Permit NumberBLD19-01949
StatusFinaled
Name KB SAFETY SERVICES LLC
Site Address 5277 W KOOTENAI ST
Project NameHeatherwood Senior Living
Customer NumberEARLY START BLD19-02200
ePlanReviewYes
Description
(HEATHERWOOD SENIOR LIVING) **PLAN MODIFICATION 12/17/19 To remove the fire rating from non-structural elements at exterior walls.** Permit is to remove and replace existing exterior siding, provide accent pop-out framing and new parapet wall over single story roof. This building is fully fire sprinklered. Any alterations or additions to the sprinkler system will require a separate permit and shall comply with NFPA 13 as regulated by the fire department. A letter of compliance is to be issued upon approval and completion of this project. An early start permit was issued for the exterior windows and exterior siding under BLD19-02200. No design review approval was required since parcel is not located in a design overlay zone. **JHB**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Third Notice 7/14/20208/11/2020 DONE
mailed 8-14-2020
Third Notice 5/12/20207/9/2020 DONE
mailed 7-9-2020
Second Notice 4/13/20205/7/2020 DONE
mailed 5-8-2020
First Notice3/4/20203/4/20204/3/2020 DONE
DetailsTell Riley
mailed 4-6-2020
BLD-Final3/4/20203/4/20203/4/2020PDONE
DetailsTell Riley
Doyle Phone #: ###-####//final complete per description/scope//landscaping will be completed to remove dirt/vegitation from near siding//
DOC - Permit Finaled3/4/20203/4/20203/4/2020PPASS
DetailsTell Riley
BLD-Final2/7/20202/7/20202/7/2020PNR
DetailsTell Riley
Doyle Phone #: ###-####//no roofing on door cover or any accents//
BLD-Final2/5/20202/6/20202/6/2020ACANC
DetailsTell Riley
Dole Phone #: ###-####//needs electrical final prior to building final//let contact know//
FIRE-Final Inspection2/5/20202/5/20202/5/2020PPASS
DetailsTroy Cobbley
Life safety passed.

Doyle Phone #: ###-####
FIRE-Conference1/16/20201/16/20201/16/2020PDONE
DetailsTroy Cobbley
The phone conferenced with the geal contractor about the possible need for a sprinkler contractor to to determine whether sprinkler coverage is needed in the new construction areas.
BLD-Framing/Rough-in1/15/20201/15/20201/15/2020PPASS
DetailsTell Riley
Doyle- call for access Phone #: ###-####//final framing for wall accents, installed ledgers with lags and a 35 clips per plans//sheathing was installed at time of inspeciton//
BLD-Framing/Rough-in12/23/201912/24/201912/24/2019APASS
DetailsTell Riley
Doyle Phone #: ###-####//south wall in courtyard accent framing//
BLD-Framing/Rough-in12/19/201912/19/201912/19/2019PPART
DetailsTell Riley
Call half hour before // Doyle Phone #: ###-####//gyp board on side entry per details//north wall in courtyard framing of accents ok//
CHANGE STATUS TO (ISS)  12/19/2019 DONE
BLD-Framing/Rough-in12/17/201912/18/201912/18/2019AFAIL
DetailsTell Riley
call ahead // Doyle Phone #: ###-####//side entry cover--need to add 1 hr over structural beams per plans//
Permit Ready to Issue  12/18/2019 DONE
PLAN MOD
Plan assigned to (Joe)12/5/201912/5/201912/17/2019 PASS
DetailsJoe Bruce
(plan mod) Heatherwood Senior Living
Routing - PLAN CHECK12/10/2019 12/17/2019 PASS
DetailsJoe Bruce
PLAN MOD - Removed fire rating from non-structural elements.
BLD-Framing/Rough-in12/4/201912/5/201912/5/2019APART
DetailsTell Riley
Call 30 minutes ahead // Doyle Phone #: ###-####//plan change on wall accents--advised Doyle to submit for plan mod to plan review//
Plan Modification Accepted  12/5/2019 DONE
removed the need to fire rate the soffits on the non structural over builds and surface applied eyebrow roofs. these are all non structural items and do not effect the existing fire rating of the walls
BLD-Framing/Rough-in12/2/201912/3/201912/3/2019APART
DetailsTell Riley
Call 30 mins ahead- Doyle Phone #: ###-####//parapet wall ok//wall accent framing ok--need to add 1 hr protection per plans and call for verifiction//side entry framing ok--add 1 hr rated assembly per plans and call for inspection//
BLD-Framing/Rough-in10/29/201910/29/201910/29/2019PNR
DetailsTell Riley
on parapet wall - Doyle Phone #: ###-####//discussed parapet wall framing//will call when framing is completed//
BLD-Framing/Rough-in10/8/201910/8/201910/8/2019PPASS
DetailsTell Riley
Call 30 minutes ahead // Doyle Phone #: ###-####//fire rated covers have been fixed//framing for cover ok//framing inspections for other areas will be required/
BLD-Framing/Rough-in10/7/201910/8/201910/8/2019APART
DetailsTell Riley
Doyle-please call when on way Phone #: ###-####//fire rated can light covers need to sit flat to ceilng--some have gaps under them//call in for re-inspection//ok to begin cover//
BLD-Framing/Rough-in10/1/201910/2/201910/2/2019AFAIL
DetailsTell Riley
call 30 mins before // dowel Phone #: ###-####//need electrical sign off//fire proofing at can lights not approved--use approved fire proofing//call for re-inspection//
BLD-Footing10/1/201910/2/201910/2/2019PPASS
DetailsTell Riley
Doyle-please call when on way Phone #: ###-####//ok to pour//special inspection was performed for dowels epoxied into footing//
BLD-Footing9/30/201910/1/201910/1/2019PPART
DetailsTell Riley
call when you are on your way- Dole Phone #: ###-####//footings for cover already poured//oversized from plans//verts will be drilled and epoxied--special inspection required//call for foundation inspection//
Plan Reviewer's activity  9/30/2019 DONE
Approved an alternate 1-hr roof/ceiling assembly for the porte cochere. CJW
BLD-Framing/Rough-in9/27/20199/27/20199/27/2019PFAIL
DetailsTell Riley
Call half hour before // Doyle Phone #: ###-####//1 hr ceiling does not meet details on plans//submit plan mod for changes in fire rated ceiling//verify penetrations for cans in rated ceiling//
BLD-Framing/Rough-in9/26/20199/27/20199/27/2019AFAIL
DetailsTell Riley
Doel Phone #: ###-####//no framers onsite//appears to be front entry cover--framing is not visible as framing has already been covered//call for re-inspection//
BLD-Framing/Rough-in9/23/20199/25/20199/24/2019ACANC
DetailsTell Riley
Doyle -per Doyle need to cancel inspection
BLD-Framing/Rough-in8/30/20199/3/20199/3/2019APART
DetailsTell Riley
Doyle Phone #: ###-####//north wing framing of exterior accents ok per plans//ad fire blocking as discussed//call for other wings framing inspections//
Issue PAID IN FULL permit  8/2/2019 DONE
Inspection Record Card- Bld  8/2/2019 DONE
Plan assigned to (JHB)6/13/20196/13/20197/30/2019 PASS
DetailsJoe Bruce
07/31 (3rd Rev) 06/25 (L2) Heatherwood Senior Living, ePlan (Struc)
Routing Off Site - STRUCTURAL7/24/2019 7/30/2019 PASS
DetailsJoe Bruce
AHJ
PLANS/APPL TAKEN TO FRONT DESK  7/30/2019 DONE
Permit Ready to Issue  7/30/2019 DONE
Need MET
Revised Cert of Value

(***DOC FINAL early start permit after issuance of this permit BLD19-02200)
Plan resubmittals received  7/24/2019 DONE
DetailsJoe Bruce
Routing Off Site - STRUCTURAL7/16/2019 7/22/2019 FAIL
DetailsJoe Bruce
AHJ - Not all comments were responded to please see the original comments as well as an added comment to one of the original comment. Please provide a written response to the structural comments.
Plan resubmittals requested  7/22/2019 DONE
DetailsJoe Bruce
Structural comments required for a resubmittal.
Plan resubmittals received  7/16/2019 DONE
DetailsJoe Bruce
Architect revised sheet A2.0 to have city stamping area clear.
Routing - PLAN CHECK7/16/2019 7/16/2019 PASS
DetailsJoe Bruce
Plan resubmittals received  7/15/2019 FAIL
DetailsJoe Bruce
Please provide the following so we can accept your resubmittal:
1) Plan sheet A2.0 does not have the required space reserved for City approval stamps as specified in the Electronic Plans Submittal Standards. The structural engineers stamp is obstructing the space designated for the city stamp. Revise sheets with a blank 4” x 2” space located 3” off the right sheet edge to allow for the title block.
Routing - FIRE6/13/20196/13/20196/25/2019 PASS
DetailsMark Scharfen
06.25.2019-Completed fire review. Made notation on plans. No report needed. Passed fire review.
Routing Off Site - STRUCTURAL6/13/2019 6/25/2019 FAIL
DetailsJoe Bruce
AHJ
1st review completed  6/25/2019 FAIL
DetailsJoe Bruce
Plan resubmittals requested  6/25/2019 DONE
DetailsJoe Bruce
Emailed Architect Plan Review Report.
Routing - PLAN CHECK6/13/2019 6/24/2019 FAIL
DetailsJoe Bruce
See plan review report for corrections required.
Intake Approval  6/13/2019 PASS
DetailsMichael Hanson
Prescreen approved my M_H. Early start issued under BLD19-02200 for window and siding portion of project.
Routing - Design Review6/13/2019 6/13/2019 PASS
DetailsJosh Wilson
No DR required- not in Design Review overlay
Intake Approval  6/3/2019 FAIL
DetailsMichael Hanson
Please provide planning and zoning approval letter. The DRH19-00227 listed in the application is a voided permit.
Application received  5/30/2019 DONE
Application submitted via PDS Online on May 30 2019 12:00AM
Third Notice 8/16/2020