Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberBLD19-01675
StatusReady to Issue
Name THE EWING COMPANY INC
Site Address 1390 W GOWEN RD
Project NameITD Aeronautics Hangar/Office
Customer Number 
ePlanReviewYes
Description
(ITD AERONAUTICS HANGAR AND OFFICE) ""PLAN MODIFICATION TO RECONFIGURE DUCTING AND ADD A FIRE DAMPER""Deferred submittal received for office portion of the metal building on 2/21/20 (approved). GREEN BUILDING CONSTRUCTION"" **DEFERRED SUBMITTAL FOR PRE-ENGINEERED METAL HANGAR BUILDING STRUCTURE** ** DEFERRED SUBMITIALS HAVE BEEN RECEIVED AND APPROVED FOR THE HANGAR PORTION OF THE STRUCTURE WITH DEFERRED SUBMITTALS STILL PENDING FOR THE OFFICE PORTION OF THE BUILDING. Permit to construct a new aircraft hangar and office/support space for the Idaho Transportation Department Aeronautics division. This project is a green building to be constructed under the 2012 International Green Construction Code (IGCC). Work to include:
Contact Information
See Activities list for contact information
Color Key
Current location of plans being reviewed:  
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
OVERRIDE  8/12/2020  
Plan assigned to (CDM)7/31/20207/31/20208/12/2020 PASS
DetailsCarl D Madsen
Routing - PLAN CHECK8/4/2020 8/12/2020 PASS
DetailsCarl D Madsen
Permit Ready to Issue  8/12/2020 DONE
plan mod approved
Routing - MECHANICAL8/4/2020 8/4/2020 PASS
DetailsTroy James
Plan Modification Accepted  7/31/2020 DONE
Added HVAC fire damper
BLD-Conference7/29/20207/30/20207/30/2020APASS
DetailsJim Storey
Please call prior to coming onsite Phone #: ###-#### Inspection requested via web by Cody Sandercock aproved fire stopping assembly for line sets.
BLD-Ceiling Grid Inspection7/15/20207/16/20207/16/2020ANR
DetailsJim Storey
Phone #: 6786443014 >> Inspection requested via mobile web by Cody Sandercock
BLD-Wall cover7/9/20207/9/20207/9/2020PPASS
DetailsJim Storey
Phone #: 6786443014 >> Inspection requested via mobile web by Cody Sandercock screw sch ok for rated walls// fire stopping not done at this time.
BLD-Wall cover6/5/20206/8/20206/8/2020APASS
DetailsJim Storey
Phone #: 6786443014 >> Inspection requested via mobile web by Cody Sandercock top of wall ok/ ok to start wallcover.
BLD-Framing/Rough-in5/27/20205/28/20205/28/2020APASS
DetailsJim Storey
As early as possible Phone #: 6786443014 >> Inspection requested via mobile web by Cody Sandercock/ framing of walls ok to top fof sliptrack
BLD-Other5/18/20205/19/20205/19/2020AFAIL
DetailsJim Storey
Phone #: 6786443014 >> Inspection requested via mobile web by Cody Sandercock c/n provide ul head of wall detail or have plan reviewer c madsen aprove as built.
BLD-Conference4/23/20204/24/20204/24/2020PPEND
DetailsJim Storey
Phone #: 6786443014 >> Inspection requested via mobile web by Cody Sandercock submittal for corridor design.
BLD-Conference4/15/20204/16/20204/16/2020APASS
DetailsJim Storey
Phone #: 6786443014 >> Inspection requested via mobile web by Cody Sandercock
BLD-Framing/Rough-in4/15/20204/16/20204/16/2020APASS
DetailsJim Storey
Phone #: 6786443014 >> Inspection requested via mobile web by Cody Sandercock hanger fur out and insulation ok.
BLD-Conference4/10/20204/13/20204/13/2020APASS
DetailsJim Storey
Phone #: 6786443014 >> Inspection requested via mobile web by Cody Sandercock roof insulation ok/ conf ok
FIRE-Conference4/9/20204/10/20204/10/2020ACANC
DetailsTroy Cobbley
Needed building inspector conference on the rated wall.

Phone #: 6786443014 >> Inspection requested via mobile web by Cody Sandercock
BLD-Framing/Rough-in4/8/20204/8/20204/8/2020PPASS
DetailsDave Hannah
hanger ok
BLD-Conference4/7/20204/8/20204/8/2020PPASS
DetailsDave Hannah
Phone #: 6786443014 >> Inspection requested via mobile web by Cody Sandercock
BLD-Conference4/3/20204/6/20204/6/2020ADONE
DetailsDave Hannah
Phone #: 6786443014 >> Inspection requested via mobile web by Cody Sandercock
BLD-Conference4/2/20204/3/20204/3/2020ADEFR
DetailsTony Young
Phone #: 6786443014 >> Inspection requested via mobile web by Cody Sandercock // called to defr for Monday
BLD-Conference4/1/20204/2/20204/2/2020ACANC
DetailsJim Storey
Phone #: 6786443014 >> Inspection requested via mobile web by Cody Sandercock Inspection cancelled via mobile web on Thursday, April 02, 2020.
OVERRIDE  3/23/2020  
Meeting  3/23/2020 DONE
Per Angela Project Manager, We do not charge admin fees on deferred submittals. Taking off admin fee and changing status back to issued. ITD project.
CHANGE STATUS TO (ISS)  3/23/2020 DONE
Per Angie Project Manager: Deferred Submittal changing status to issued. No fees are due
Permit Ready to Issue  3/23/2020 DONE
**PLAN MOD - DO NOT REISSUE**
Plan assigned to (CDM)1/13/20201/13/20203/20/2020 PASS
DetailsCarl D Madsen
Routing Off Site - STRUCTURAL3/13/2020 3/20/2020 PASS
DetailsCarl D Madsen
BLD-Concrete3/6/20203/11/20203/11/2020PPASS
DetailsJim Storey
Cody Phone #: ###-#### slab west rebar vappor barrior and primetor insulation ok// wall and roof insulation 30/35 ok per envolope.
Routing Off Site - STRUCTURAL2/19/2020 3/11/2020 FAIL
DetailsCarl D Madsen
Routing - PLUMBING2/27/2020 2/27/2020 PASS
DetailsDan Ediger
Routing - PLAN CHECK2/19/2020 2/27/2020 PASS
DetailsCarl D Madsen
BLD-Footing2/3/20202/4/20202/4/2020APEND
DetailsDave Hannah
Cody Phone #: ###-####14 needs to clean mud off rebar needs to get frost out of ground, spec. inspector needs to ok final aproval
CHANGE STATUS TO (ISS)  1/13/2020 DONE
(F) Reprint permit  1/13/2020 DONE
Plan Modification Accepted  1/13/2020 DONE
Deferred submittal (per angie). Submit pre-engineered metal building plans for the Idaho Transportation Aeronautics office Building. (see letter in documents)
OVERRIDE  1/10/2020  
Permit Ready to Issue  1/10/2020 DONE
**DO NOT REISSUE - PLAN MOD**
Routing Off Site - STRUCTURAL1/7/2020 1/10/2020 PASS
DetailsCarl D Madsen
1/2 of engineering fees billed as this was a plan mod/deferred submittal.
BLD-Concrete1/7/20201/8/20201/8/2020APASS
DetailsJim Storey
AL - vapor barrier Phone #: ###-####
Routing - PLAN CHECK12/12/2019 12/31/2019 PASS
DetailsCarl D Madsen
deferred submittal
Routing Off Site - STRUCTURAL12/16/2019 12/31/2019 FAIL
DetailsCarl D Madsen
CH2M Routed back to applicant for correction 12/31/2019 CDM
BLD-Footing12/23/201912/24/201912/24/2019APASS
DetailsBrandon Shaw
concrete at 8:30 am // Al Phone #: ###-####
BLD-Footing12/16/201912/17/201912/17/2019PFAIL
DetailsJim Storey
Al Phone #: ###-#### ground frozen/ bare exposer to close to grade// si to address if placed.
Plan Modification Accepted  12/12/2019  
DetailsCarl D Madsen
Deferred submittal for pre-engineered metal building, phase 1, hangar
BLD-Footing12/10/201912/11/201912/11/2019PPASS
DetailsJim Storey
Al Phone #: ###-#### 6ft east/west
BLD-Footing12/4/201912/5/201912/5/2019APASS
DetailsJim Storey
Al Phone #: ###-#### rebar ok si onsite cmu wall ft
Issue PAID IN FULL permit  10/1/2019 DONE
Print Occupancy Form  10/1/2019 DONE
OVERRIDE  9/23/2019  
Permit Ready to Issue  9/23/2019 DONE
MET
Need
Revised Cert of Value (IN THERE 9/20/19)
Plan assigned to (CDM)5/22/20195/24/20199/20/2019 PASS
DetailsCarl D Madsen
ITD Aeronautics Hangar/Office
PLANS/APPL TAKEN TO FRONT DESK  9/20/2019 DONE
Routing - PLAN CHECK9/16/2019 9/16/2019 PASS
DetailsCarl D Madsen
Routing - PLAN CHECK9/9/2019 9/16/2019 PASS
DetailsCarl D Madsen
Routing - MECHANICAL9/9/2019 9/11/2019 PASS
DetailsTroy James
Approved pending building review approval for fire damper requirements at corridor.
Routing - PLANNING9/9/2019 9/10/2019 PASS
DetailsKarla Nelson
Planter islands have been waived for this case.
Routing PW Street Lights9/10/2019 9/10/2019 PASS
DetailsTom Marshall
Routing PW Street Lights9/9/2019 9/9/2019 FAIL
DetailsTom Marshall
Plan resubmittals received  9/9/2019 DONE
DetailsJoe Bruce
Plan resubmittals received  9/6/2019 FAIL
DetailsJoe Bruce
Please provide the following before your resubmittal is accepted.
1) Sheets M01, M21, and M61 have a stamp by the registered design professional that is black and not legible when printed in grayscale/monochrome. Please revise the engineers stamp to be legible. Engineers stamp on original submittal was legible.
2) Sheet A0.1 is blank and appears to be missing information. Resubmit this sheet with appropriate information.
Routing - FIRE8/23/20198/23/20198/26/2019 PASS
DetailsMark Scharfen
08/29-ITD Hanger Resubmittal review completed 08.26.2019. Uploaded rev_fire 08.26.2019.pdf.
Routing - PLAN CHECK8/23/2019 8/24/2019 FAIL
DetailsCarl D Madsen
This resubmittal was only for Fire review. Additional resubmittals for mechanical, green building and street lights are pending.
Routing - PLAN CHECK7/30/2019 8/17/2019 FAIL
DetailsCarl D Madsen
Routing Off Site - STRUCTURAL7/30/2019 8/17/2019 PASS
DetailsCarl D Madsen
Routing PW Drainage7/31/2019 8/8/2019 PASS
DetailsBrian Murphy
Routing - FIRE7/30/20197/30/20198/6/2019 FAIL
DetailsMark Scharfen
08.06.2019-Completed 2nd review. Uploaded rev_fire 08.06.2019.pdf and emailed architect.
Routing PW Street Lights7/31/2019 7/31/2019 FAIL
DetailsTom Marshall
Routing PW Sewer Design7/31/2019 7/31/2019 PASS
DetailsDeAnn Brown
Route to Impact Fee Review7/2/20197/5/20197/2/2019 PASS
DetailsShannon Cade
Review requested for Commercial Permit
Routing - FIRE5/22/20195/22/20197/2/2019 FAIL
DetailsMark Scharfen
07.02.2019-Completed fire review. Uploaded rev_fire 07.02.2019.pdf and emailed applicant.
1st review completed  7/2/2019 DONE
Routing Off Site - STRUCTURAL5/24/2019 6/28/2019 FAIL
DetailsCarl D Madsen
CH2M Hill
Routing - PLAN CHECK5/22/2019 6/28/2019 FAIL
DetailsCarl D Madsen
Routing - MECHANICAL5/22/2019 6/12/2019 PASS
DetailsTroy James
Routing - PLUMBING5/22/2019 6/12/2019 FAIL
DetailsDan Ediger
See detail for Sand and oil separator does not meet code.
The duplex ejection system requires 3" minimum pumps and discharge line.
Routing PW Sewer Design5/28/2019 6/12/2019 PASS
DetailsDeAnn Brown
2" pressure service is a private sewer facility and must meet the plumbing code requirements.
Routing PW Environmental5/28/2019 6/12/2019 PASS
DetailsTerry Alber
Approved with no fire suppression foam system. Should fire suppression foam system be installed, automatic valve downstream of oil/sediment interceptor required.
Routing - PLANNING5/22/2019 6/4/2019 PASS
DetailsKarla Nelson
Passed with the condition that the landscape plan be modified to include internal planter islands for every grouping of parking that exceeds 10 spaces. Terminal planters shall be provided a the ends of rows. Landscape planters shall be a minimum of 8' and shall be landscaped with at least 1 tree and shall be covered with shrubs or other vegetative groundcover.
Note on plan call for a maximum height of 76'. The M-1 district only allows for heights of 55' any structure or equipment in excess of 55' will require a conditional use permit.
Routing - PLUMBING9/23/2019 6/3/2019 PASS
DetailsDaryl Spivey
Per plan and ISPC.
Routing - Addressing5/22/2019 5/31/2019 PASS
DetailsDoug Chausow
Corrected address to 1390 W Gowen Rd
Routing - PUBLIC WORKS5/22/2019 5/31/2019 PASS
DetailsAngela Hardy
Routing - Erosion and Sediment5/22/2019 5/30/2019 PASS
DetailsAndy J. Long
SWPPP/ESC plan approved. Contractor and ESC Responsible Person TBD. Site preparation inspection is required.
Routing PW Solid Waste5/28/2019 5/29/2019 PASS
DetailsPeter J. McCullough
Routing PW Street Lights5/28/2019 5/29/2019 FAIL
DetailsTom Marshall
Need street light plan for Gowen Rd.
Intake Approval  5/22/2019 PASS
DetailsJoe Bruce
Intake approval/fees paid 5/22/19
Intake Approval  5/14/2019 FAIL
DetailsJoe Bruce
Provide the following items to complete the prescreen process:
1) Plan sheets do not have the required space reserved for City approval stamps as specified in the Electronic Plans Submittal Standards. Revise sheets with a blank 4” x 2” space located 3” off the right sheet edge to allow for the title block. Verify ALL plan sheets have the required space for city approval stamp.
2) Site Specific Fire Flow at the fire hydrant letter is required from Suez Water. Please email: katie.birkenstein@suez.com for your request to receive the required letter for plan review. Upload this document into the documents folder.
3) Form #310 – “Statement of Special Inspections” is required to be completed by the structural engineer for the metal deck and welding. Provide this information on the form.
4) The prefabricated metal building do not appear to be submitted. Please submit the metal building drawings as required. A letter signed by Jason Blais (Building Official) might be accepted if a deferred submittal is desired.
5) The permanent operation & maintenance agreement form is required to be mailed or dropped off to Brian Murphy. Please contact Brian Murphy at ###-#### regarding this requirement.
6) Provide an Erosion & Sediment Control Narrative for this project. No document could be locate in the documents folder.
7) The heating and cooling load calculations could not be found attached to the plans. Please provide the heating and cooling load calcs on the plans or submitted as separate documents.
Application received  5/10/2019 DONE
Application submitted via PDS Online on May 10 2019 12:17PM
Routing PW Drainage5/28/2019   FAIL
DetailsBrian Murphy
need airort o and m