Second Notice | | 7/19/2020 | 8/11/2020 | | DONE |
|
|
|
mailed 8-14-2020
|
First Notice | | 6/28/2020 | 7/9/2020 | | DONE |
|
|
|
mailed 7-9-2020
|
Permanent Occupancy | | | 6/18/2020 | | DONE |
|
|
|
|
BLD-Final | 6/16/2020 | 6/17/2020 | 6/17/2020 | A | PASS |
Mike Jordan
|
|
|
Screened- Tom Phone #: ###-####. Ok for temp occ. Will be ok for perm occ. once electrical and plumbing sign perm.
|
FIRE-Final Inspection | 6/8/2020 | 6/9/2020 | 6/9/2020 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed. Hardware on Mech Room door to be single action, to be verified by the building inspector.
screeend // Tom Phone #: ###-####
|
Zoning Approval | 6/9/2020 | 6/9/2020 | 6/9/2020 | | PASS |
Katelyn Menuge
|
|
|
|
FIRE-Final Inspection | 6/4/2020 | 6/4/2020 | 6/4/2020 | P | FAIL |
Troy Cobbley
|
|
|
Provide final for fire alarm and fire sprinkler permits, provide ADA compliant hardware for Riser Room door, repair exit sign and get approval for the missing fire hydrant at the corner of Fairview and Cole (plans show existing on corner)
screened // Tom Phone #: ###-####
|
BLD-Ceiling Grid Inspection | 3/31/2020 | 3/31/2020 | 3/31/2020 | P | PASS |
Mike Jordan
|
|
|
Tom Phone #: ###-####
|
Print Occupancy Form | | | 3/10/2020 | | DONE |
|
|
|
|
CHANGE STATUS TO (ISS) | | | 3/10/2020 | | DONE |
|
|
|
|
OVERRIDE | | | 3/6/2020 | | |
|
|
|
|
Plan assigned to (JAR) | 2/20/2020 | 2/20/2020 | 3/6/2020 | | DONE |
Julie Romig
|
|
|
03/06 (5 days) - Plan Mod Primary Health Fairview - Plan mod #1- A lot line adjustment at the west side of the parcel has been included, with the addition of 4 parking stalls, modified landscape and civil. This change has been reviewed and approved under DRH20-00042
|
Routing - PLAN CHECK | 2/21/2020 | | 3/6/2020 | | PASS |
Julie Romig
|
|
|
Per Julie's email on 3/6/2020
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/6/2020 | | DONE |
Julie Romig
|
|
|
|
Permit Ready to Issue | | | 3/6/2020 | | DONE |
|
|
|
DO NOT ISSUE- plan mod
|
Routing PW Environmental | 2/21/2020 | | 3/4/2020 | | PASS |
Zach Conde
|
|
|
PLAN MOD
|
Routing - PLANNING | 2/21/2020 | | 2/26/2020 | | PASS |
David Moser
|
|
|
See DRH20-00042
|
Routing - Design Review | 2/21/2020 | | 2/25/2020 | | PASS |
Katelyn Menuge
|
|
|
DRH20-00042 Plan Mod Pass
|
Routing PW Solid Waste | 2/21/2020 | | 2/24/2020 | | PASS |
Evan Carpenter
|
|
|
PLAN MOD
|
Routing PW Drainage | 2/21/2020 | | 2/24/2020 | | PASS |
Brian Murphy
|
|
|
PLAN MOD
|
Routing - PUBLIC WORKS | 2/21/2020 | | 2/21/2020 | | PASS |
Candy A. Nichols
|
|
|
PLAN MOD-NO NEW PLUMBING
|
Plan Modification Accepted | | | 2/20/2020 | | DONE |
|
|
|
Plan mod #1
|
BLD-Framing/Rough-in | 1/27/2020 | 1/28/2020 | 1/28/2020 | A | PASS |
Mike Jordan
|
|
|
scott Phone #: ###-####. Interior steel stud framed walls ok.
|
BLD-Energy code compliance | 1/17/2020 | 1/17/2020 | 1/17/2020 | P | PASS |
Mike Jordan
|
|
|
Scott Phone #: ###-####
|
BLD-Energy code compliance | 1/13/2020 | 1/13/2020 | 1/13/2020 | P | CANC |
Mike Jordan
|
|
|
Scott Phone #: ###-####
|
BLD-Framing/Rough-in | 1/13/2020 | 1/13/2020 | 1/13/2020 | P | PASS |
Mike Jordan
|
|
|
Scott Phone #: ###-####. exterior wood framed walls only ok to insulate.
|
BLD-Other | 12/16/2019 | 12/16/2019 | 12/16/2019 | P | PASS |
Mike Jordan
|
|
|
roof nailing - Scott Phone #: ###-####
|
BLD-Wall Bracing | 12/11/2019 | 12/11/2019 | 12/11/2019 | P | PASS |
Dave Hannah
|
|
|
|
BLD-Wall Bracing | 12/10/2019 | 12/11/2019 | 12/11/2019 | A | NR |
Mike Jordan
|
|
|
Scott Phone #: ###-####. Moved to pm. inspection.
|
BLD-Other | 12/2/2019 | 12/3/2019 | 12/3/2019 | P | DONE |
Mike Jordan
|
|
|
slab on grade // Scott Phone #: ###-####
|
BLD-Foundation | 11/5/2019 | 11/5/2019 | 11/5/2019 | P | PASS |
Mike Jordan
|
|
|
Scott Phone #: ###-####
|
BLD-Foundation | 10/29/2019 | 10/30/2019 | 10/30/2019 | P | CANC |
Mike Jordan
|
|
|
rebar// scott Phone #: ###-####
|
BLD-Footing | 10/25/2019 | 10/28/2019 | 10/28/2019 | A | PART |
Mike Jordan
|
|
|
rebar // Scott Phone #: ###-####. Permiter footing. Work in progress. Will have special inspection. will need concrete blankets due to cold temps. Ok to place concrete pending special inspection.
|
Telephone call | | | 10/11/2019 | | DONE |
|
|
|
Emailed Erin to let her know that we cannot issue the permit until we have been notified of approved ACHD plans
|
Issue PAID IN FULL permit | | | 10/11/2019 | | DONE |
|
|
|
|
Print Occupancy Form | | | 10/11/2019 | | DONE |
|
|
|
|
OVERRIDE | | | 10/4/2019 | | |
|
|
|
|
Permit Ready to Issue | | | 10/4/2019 | | DONE |
|
|
|
met: erinh@cmcompany.com
Need: ACHD receipt AND approval to issue permit (see attached email from ACHD 10/11/19 LEG)
ALL MET
Need
RP
GC
Revised Value
|
Plan assigned to (JAR) | 8/12/2019 | 8/16/2019 | 10/2/2019 | | DONE |
Julie Romig
|
|
|
1st Rev Comp - 2nd Comp - 502 Primary Health
|
Routing - PLAN CHECK | 10/2/2019 | | 10/2/2019 | | PASS |
Julie Romig
|
|
|
See Redlines
|
Routing - Design Review | 10/2/2019 | | 10/2/2019 | | PASS |
Katelyn Menuge
|
|
|
Cross-Access Easement needs to be updated and NMID compliance letter submitted prior to building occupancy.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/2/2019 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 9/24/2019 | | 10/1/2019 | | FAIL |
Julie Romig
|
|
|
|
Routing PW Drainage | 9/24/2019 | | 9/25/2019 | | PASS |
Brian Murphy
|
|
|
|
Routing Off Site - STRUCTURAL | 9/24/2019 | | 9/25/2019 | | PASS |
Julie Romig
|
|
|
|
Routing - Design Review | 9/24/2019 | | 9/24/2019 | | FAIL |
Katelyn Menuge
|
|
|
Update street tree species to full-spread, Class II varieties, need updated cross-access easement that aligns with service drive.
|
Routing - PLANNING | 9/24/2019 | | 9/24/2019 | | PASS |
David Moser
|
|
|
|
Route to Impact Fee Review | 9/20/2019 | 9/23/2019 | 9/20/2019 | | PASS |
Eric Bilimoria
|
|
|
Review requested for Commercial Permit
|
1st review completed | | | 9/20/2019 | | FAIL |
Julie Romig
|
|
|
|
Routing - PLAN CHECK | 8/16/2019 | | 9/20/2019 | | FAIL |
Julie Romig
|
|
|
|
Routing - FIRE | 8/12/2019 | 8/16/2019 | 9/19/2019 | | PASS |
Erika Akin
|
|
|
Attached comments to case
|
Routing PW Drainage | 8/19/2019 | | 9/4/2019 | | FAIL |
Brian Murphy
|
|
|
NEED SWALE DETAIL APENDX J
|
Routing - Erosion and Sediment | 8/16/2019 | | 8/22/2019 | | PASS |
Michael Zawacki
|
|
|
Site prep inspection required.
RP needed.
|
Routing - MECHANICAL | 8/16/2019 | | 8/22/2019 | | PASS |
Troy James
|
|
|
|
Routing - PLANNING | 8/16/2019 | | 8/20/2019 | | FAIL |
David Moser
|
|
|
service drive and trash enclosure in rear parking setback
|
Routing - Addressing | 8/16/2019 | | 8/20/2019 | | PASS |
Laura Hunter
|
|
|
|
Routing PW Street Lights | 8/19/2019 | | 8/20/2019 | | PASS |
Tom Marshall
|
|
|
|
Routing PW Solid Waste | 8/19/2019 | | 8/20/2019 | | PASS |
Evan Carpenter
|
|
|
|
Routing Off Site - STRUCTURAL | 8/16/2019 | | 8/20/2019 | | FAIL |
Julie Romig
|
|
|
Stapley
|
Routing - PUBLIC WORKS | 8/16/2019 | | 8/19/2019 | | PASS |
Morgan Webb
|
|
|
|
Routing - PLUMBING | 8/16/2019 | | 8/19/2019 | | PASS |
Daryl Spivey
|
|
|
Per plan and ISPC.
|
Routing - Design Review | 8/16/2019 | | 8/19/2019 | | FAIL |
Katelyn Menuge
|
|
|
See Changemarks
|
Intake Approval | | | 8/12/2019 | | PASS |
Michael Hanson
|
|
|
|
Application received | | | 8/1/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Aug 1 2019 1:21PM
|
Third Notice | | 8/16/2020 | | | |
|
|
|
|