review4/23/20194/26/20194/24/2019 PASS
DetailsKarina Myles
Review requested for Commercial Permit
Routing - FIRE4/11/20194/11/20194/23/2019 PASS
DetailsMark Scharfen
IFC Review complete 04.23.2019. No report needed.
1st review completed  4/23/2019 FAIL
Plan resubmittals requested  4/23/2019 DONE
DetailsJoe Bruce
Routing - PLAN CHECK4/11/2019 4/23/2019 FAIL
DetailsJoe Bruce
Routing Off Site - STRUCTURAL4/11/2019 4/22/2019 FAIL
DetailsJoe Bruce
ahj
Routing - MECHANICAL4/11/2019 4/11/2019 PASS
DetailsTroy James
Routing - Addressing4/11/2019 4/11/2019 PASS
DetailsDoug Chausow
Routing - PUBLIC WORKS4/11/2019 4/11/2019 PASS
DetailsAngela Hardy
Routing - Design Review4/11/2019 4/11/2019 FAIL
DetailsKayCee Babb
Project shall comply with all conditions of approval associated with DRH19-00089, including: painted crosswalks shall be the full width of the curb ramps and enter the parking lot aisle at a perpendicular manner, not angled - pathway through the landscape terminal may be used in addition to required crosswalk; show bicycle parking on site plan that meets dimensional standards; both entries require a minimum 3' canopy or recessed entry - clearly indicate on site plan the depth of the canopy over the western most entry.
Intake Approval  4/10/2019 PASS
DetailsJavier Guzman
Intake Approval  4/5/2019 FAIL
DetailsJoe Bruce
1) Plan sheet, A3.2 do not have the required space reserved for City approval stamps as specified in the Electronic Plans Submittal Standards. Revise sheets with a blank 4” x 2” space located 3” off the right sheet edge to allow for the title block. Verify ALL plan sheets have the required space for city approval stamp.
2) The incorrect mechanical code is listed on the "Project Information" - See sheet G0.1. The city of Boise has adopted the 2012 International Mechanical Code. Please revise the drawings to reflect the updated code.
3) The building type III-N is not an applicable construction type within the 2015 International Building Code. Please classify the construction type of the building that aligns with the 2015 IBC.
4) Sheet S0.1 "Special Inspection" drawing states the incorrect building code and code references in Chapter 17. The City of Boise has adopted the 2015 International Building Code. Please update the referenced code sections on this sheet and utilize the 2015 IBC for special inspections.
Application received  4/4/2019 DONE
Application submitted via PDS Online on Apr 4 2019 10:56AM