Permit Information
Permit NumberBLD19-02456
StatusIssued
Name SLETTEN CONSTRUCTION
Site Address 816 W BANNOCK ST Unit: 100
Project NameGarro: Suite 100 Shell
Customer Number 
ePlanReviewYes
Description
(GARRO BUILDING - VANILLA - SUITE 100) SPECIAL INSPECTIONS REQUIRED- USING INTUMESCENT COATING TO ACHIEVE (1) HOUR CEILING ASSEMBLY. **Permit is for the 1st floor of the existing historic building. Work to include: removal of non-structural, non-functioning, elements from previous tenants; installation of a 1-hr rated floor/ceiling assembly; installation of 1-hr rated column wraps, new interior lighting, and replacement of mechanical. This building is sprinklered to allow the 5th floor. The sprinkler and fire alarm system must be maintained and functional at all times. This building is fully fire sprinklered any alterations or modifications to the sprinkler system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA #13 as regulated by the fire department. No occupancy permit will be issued and any relocated or future tenants must apply for building permit and receive a certificate of occupancy prior to occupying. This building is sprinklered to allow 5th floor. ***BJM***
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Other10/28/201910/29/201910/29/2019APASS
DetailsDave Hannah
Requesting inspection of 1st layer of ceiling drywall before the intumescent paint is applied. Three holes left open will receive fire rated access panels after the intumescent is applied. Phone #: ###-#### Inspection requested via web by Dustin Keyes
Place hold on job10/3/2019 10/28/2019 DONE
DetailsTiffany Carson-Herker
waiting for signed permit
Issue PAID IN FULL permit  10/3/2019 DONE
Inspection Record Card- Bld  10/3/2019 DONE
Plan assigned to (BJM)7/12/20197/12/20199/27/2019 DONE
DetailsBrian McGowan
09/16- 1st Review Complete- L-2, Garro Building Vanilla, ePlan
Routing - PLAN CHECK9/27/2019 9/27/2019 PASS
DetailsBrian McGowan
PLANS/APPL TAKEN TO FRONT DESK  9/27/2019 DONE
DetailsBrian McGowan
Permit Ready to Issue  9/27/2019 DONE
MET DKEYES@SLETTENINC.COM
Need GC
Need Rev Val
Route to Impact Fee Review8/5/20198/8/20198/6/2019 PASS
DetailsEric Bilimoria
Review requested for Commercial Permit
1st review completed  8/5/2019 DONE
DetailsBrian McGowan
Routing - PLAN CHECK7/9/2019 8/5/2019 FAIL
DetailsBrian McGowan
More information required on the intumescent paint proposed to be used. Specific brand, installation specifications, special inspections form and assembly details showing compliance with being used in the method proposed.
Routing PW Flood Plain7/10/2019 7/11/2019 CANC
DetailsJason C. Taylor
Project is outside Special Flood Hazard Area, no floodplain review required. If you have any questions, please call Jason Taylor at ###-####.
Routing - Addressing7/9/2019 7/10/2019 PASS
DetailsDoug Chausow
Suite 100
Routing - PUBLIC WORKS7/9/2019 7/10/2019 PASS
DetailsAngela Hardy
Plan assigned to (CJW)7/9/20197/9/20197/9/2019 DEFR
DetailsCarl Westfall
L-2, Garro Building Vanilla, ePlan
Intake Approval  7/9/2019 PASS
DetailsBrian McGowan
Prescreen approved my BJM
Intake Approval  7/3/2019  
DetailsBrian McGowan
Please provide the following for your Prescreen to be approved;

1. There is a note on each Plan Sheet specifying they are 100% BID DOCUMENTS. Please remove this note.
Application received  7/1/2019 DONE
Application submitted via PDS Online on Jul 1 2019 2:53PM