Permit Information
Permit NumberBLD19-01795
StatusReady to Issue
Name K2 CONSTRUCTION
Site Address 1800 W FAIRVIEW AVE
Project NameRed Lion Downtowner
Customer Number 
ePlanReviewYes
Description
(RED LION) //1-13-2020 PLAN MODIFICATION TO FRAME AND ENCLOSE DRYERS WITH MAINTANENCE ACCESS DOOR INTO THE REAR DRYER ENSCLOSED AREA. JG// Permit is to remodel an existing 971 sq. ft. conference room and convert it to a laundry room within the existing hotel main floor. Approval is contingent upon adhering to the approved plans on file. Work to include: removal of floor carpet and replace with vinyl flooring, mechanical work, plumbing work and electrical work. This building is fully Fire Sprinklered. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JG**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permit Ready to Issue  1/31/2020 DONE
DO NOT ISSUE- plan mod approved
Plan assigned to (JG)1/10/20201/10/20201/30/2020 PASS
DetailsJavier Guzman
01/21 Plan Mod Red Lion Downtowner ePlan, pend fire
Routing - FIRE1/14/20201/14/20201/24/2020 PASS
DetailsErika Akin
No change to previous comments for plan mod
Routing - PLAN CHECK1/14/2020 1/22/2020 PASS
DetailsJavier Guzman
Door behind dryers is for access only and no an occupied space. **Revised comment from JG after conversation with Doug at JGT architecture.** Plan mod was passed by JHB
Route to Impact Fee Review1/10/20201/13/20201/14/2020 PASS
DetailsTravis P Black
Review requested for Commercial Permit
Plan Modification Accepted  1/10/2020 DONE
J. Gregory Toolson requested a plan mod workflow. Enclose dryers with frame wall with access door into enclosure for maintenance purposes. Sheet A-1.0
Plan Reviewer's activity  1/7/2020 DONE
DetailsJoe Bruce
Phone conversation with Phillip and mentioned he will be submitting a plan modification to add the wall in laundry room. **JHB**
Plan Reviewer's activity  12/20/2019 DONE
DetailsJoe Bruce
Received a call from Phillip, facility manager for Red Lion and he mentioned that phase II will be submitted with additional walls that will be installed in the laundry room that will be submitted by K2 construction after Dec. 25th. This permit cannont be finaled until phase 2 is completed due to fire sprinkler spacing. **JHB**
Plan Reviewer's activity  12/19/2019 DONE
DetailsJoe Bruce
Spoke with Jim Page about extending Temp Occupancy. 90 days from 10/15/19 would be 1/13/20. Contractor would like additional 90 days to complete the project. The new date for Temp is 4/12/20. An occupancy has already been established for this tenant. It shall remain in effect. **JHB**
BLD-Final10/14/201910/15/201910/15/2019PPART
DetailsDave Hannah
Dennis Phone #: ###-#### ok for tco ok to go perm after fire oks for permt
FIRE-Final Inspection10/14/201910/15/201910/15/2019APART
DetailsJim Page
Exit signage and emergency lighting that was noted on the past life safety inspections has been replaced and operational, sprinkler and fire alarm modifications are required due to the change in occupancy for area of work, fire alarm and fire sprinkler modifications are being designed and submitted for review. Partial final inspection for life fire safety is complete, fire exitnguisher is placed, inspection tag for fire exitguisher expired in september of 2019, fire extinguishers will need annual inspection performed before next final life fire safety inspection, annual inspection of fire extinguihsers will be verified at that time. Reccomend replacing the 2 fire sprinklers above dryers to a higher temp head, heads in place appear to be 165 degree heads. Per conversation with Ron Johnson with Boise Fire a 90 day TCO is authorized for life fire safety contingent upon fire sprinkler and fire alarm modifications being submitted, approved, inspected and passed. A follow up inspection will be required for life fire safety when the fire sprinkler and fire alarm modifications have been finaled.

Dennis Phone #: ###-####
FIRE-Final Inspection10/14/201910/14/201910/14/2019PCANC
DetailsJim Page
Phone number provided for point of contact was not the correct phone number for Dennis, provide correct phone number for point of contact for proper coordination of inspection completion, this request is cancelled.

dennis Phone #: ###-####
FIRE-Final Inspection10/7/201910/7/201910/7/2019PFAIL
DetailsTroy Cobbley
Need the emergency dialer replacement permit, FIR19-00467, finaled first, need city approved plans and small documents, need tagged/mounted fire extinguisher, need exit signs in the room and the two paths of egress repaired, possibly need emergency lighting, sprinklers were spaced for the old light hazard conference room but now the room is an ordinary hazard Laundry room, the fire alarm strobes are overspaced from the northeast corner of the room.....ect.


Dennis Phone #: ###-####
BLD-Final10/7/201910/7/201910/7/2019PCANC
DetailsDave Hannah
Dennis Phone #: ###-####
BLD-Final10/4/201910/7/201910/7/2019ACANC
DetailsDave Hannah
Denise Phone #: ###-#### needs fire finals
BLD-Framing/Rough-in8/2/20198/2/20198/2/2019PPASS
DetailsDave Hannah
Dennis Phone #: ###-####
Issue PAID IN FULL permit  6/25/2019 DONE
Inspection Record Card- Bld  6/25/2019 DONE
Plan assigned to (JG)5/24/20195/24/20196/24/2019 PASS
DetailsJavier Guzman
2nd rev comp, 06/18 L3 Red Lion Downtowner ePlan, pend fire
Routing - PLAN CHECK6/24/2019 6/24/2019 PASS
DetailsJavier Guzman
PLANS/APPL TAKEN TO FRONT DESK  6/24/2019 DONE
Permit Ready to Issue  6/24/2019 DONE
all met emailed Robert Pryor -Need GC
Need Rev Val
Routing - FIRE5/24/20195/24/20196/20/2019 PASS
DetailsMark Scharfen
06.20.2019-Completed fire review. Uploaded rev_fire 06.20.2019.pdf.
1st review completed  6/20/2019 DONE
Routing PW Environmental5/28/2019 6/12/2019 PASS
DetailsTerry Alber
Trench drain requires lint screening.
Routing - PLAN CHECK5/24/2019 6/12/2019 FAIL
DetailsJavier Guzman
Routing - MECHANICAL5/24/2019 5/29/2019 PASS
DetailsTroy James
Routing - Addressing5/24/2019 5/29/2019 PASS
DetailsDoug Chausow
Routing - PUBLIC WORKS5/24/2019 5/28/2019 PASS
DetailsAngela Hardy
Routing - PLUMBING5/24/2019 5/28/2019 PASS
DetailsDaryl Spivey
Per plan and ISPC.
Intake Approval  5/22/2019 FAIL
DetailsJavier Guzman
Provide and upload the following:
• Per ePlan submittal standards reserve the bottom right corner for City approval stamps. Leave a blank 4” x 4” space located 3” off the right sheet edge to allow for the title block on plan sheet A1.0
Intake Approval  5/22/2019 PASS
Application received  5/17/2019 DONE
Application submitted via PDS Online on May 17 2019 4:45PM