Permit Information
Permit NumberBLD19-03618
StatusFinaled
Name CM COMPANY
Site Address 800 E PARK BLVD Unit: 400
Project NameSt. Luke's IHT Offices - 4th
Customer Number 
ePlanReviewYes
Description
(ST. LUKE’S INTEGRATED HEALTH TECHNOLOGIES OFFICE – ENTIRE 4TH STORY – ST. LUKE’S PLAZA IV) (5-8-20 PLAN MODIFICATION TO REMOVE TWO CONFERENCE ROOMS AND REPLACE THEM WITH OPEN OFFICE USE. THE TOTAL OCCUPANT LOAD OF THE 4TH STORY IS REDUCED BY 12 BUT SINCE THE REDUCTION IS INCONSEQUENTIAL, NO CHANGES WERE MADE TO THE PERMIT. IN ADDITION, SOME LIGHT FIXTURES WILL BE CHANGED BUT ANY CHANGE IN THE TOTAL WATTAGE USED FOR LIGHTING WAS CONSIDERED NEGLIGIBLE.) The fire sprinkler system is used for high rise and for code trade-offs. To remodel the entire 33,286 square foot 4th story (about 31,976 square feet with shafts not included) of an existing 7 story high rise building to be used as an administrative office space. Work is to include interior nonbearing walls, two upgraded multi-user toilet rooms accessible to the disabled, two single-user toilet rooms accessible to the disabled, suspended acoustical ceilings, gypsum board ceilings and soffits, new 90 minute fire doors in the existing 2-hr stairway enclosures, upgraded elevator lobby, new smoke-fire dampers where HVAC ducts and transfer openings penetrate shafts and where ducts penetrate the elevator vestibule, interior doors, interior windows, millwork, core drilled 2-hr floor for electrical outlet floor boxes, and finishes. The existing 1-hr corridor will be downgraded to a non-rated corridor. Quick-response fire sprinkler heads will be installed throughout the 4th story to substitute for 1-hr corridors and to reduce exit door separation. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 (including replacing all heads with quick-response fire sprinklers) and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice 6/25/20207/9/2020 DONE
mailed 7-9-2020
Permanent Occupancy  6/15/2020 DONE
BLD-Final6/9/20206/9/20206/9/2020PPASS
DetailsDave Hannah
Bruce Phone #: ###-####
BLD-Final6/4/20206/4/20206/5/2020PPEND
DetailsDave Hannah
Bruce *screened* Phone #: ###-#### ok for tco but needs to install glass in doors
FIRE-Final Inspection6/2/20206/4/20206/4/2020APASS
DetailsJim Page
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extingiushers are placed with current inspection tags. Final life fire safety inspection is complete, signatures provided on permit sign off card.

Bruce *screeend* Phone #: ###-####
FIRE-Final Inspection6/1/20206/3/20206/2/2020ACANC
DetailsJim Page
Rescheduled for 04JUN2020 to coincide with fire alarm inspection, this request is cancelled.

Bruce *screeend* Phone #: ###-####
CHANGE STATUS TO (ISS)  5/28/2020 DONE
Plan assigned to (CJW)4/28/20204/28/20205/8/2020 PASS
DetailsCarl Westfall
plan mod - St. Luke's offices (plan intake approved)
Routing - PLAN CHECK5/7/2020 5/8/2020 PASS
DetailsCarl Westfall
IBC plan mod review approved
Plan Reviewer's activity  5/8/2020 PASS
Plan mod review approved
Permit Ready to Issue  5/8/2020 DONE
plan mod approved
Routing - PLAN CHECK5/4/2020 5/7/2020 PASS
DetailsCarl Westfall
Plan intake review approved the 2nd time because problems with ePlanReview deleted what had been done previously.
Routing - PLAN CHECK5/7/2020 5/7/2020 PASS
DetailsCarl Westfall
Plan mod review approved
Plan Modification Accepted  5/4/2020 DONE
Workflow in ePlanReview received
Plan Modification Accepted  4/28/2020 DONE
removal of conference rooms in N.W. corner and replace w/additional cubicle space.
Electrical revisions included all associated changes related to removal of conference rooms, along with miscellaneous changes to power and data requested by owner.
Mechanical revision include all associated changes related to removal of conference rooms, along with miscellaneous changes requested by owner.
BLD-Ceiling Grid Inspection3/24/20203/25/20203/26/2020PPASS
DetailsDave Hannah
Bruce Phone #: ###-####
BLD-Framing/Rough-in2/24/20202/25/20202/25/2020APART
DetailsDave Hannah
Bruce- Phone #: ###-#### hard lids in rest rooms ok to cover
BLD-Framing/Rough-in2/14/20202/18/20202/18/2020APASS
DetailsDave Hannah
bruce Phone #: ###-#### ok to cover restrooms
BLD-Framing/Rough-in2/11/20202/12/20202/12/2020ANR
DetailsDave Hannah
Bruce Phone #: ###-####
BLD-Framing/Rough-in1/13/20201/13/20201/13/2020PPART
DetailsJim Storey
Bruce Phone #: ###-####// small offices out of the core area ok to start gyp.// c/n for ft backing/ fire stopping floor 2hr plm and ele.// patch 2 hr fireprooffing.
Print Occupancy Form  12/2/2019 DONE
Issue PAID IN FULL permit  12/2/2019 DONE
Permit Ready to Issue  11/21/2019 DONE
MET
NEED
GC
Revised Certificate of Value
Plan assigned to (CJW)9/30/201910/25/201911/20/2019 PASS
DetailsCarl Westfall
(1st done) 10/18/19 (L-3 - 15 days) (eplan - 60 sheets) St. Luke’s Integrated Health Technologies Office (back to applicant)
Routing - PLAN CHECK11/19/2019 11/20/2019 PASS
DetailsCarl Westfall
PLANS/APPL TAKEN TO FRONT DESK  11/20/2019 DONE
Routing - PLAN CHECK11/15/2019 11/19/2019 FAIL
DetailsCarl Westfall
Mec and Plum drawings did not provide the required stamp space.
Plan resubmittals received  11/19/2019 DONE
Plan resubmittals received  11/15/2019 DONE
Route to Impact Fee Review10/24/201910/27/201910/25/2019 PASS
DetailsEric Bilimoria
Review requested for Commercial Permit
Routing - FIRE9/30/20199/30/201910/24/2019 PASS
DetailsErika Akin
Attached comments to case
1st review completed  10/24/2019 DONE
Plan resubmittals requested  10/24/2019 DONE
Routing - PLAN CHECK9/30/2019 10/24/2019 FAIL
DetailsCarl Westfall
Routing - PLUMBING9/30/2019 10/7/2019 PASS
DetailsDaryl Spivey
Per plan and ISPC.
Routing - MECHANICAL9/30/2019 10/4/2019 PASS
DetailsTroy James
Routing - PLANNING9/30/2019 10/1/2019 PASS
DetailsDavid Moser
office remodel of 4th floor and allowed in C-1 zone
Routing - Addressing9/30/2019 10/1/2019 PASS
DetailsDoug Chausow
4th Floor, Suite 400
Routing - PUBLIC WORKS9/30/2019 10/1/2019 PASS
DetailsMorgan Webb
Intake Approval  9/30/2019 PASS
Intake Approval  9/19/2019 FAIL
DetailsJavier Guzman
For prescreen review provide and upload the following:
• Plan sheet ID1.2B, A3.1B, A4.3B, A7.0B, A7.1B, A9.1B required to be stamped by an Idaho licensed architect.
• Per ePlan submittal standards the reserve the bottom right corner on all the drawing plumbing and mechanical plan sheets for the City electronic stamps. Leave a blank 4” x 2” space located 3” off the right sheet edge to allow for the title block. see ePlan standards at https://www.cityofboise.org/media/7025/electronic_submittal_standards.pdf
• Per ePlan submittal standards the reserve the bottom right corner on the drawing plans for the City electronic stamps. Leave a blank 4” x 2” space located 3” off the right sheet edge to allow for the title block on plan sheet E13.0 see ePlan standards at https://www.cityofboise.org/media/7025/electronic_submittal_standards.pdf
Application received  9/13/2019 DONE
Application submitted via PDS Online on Sep 13 2019 1:54PM