First Notice | 12/24/2019 | 12/24/2019 | 12/30/2019 | | DONE |
Tony Young
|
|
|
mailed 1-1-20
|
BLD-Final | 12/19/2019 | 12/24/2019 | 12/24/2019 | P | PASS |
Tony Young
|
|
|
Final inspection request for new precast stairs installed on exiting columns. Phone #: ###-#### Inspection requested via web by Brian Hetmer// received special inspection report via e-mail
|
DOC - Permit Finaled | 12/24/2019 | 12/24/2019 | 12/24/2019 | P | PASS |
Tony Young
|
|
|
|
BLD-Final | 12/18/2019 | 12/19/2019 | 12/19/2019 | A | PEND |
Tony Young
|
|
|
Final inspection request for new precast stairs installed on exiting columns. Phone #: ###-#### Inspection requested via web by Brian Hetmer
|
BLD-Final | 12/17/2019 | 12/18/2019 | 12/18/2019 | P | PEND |
Tony Young
|
|
|
Final inspection request for new precast stairs installed on exiting columns. Phone #: ###-#### Inspection requested via web by Brian Hetmer// pending letter
|
BLD-Final | 12/16/2019 | 12/17/2019 | 12/17/2019 | P | PEND |
Tony Young
|
|
|
Final inspection request for new precast stairs installed on exiting columns. Phone #: ###-#### Inspection requested via web by Brian Hetmer// all ok,, just pending the letter from the special inspections
|
FIRE-Final Inspection | 12/16/2019 | 12/17/2019 | 12/17/2019 | A | PASS |
Jim Page
|
|
|
Final life fire safety inspection for scope of work is complete.
Final inspection request for new precast stairs installed on exiting columns. Phone #: ###-#### Inspection requested via web by Brian Hetmer
|
BLD-Final | 12/13/2019 | 12/16/2019 | 12/16/2019 | P | PART |
Tony Young
|
|
|
Final inspection request for new precast stairs installed on exiting columns. Phone #: ###-#### Inspection requested via web by Brian Hetmer// ok pending f/l/s and final letter from the engineer
|
Issue PAID IN FULL permit | | | 12/11/2019 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 12/11/2019 | | DONE |
|
|
|
|
Expiration Notice | 12/6/2019 | 12/30/2019 | 12/6/2019 | | DONE |
Brittany Hill
|
|
|
|
OVERRIDE | | | 9/10/2019 | | |
|
|
|
|
Routing - FIRE | 7/31/2019 | 8/2/2019 | 9/10/2019 | | PASS |
Mark Scharfen
|
|
|
09/10 - 502 Healthwise Stair Replacement. Exterior pre-cast stair. No report needed. Approved.
|
1st review completed | | | 9/10/2019 | | DONE |
Michael Hanson
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/10/2019 | | DONE |
Michael Hanson
|
|
|
|
Permit Ready to Issue | | | 9/10/2019 | | DONE |
|
|
|
ALL MET Need GC
Need rev cert of val
Need RP-met
|
Plan assigned to (M_H) | 7/31/2019 | | 9/10/2019 | | DONE |
Michael Hanson
|
|
|
09/10 #502 L3 ePlan - Healthwise Stair Replacement - Pending fire review
|
Routing - PLAN CHECK | 7/31/2019 | | 9/6/2019 | | PASS |
Michael Hanson
|
|
|
|
Routing PW Grading-Hillside | 8/2/2019 | | 8/19/2019 | | PASS |
Melissa Jannusch
|
|
|
A letter from the applicant’s geotechnical engineer indicating that the footing/column subgrade is acceptable must be approved by Public Works prior to scheduling a footing inspection. Please allow 24 hours for subgrade approval processing. Call Melissa Jannusch at ###-####
|
Routing Off Site - STRUCTURAL | 8/2/2019 | | 8/16/2019 | | PASS |
Michael Hanson
|
|
|
Passed in ePlan per Dave Haugland @ AHJ engineering.
|
Routing - Design Review | 8/2/2019 | | 8/6/2019 | | PASS |
Josh Wilson
|
|
|
No DR req'd.
|
Routing - Erosion and Sediment | 8/2/2019 | | 8/6/2019 | | PASS |
Michael Zawacki
|
|
|
Waiver approved.
|
Routing - PLANNING | 8/2/2019 | | 8/5/2019 | | PASS |
Brent Moore
|
|
|
|
Routing - Addressing | 8/2/2019 | | 8/5/2019 | | PASS |
Doug Chausow
|
|
|
|
Routing - PUBLIC WORKS | 8/2/2019 | | 8/2/2019 | | PASS |
Angela Hardy
|
|
|
|
Intake Approval | | | 7/31/2019 | | |
Brian McGowan
|
|
|
|
Intake Approval | | | 7/24/2019 | | FAIL |
Brian McGowan
|
|
|
Please provide the following for your Prescreen to be approved:
1. A completed Form #310.
2. Complete the Responsible Person Information on Form #701.
3. Engineering calculations need to be provided.
4. Provide Soils and Geotech Report if calculations are not set at default.
5. Provide Planning and Zoning Approval letter.
6. Please provide the Code Analysis for Boise City and the Building Data for the building you are attaching the stairs to.
|
Application received | | | 7/12/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Jul 12 2019 11:03AM
|