Permit Information
Permit NumberBLD19-02090
StatusIssued
Name ZACHARY SHIPSEY
Site Address 10152 W STATE ST
Project NameBig Automotive
Customer NumberDEMO BLD19-02493
ePlanReviewYes
Description
(BIG AUTOMOTIVE) (Demo Permit: BLD19-02493) (CUP19-00019) **PLAN MODIFICATION 12-27-2019 to remove the firewall that separated the office and shop since an alternate was approved by the fire department to omit the fire suppression system that was originally approved by the fire marshal. **This building is NOT fire sprinklered and shall have fire suppression canisters installed per plan and letter signed by the assistant fire marshal.** Permit is to convert an existing 3,358 sq. ft. residence into an automotive office with parts storage, break room, conference room, administrative offices, (2) two accessible restrooms, and an automotive detailing area in the former 2-car garage. A new covered drive aisle is being added to the existing front covered porch area and is intended for automobiles to drive and/or park underneath. A 55’ x 55’ pre-engineered metal building that totals 2,915 sq. ft. will be added onto the rear (north) of the site and will be divided by a 3-hour fire wall. The PEMB will have 7 overhead doors for automotive use and includes a utility connection for a future breakroom and restroom for the occupants of the building. Separate permits will be required for these plumbing fixtures. **SPECIAL INSPECTIONS** are required per attached Form 310 for concrete placement, anchor bolts, welding, footing excavation/compaction and high-strength bolts. Approval is contingent upon adhering to the approved plans on file and attached engineering. The Fire Sprinkler Suppression System and/or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed as regulated by the Boise Fire Department. Racking that exceeds 8 ft. in height requires a separate Building Permit be submitted and approved before installation. **JHB**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Aging Inspection7/30/20207/30/20207/31/2020 PASS
DetailsTony Young
BLD-Conference7/30/20207/30/20207/30/2020PDONE
DetailsTony Young
Zach *screened* Phone #: ###-####// walk through
BLD-Aging Inspection7/29/20207/29/20207/30/2020 PASS
DetailsTony Young
BLD-Framing/Rough-in3/16/20203/17/20203/17/2020APASS
DetailsDave Hannah
Zach Phone #: ###-#### front drive canopy ok
BLD-Wall cover2/21/20202/24/20202/24/2020APASS
DetailsJim Storey
Zach Phone #: ###-####
BLD-Foundation2/13/20202/14/20202/14/2020PPASS
DetailsBrandon Shaw
Work in progress...
Frost protection is required...
BLD-Framing/Rough-in2/5/20202/6/20202/7/2020PPASS
DetailsTony Young
Zach Phone #: ###-####,, ok to cover
BLD-Framing/Rough-in2/5/20202/6/20202/6/2020APEND
DetailsTony Young
Zach Phone #: ###-####
BLD-Conference2/4/20202/5/20202/5/2020APART
DetailsTony Young
Zach Phone #: ###-####,, ok to cover interior walls without mechanical
OVERRIDE  2/4/2020  
CHANGE STATUS TO (ISS)  2/4/2020 DONE
plan mod
Permit Ready to Issue  2/4/2020 DONE
DO NOT ISSUE- plan mod approved
Plan assigned to (Joe)12/10/201912/10/20192/3/2020 PASS
DetailsJoe Bruce
(plan mod) Big Automotive
Routing - PLAN CHECK2/3/2020 2/3/2020 PASS
DetailsJoe Bruce
plan mod passed.
BLD-Footing1/27/20201/28/20201/28/2020PPASS
DetailsDave Hannah
Zack Phone #: ###-####
Intake Approval  1/27/2020 FAIL
DetailsJoe Bruce
The PEMB drawings are missing an engineers stamp. Sent drawings back for upload.
BLD-Framing/Rough-in1/16/20201/16/20201/17/2020PNR
DetailsTony Young
Donavin Phone #: ###-####// frame walk through only,, needs trades, seal pack etc.
Plan resubmittals received  1/7/2020 FAIL
DetailsJoe Bruce
The pre-engineered metal building drawings still have references to the firewall.
Plan resubmittals received  1/2/2020 FAIL
DetailsJoe Bruce
There are still multiple locations I am seeing references to the fire wall on this set of plans. Sheet A-0.0 - Project Narrative still references the shop and office to be separated by a firewall, Sheet A2.4 - Wall type 2A still references the UL fire wall assembly. The PEMB drawings have a firewall listed on most of the drawings. - There might be other references to this firewall on the plans that I have not found. Please have all these references to the firewall removed. I am mostly concerned with these drawings being referenced in the future and seeing the firewall reference on the plans will confuse the plans examiner and require the firewall rating to be maintained.
Routing - FIRE12/18/201912/18/201912/27/2019 PASS
DetailsJoe Bruce
See email for alternate agreement to providing a fire alarm system throughout building in lieu of fire canisters. Applicant is removing fire wall since fire alarm system is being provided throughout. **JHB**
Plan resubmittals requested  12/27/2019 DONE
DetailsJoe Bruce
Routing - PLAN CHECK12/18/2019 12/27/2019 FAIL
DetailsJoe Bruce
Plan Mod failed since all plans sheets have not been updated to remove the fire wall.
Intake Approval  12/16/2019 FAIL
DetailsJoe Bruce
Please provide the following to complete your prescreen:
1) Sheets A3.2 and A3.3 are missing a stamp by the registered design professional. Provide the architects stamp on these sheets.
Plan Modification Accepted  12/10/2019 DONE
plan mod -removing the fire wall between the residence/office and shop
Issue PAID IN FULL permit  11/20/2019 DONE
Print Occupancy Form  11/20/2019 DONE
(F) Reprint permit  11/20/2019 DONE
Print Occupancy Form  11/20/2019 DONE
OVERRIDE  11/19/2019  
Plan assigned to (JHB)6/19/20196/21/201911/19/2019 PASS
DetailsJoe Bruce
(4th Rev Comp) 07/30 - 502 Big Automotive Addition and Remodel
PLANS/APPL TAKEN TO FRONT DESK  11/19/2019 DONE
DetailsJoe Bruce
Addtional plan review fees for 5th plan review from structural engineer.
Permit Ready to Issue  11/19/2019  
ALL MET NEED
RP

MET-
GC
Revised Certificate of Value
Routing Off Site - STRUCTURAL11/12/2019 11/18/2019 PASS
DetailsJoe Bruce
Plan resubmittals received  11/12/2019 DONE
DetailsJoe Bruce
Plan resubmittals requested  10/21/2019 DONE
DetailsJoe Bruce
ePlan task sent back to Architect.
Routing Off Site - STRUCTURAL10/15/2019 10/21/2019 FAIL
DetailsJoe Bruce
AHJ - Chris Holladay
Routing PW Drainage10/15/2019 10/17/2019 PASS
DetailsBrian Murphy
Plan resubmittals received  10/15/2019 DONE
DetailsJoe Bruce
Plan resubmittals requested  9/12/2019 DONE
DetailsJoe Bruce
ePlan task sent back to architect.
Routing PW Drainage9/5/2019 9/12/2019 FAIL
DetailsJason C. Taylor
see changemarks in ePlan. JCT
Routing Off Site - STRUCTURAL9/5/2019 9/9/2019 FAIL
DetailsJoe Bruce
AHJ - Corrections Required.
Routing - PLAN CHECK9/5/2019 9/9/2019 PASS
DetailsJoe Bruce
Plan resubmittals received  9/5/2019 DONE
DetailsJoe Bruce
Routing - PLAN CHECK8/12/2019 8/20/2019 FAIL
DetailsJoe Bruce
See 2nd Plan Review report for additional items required for a resubmittal.
Plan resubmittals requested  8/20/2019 DONE
DetailsJoe Bruce
Spoke with Glenn on the phone about resubmittal items. JHB
Routing - FIRE8/12/20198/12/20198/19/2019 PASS
DetailsMark Scharfen
08/23-Big Automotive resubmittal MS review complete. UPloaded and emailed rev_fire 08.19.2019.pdf to architect. Architect provided information. Resolved.
Routing Off Site - STRUCTURAL8/12/2019 8/14/2019 FAIL
DetailsJoe Bruce
Routing PW Drainage8/12/2019 8/14/2019 FAIL
NEED VARIANCE OK
Routing - MECHANICAL8/12/2019 8/13/2019 PASS
DetailsTroy James
Routing - PLUMBING8/12/2019 8/13/2019 PASS
DetailsDaryl Spivey
Per plan and ISPC
Routing - PUBLIC WORKS8/12/2019 8/13/2019 PASS
DetailsMorgan Webb
Routing PW Street Lights8/12/2019 8/12/2019 PASS
DetailsTom Marshall
Routing PW Sewer Design8/12/2019 8/12/2019 PASS
DetailsDeAnn Brown
Additional plumbing fixtures will connect to existing on-site sewer service outside the building.
Plan resubmittals received  8/12/2019 DONE
DetailsJoe Bruce
Route to Impact Fee Review7/29/20198/1/20198/9/2019 PASS
DetailsEric Bilimoria
Review requested for Commercial Permit
Routing - FIRE6/19/20196/21/20197/29/2019 FAIL
DetailsMark Scharfen
07.29.2019-Completed fire review. Uploaded and emailed to architect and applicant rev_fire 07.29.2019.pdf
1st review completed  7/29/2019 FAIL
DetailsJoe Bruce
Plan resubmittals requested  7/29/2019 DONE
DetailsJoe Bruce
Routing - PLAN CHECK6/19/2019 7/26/2019 FAIL
DetailsJoe Bruce
Added plan review report with corrections required in the agency comments folder in ePlan.
Routing Off Site - STRUCTURAL6/19/2019 7/17/2019 FAIL
DetailsJoe Bruce
AHJ - Chris Holladay
Routing PW Environmental6/21/2019 7/16/2019 PASS
DetailsRick Christenson
Approved for office/storage
Meeting  7/16/2019 DONE
Submitted a Revised Certificate of Value without interior Demo
Routing - MECHANICAL7/8/2019 7/8/2019 PASS
DetailsTroy James
Routing PW Drainage6/21/2019 7/5/2019 FAIL
geotech sidewall infiltration, less tan3 ft to gwand apendex j
Routing PW Solid Waste6/21/2019 7/2/2019 PASS
DetailsPeter J. McCullough
Approved for Commercial carts only.
Routing - MECHANICAL6/19/2019 6/27/2019 FAIL
DetailsTroy James
Emailed the applicant
Routing - Erosion and Sediment6/19/2019 6/25/2019 PASS
DetailsMichael Zawacki
RP needs valid con #
Routing - PLUMBING6/19/2019 6/24/2019 FAIL
DetailsDan Ediger
1. Requires a 4" building drain.
2. Install a backflow assembly.
Routing - PLANNING6/19/2019 6/21/2019 PASS
DetailsBrent Moore
Routing - Addressing  6/21/2019 PASS
Routing - PUBLIC WORKS6/19/2019 6/21/2019 FAIL
DetailsMorgan Webb
NEED DETAILED PLUMBING PLANS FOR ENTIRE PROJECT.
Routing PW Street Lights6/21/2019 6/21/2019 FAIL
DetailsTom Marshall
Routing PW Sewer Design6/21/2019 6/21/2019 FAIL
DetailsDeAnn Brown
Show how new waste piping for bathroom in shop addition will connect to existing sewer service or the sewer main in State Street.
Intake Approval  6/19/2019 PASS
DetailsBrian McGowan
Intake Approval  6/12/2019 FAIL
DetailsBrian McGowan
The drawings for the steel building must be a minimum 18"x24".
The City of Boise Approval Stamp must be legible when applied as well.
I think the stamp should work when the sheets are 18"x24" or 24"x36" like the other drawing sheets. Please verify prior to resubmitting.
Intake Approval  6/10/2019 FAIL
DetailsBrian McGowan
Please provide the following documents or information for your Prescreen to be approved;
1. Provide all sheets for Form #310.
2. Provide a Landscape Plan and Plant schedule.
3. Provide an ESC Plan
4. Sheet A-10.0 was not provided as specified in the Checklist.
5. No Plumbing Fixture Schedule on Sheet P-1
6. Please provide the drawings, energy compliance and details for the proposed shop.
Application received  6/6/2019 DONE
Application submitted via PDS Online on Jun 6 2019 1:45PM