BLD-Foundation | 8/12/2020 | 8/12/2020 | 8/12/2020 | P | PART |
Brandon Shaw
|
|
|
Pending special inspection...
|
BLD-Footing | 8/5/2020 | 8/6/2020 | 8/6/2020 | A | PART |
Brandon Shaw
|
|
|
Pending special inspections...
|
CHANGE STATUS TO (ISS) | | | 7/2/2020 | | DONE |
|
|
|
|
OVERRIDE | | | 6/30/2020 | | |
|
|
|
|
Routing - FIRE | 6/18/2020 | 6/18/2020 | 6/30/2020 | | PASS |
Mark Stumbaugh
|
|
|
06/26 Plan Mod Pivot KA ePan MAS
|
Plan assigned to (JG) | 6/12/2020 | 6/12/2020 | 6/30/2020 | | PASS |
Javier Guzman
|
|
|
06/26 Plan Mod Pivot KA ePan, fire
|
Permit Ready to Issue | | | 6/30/2020 | | DONE |
|
|
|
plan mod approved
DO NOT RE ISSUE
|
Routing PW Solid Waste | 6/22/2020 | | 6/26/2020 | | PASS |
Evan Carpenter
|
|
|
|
Routing - PLAN CHECK | 6/18/2020 | | 6/26/2020 | | PASS |
Javier Guzman
|
|
|
|
Routing - Design Review | 6/18/2020 | | 6/24/2020 | | PASS |
Josh Wilson
|
|
|
|
Routing PW Flood Plain | 6/22/2020 | | 6/23/2020 | | PASS |
Jason C. Taylor
|
|
|
Project is outside Special Flood Hazard Area, no floodplain review required. If you have any questions, please call Jason Taylor at ###-####.
|
Routing PW Street Lights | 6/22/2020 | | 6/23/2020 | | PASS |
Tom Marshall
|
|
|
|
Routing PW Sewer Design | 6/22/2020 | | 6/22/2020 | | PASS |
DeAnn Brown
|
|
|
|
Routing PW Drainage | 6/22/2020 | | 6/22/2020 | | PASS |
Brian Murphy
|
|
|
minor grading modifications ok
|
Routing - PUBLIC WORKS | 6/18/2020 | | 6/22/2020 | | PASS |
Morgan Webb
|
|
|
please route to whomever else in PW needs to re-review project
|
Plan Modification Accepted | | | 6/12/2020 | | DONE |
|
|
|
Modifications to trash enclosure
|
Plan Reviewer's activity | | | 6/12/2020 | | DONE |
Javier Guzman
|
|
|
Failed Prescreen
For prescreen review provide and upload the following:
• Provide a completed plan modification application, application can be found on our website at https://www.cityofboise.org/departments/planning-and-development-services/building/building-permits/commercial-construction-500/522-plan-modification/
|
OVERRIDE | | | 3/5/2020 | | |
|
|
|
|
Plan assigned to (JG) | 9/4/2019 | 9/4/2019 | 3/5/2020 | | PASS |
Javier Guzman
|
|
|
3rd rev comp, 502 Pivot KA Barber Valley
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/5/2020 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 3/5/2020 | | DONE |
|
|
|
NEED
ACHD
MET
RP
GC FORM
REVISED VALUE
|
Issue PAID IN FULL permit | | | 3/5/2020 | | DONE |
|
|
|
|
Print Occupancy Form | | | 3/5/2020 | | DONE |
|
|
|
|
Routing PW Sewer Design | 3/4/2020 | | 3/4/2020 | | PASS |
DeAnn Brown
|
|
|
|
Routing - PLAN CHECK | 1/23/2020 | | 2/10/2020 | | PASS |
Carl D Madsen
|
|
|
|
Routing Off Site - STRUCTURAL | 1/23/2020 | | 2/10/2020 | | PASS |
Javier Guzman
|
|
|
Signed off in ePlan by Stapley engineers
|
Routing PW Sewer Design | 1/23/2020 | | 1/31/2020 | | FAIL |
DeAnn Brown
|
|
|
Revisions to the sewer design and easement document completion still needed. Coordinating directly with Rob Sunderlage and Tucker Anderson.
|
Routing Off Site - STRUCTURAL | 12/17/2019 | | 12/30/2019 | | FAIL |
Javier Guzman
|
|
|
failed in ePlan by Stapley Engineering
|
Routing - PLAN CHECK | 12/17/2019 | | 12/30/2019 | | FAIL |
Javier Guzman
|
|
|
|
Routing - FIRE | 12/17/2019 | 12/17/2019 | 12/20/2019 | | PASS |
Mark Stumbaugh
|
|
|
MAS Resub Pivot KA
|
Routing - PLUMBING | 12/17/2019 | | 12/20/2019 | | PASS |
Dan Ediger
|
|
|
See reline note. Per ISPC and plans
|
Routing - MECHANICAL | 12/17/2019 | | 12/18/2019 | | PASS |
Troy James
|
|
|
|
Routing PW Sewer Design | 12/17/2019 | | 12/17/2019 | | FAIL |
DeAnn Brown
|
|
|
Sewer extension plans were not submitted to Boise Public Works. Make changes show in changemarks and submit updated sheets directly to DeAnn Brown.
|
Route to Impact Fee Review | 10/15/2019 | 10/18/2019 | 10/17/2019 | | PASS |
Eric Bilimoria
|
|
|
Review requested for Commercial Permit
|
1st review completed | | | 10/15/2019 | | FAIL |
Javier Guzman
|
|
|
|
Routing - PLAN CHECK | 9/4/2019 | | 10/15/2019 | | FAIL |
Javier Guzman
|
|
|
|
Routing - FIRE | 8/30/2019 | 9/4/2019 | 10/11/2019 | | FAIL |
Mark Stumbaugh
|
|
|
10/10 - 502 Pivot KA Barber Valley
|
Routing Off Site - STRUCTURAL | 9/4/2019 | | 10/11/2019 | | FAIL |
Javier Guzman
|
|
|
failed in ePlan by Stapley Engineering
|
Routing PW Drainage | 9/4/2019 | | 9/13/2019 | | PASS |
Brian Murphy
|
|
|
|
Routing - Design Review | 9/4/2019 | | 9/11/2019 | | PASS |
Josh Wilson
|
|
|
Ok per DRH19-00161
|
Routing - PLANNING | 9/4/2019 | | 9/10/2019 | | PASS |
Brent Moore
|
|
|
|
Routing PW Flood Plain | 9/4/2019 | | 9/9/2019 | | PASS |
Jason C. Taylor
|
|
|
Approved LOMR 13-10-1085A on File. No floodplain review required. If you have any questions, please call Jason Taylor at ###-####.
|
Routing - PLUMBING | 9/4/2019 | | 9/6/2019 | | PASS |
Dan Ediger
|
|
|
See Redline notes.
Per plans and ISPC
|
Routing PW Environmental | 9/4/2019 | | 9/6/2019 | | PASS |
Rick Christenson
|
|
|
|
Routing - Addressing | 9/4/2019 | | 9/6/2019 | | PASS |
Doug Chausow
|
|
|
BUILDING ADDRESS: 3083 E Barber Valley Rd
|
Routing - PUBLIC WORKS | 9/4/2019 | | 9/6/2019 | | PASS |
Angela Hardy
|
|
|
|
Routing PW Street Lights | 9/4/2019 | | 9/5/2019 | | PASS |
Tom Marshall
|
|
|
|
Routing PW Sewer Design | 9/4/2019 | | 9/5/2019 | | FAIL |
DeAnn Brown
|
|
|
Sewer extension plans have not been submitted to Boise Public Works for review and approval. Coordinate review with DeAnn Brown.
|
Routing - MECHANICAL | 9/4/2019 | | 9/5/2019 | | FAIL |
Troy James
|
|
|
See eplan. Emailed corrections to Tucker with Babcock design.
|
Routing PW Solid Waste | 9/4/2019 | | 9/5/2019 | | PASS |
Evan Carpenter
|
|
|
|
Routing - Erosion and Sediment | 9/4/2019 | | 9/4/2019 | | PASS |
Michael Zawacki
|
|
|
RP needed. Site is in area with high water table, dewatering may be needed.
Site prep inspection required.
Some errors in location on swppp, please correct for on site binder.
|
Intake Approval | | | 8/30/2019 | | PASS |
Brian Murphy
|
|
|
|
Intake Approval | | | 8/28/2019 | | FAIL |
Brian McGowan
|
|
|
The required Recorded Document must be provided prior to accepting the Prescreen.
|
Intake Approval | | | 8/22/2019 | | |
Brian McGowan
|
|
|
Please address or provide the following information for your Prescreen to be approved:
1. No Sheet E101 was provided for the Street Lights.
2. I could not find the Fire Hydrant locations on CS101.
3. Appendix J needs to be signed by a City Official.
4. I could not locate the Drainage Sytems O and M Plan
5. No Sheet G101 was uploaded.
6. No Sheet E103 was uploaded.
7. No Sheet E502 was uploaded.
8. No Sheet E301 was uploaded.
9. No Sheets E201, E501, E401, E100, E 601, E602 were uploaded.
|
Application received | | | 8/8/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Aug 8 2019 1:57PM
|