Information based on query as of Wednesday, July 24, 2024.
Permit Information
Permit NumberBLD19-02129
StatusFinaled
Name SIMPLICTY HOMES LLC
Site Address 11467 W ALDERSHOT DR
Project Name 
Customer Number 
ePlanReviewNo
Description
**PASSES USING UA TRADE OFF** Permit for the construction of a new 1623 sq. ft., one story single family dwelling with 4 bedrooms, 2 bathrooms, approximately 58 sq. ft. of covered patio/porch and a 402 sq. ft. attached garage per the approved plans and any notations. R-1C zoning and setbacks per planning. JJN
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final1/8/20201/8/20201/8/2020PPASS
DetailsMike Jordan
Sam Phone #: ###-####
DOC - Permit Finaled1/8/20201/8/20201/8/2020PPASS
DetailsMike Jordan
BLD-Blower Door Test Results1/8/20201/8/20201/8/2020PDONE
DetailsMike Jordan
4.9
BLD-Energy code compliance10/24/201910/25/201910/25/2019APASS
DetailsMike Jordan
Sam Phone #: ###-####
BLD-Framing/Rough-in10/25/201910/25/201910/25/2019APASS
DetailsMike Jordan
Sam Phone #: ###-####
BLD-Framing/Rough-in10/21/201910/22/201910/22/2019AFAIL
DetailsMike Jordan
SAM Phone #: ###-####. Complete lateral bacing on A02,A04, A05 and A07 trusses. Nail off B3 2ply truss per the engineering Provide header over masgterbedroom door to support the continous bearing of the A2 truss above. Correction notice posted. Ok to insulate.
BLD-Framing/Rough-in10/18/201910/18/201910/18/2019PFAIL
DetailsMike Jordan
sam Phone #: ###-####. Provided truss engineering does not match instaleed trusses. DO NOT INSULATE. Needs to provide the correct truss engineering.
Routing - MECHANICAL9/13/2019 9/13/2019 PASS
DetailsChad Schwendiman
Revised acca report
BLD-Wall Bracing9/10/20199/10/20199/10/2019PPASS
DetailsMike Jordan
sam Phone #: ###-####
BLD-Footing8/1/20198/2/20198/2/2019APASS
DetailsMike Jordan
Erme Phone #: ###-####
Issue PAID IN FULL permit  7/15/2019 DONE
OVERRIDE  7/12/2019  
Plan assigned to (J_N)6/11/20196/11/20197/12/2019 DONE
DetailsJenny Nelson
06/24 sfd L1 Paper. 1st complete 6/21, need site plan
Routing - PLAN CHECK7/12/2019 7/12/2019 PASS
DetailsJenny Nelson
Case Summary (BLD)  7/12/2019 DONE
DetailsJenny Nelson
PLANS/APPL TAKEN TO FRONT DESK  7/12/2019 DONE
DetailsJenny Nelson
Permit Ready to Issue  7/12/2019 DONE
Inspection Record Card- Bld  7/12/2019 DONE
Telephone call  7/12/2019 DONE
Left a message to Sawyer at ###-####, and emailed Tom Bosier at tbosier@simplicity-homes.com letting them know the permit is ready and fees due.
Routing - PLANNING7/10/2019 7/10/2019 PASS
DetailsSue Cummings
received site plan 7/10/19
Plan resubmittals received  7/8/2019 DONE
two copies of sheet CS taken to Jenny
1st review completed  6/21/2019 DONE
DetailsJenny Nelson
Routing - PLAN CHECK6/13/2019 6/21/2019 FAIL
DetailsJenny Nelson
Need site plan
Routing - MECHANICAL6/13/2019 6/13/2019 PASS
DetailsTroy James
Routing - PLANNING6/11/2019 6/13/2019 FAIL
DetailsSue Cummings
No site plan
Routing - PUBLIC WORKS6/11/2019 6/13/2019 PASS
DetailsMorgan Webb
Route to Impact Fee Review6/11/20196/14/20196/12/2019 PASS
DetailsShannon Cade
Initial residential review of new SFD permits requested for now.
Routing - Addressing6/11/2019 6/12/2019 PASS
DetailsDoug Chausow
Plans ACCEPTED BY PLAN TECH  6/11/2019 DONE
Intake Approval  6/11/2019 PASS
Recd Pcfee & Taken To Pln CK  6/11/2019 DONE
Intake Approval  6/7/2019 FAIL
Need Checklist filled out, 2 copies of each 8x11 site plan and large site plan with plans.
Application received 6/7/2019