Permit Information
Permit NumberBLD19-04013
StatusIssued
Name BILTMORE COMPANY
Site Address 5892 N FIVE MILE RD
Project NameNorthview Apts Bldg 1
Customer NumberBLD19-04008 FOUNDATION
ePlanReviewYes
Description
(NORTHVIEW APARTMENTS)(BLDG. 1) //6-1-2020 PLAN MODIFICATION #2 REVISED MANUAL J, D AND S REVISED. Jg// - //3-11-2020 PLAN MODIFICATION #1 FOR A CLARIFICATION ON THE FIRE PARTITION ASSEMBLIES AT THE INTERIOR SHEAR WALLS. Jg// Permit for the construction of a 27,096 sq. ft., 3-story, 24-unit apartment building. (Note: this is a building only permit and the foundation only permit is found under BLD19-04008). Work to include general site work and the construction of the new building per the approved plans and attached engineering. Note: Special Inspections required see form 310. This building is to be fully fire sprinklered with a NFPA 13-R system as required for residential occupancy and story increase. **JG**
Contact Information
See Activities list for contact information
Color Key
Current location of plans being reviewed:  
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
FIRE-Final Inspection8/7/20208/10/20208/10/2020ACANC
DetailsTroy Cobbley
Need the project related fire alarm and fire sprinkler permits finaled prior to a life safety inspection. ]
crrened- Matt Phone #: ###-####
BLD-Energy code compliance7/20/20207/20/20207/20/2020PPART
DetailsTell Riley
Matt *screened* Phone #: ###-####//ok pending tenting approval for fire sprinklers prior to cover//
BLD-Framing/Rough-in7/16/20207/17/20207/17/2020APART
DetailsTell Riley
Matt - */Screened*/ Phone #: ###-####last two units first floor//add blocking between joists a bearing wall//ok to insulate//
BLD-Framing/Rough-in7/16/20207/16/20207/17/2020PPART
DetailsDave Hannah
Screened- Mat- call before arrival Phone #: ###-#### 2econ and third floors ok insulate
BLD-Energy code compliance7/15/20207/15/20207/15/2020PPART
DetailsTell Riley
SCREENED // Matt Phone #: ###-####//3rd set of 6 from east end//2 top units still need tenting inspection//other 4 units appear to be ok//
BLD-Framing/Rough-in7/10/20207/13/20207/13/2020APASS
DetailsTony Young
screened // Pat Phone #: ###-####// ok to insulate//
BLD-Framing/Rough-in7/8/20207/8/20207/8/2020PFAIL
DetailsTell Riley
Matt - /*screened*/ Phone #: ###-####//corrections have not been completed to meet plans and specifications//See Matt onsite for CN//
BLD-Framing/Rough-in7/7/20207/8/20207/8/2020ANR
DetailsTell Riley
Matt - /*screened*/ Phone #: ###-####//corrections are not complete//moved to PM//
BLD-Framing/Rough-in7/6/20207/6/20207/6/2020PFAIL
DetailsTell Riley
SCREENED // Matt Phone #: ###-####//2nd six units still need corridor fire wall to meet listing on plans//3rd six units correction notice issued for framing corrections, see Matt onsite for list--also corridor fire wall on these six units needs to meet listing on plans//
BLD-Wall cover6/30/20206/30/20207/1/2020PCANC
DetailsTell Riley
screened // Matt Phone #: ###-####
BLD-Wall cover7/1/20207/1/20207/1/2020PPART
DetailsTell Riley
areas in fire wall to roof deck over center stairways were filled with gyp board and penetrations fire caulked//this was verified by photos sent by contractor//
BLD-Energy code compliance6/26/20206/29/20206/29/2020APART
DetailsTell Riley
ok to cover units 2nd six from east end areas not affected by CN//CN issued for fire wall 1 hr at corridor--does not refelct listing as it current create a cavity above panty areas, fire caulk penetrations//note see detail C3 for corridor ceiling 1 hr construction//
BLD-Energy code compliance6/25/20206/26/20206/26/2020ACANC
DetailsTell Riley
Phone #: ###-#### Inspection requested via web by Matthew Bundy
BLD-Wall cover6/23/20206/23/20206/23/2020PPART
DetailsTell Riley
Matt Phone #: ###-#### Inspection requested via web by Matthew Bundy//6 units on west end for fur-downs only//framing in these areas ok//pending trades inspections//fire caulk as discussed//
BLD-Framing/Rough-in6/23/20206/23/20206/23/2020PPART
DetailsTell Riley
Matt Phone #: ###-#### Inspection requested via web by Matthew Bundy//2nd six units east end//see CN onsite//ok ot insulate only//corrections will need completed prior to cover//
BLD-Energy code compliance6/17/20206/17/20206/17/2020PPART
DetailsTell Riley
Matt *screened* Phone #: ###-####//107, 108,207,208,307,308// energy requirements updated by designer via res check//attic insulation in these units will Be r50//fire caulk complete//
BLD-Energy code compliance6/15/20206/16/20206/16/2020AFAIL
DetailsTell Riley
screened // Matt Phone #: ###-####//label fire walls in attic--fire caulk penetrations//wall insulation does not meet rescheck//window u-values do not meet rescheck//1 hour rated laydown parapet was not installed for 4' from separation walls at deck//need fire sprinkler tenting inspection//
BLD-Framing/Rough-in6/11/20206/12/20206/12/2020APART
DetailsBrandon Shaw
Units 107,108, 207, 208, 307, 308
BLD-Wall cover6/11/20206/11/20206/11/2020PPART
DetailsTell Riley
screened // Matthew Phone #: ###-####//3rd 6 units 2nd floor drops--corrections made//architect approved fire blocking fix for first 4 2nd floor drops//remaining drops will have gyp on walls//
CHANGE STATUS TO (ISS)  6/5/2020 DONE
plan mod
Plan assigned to (JG)6/1/20206/1/20206/4/2020 PASS
DetailsJavier Guzman
06/09 2nd rev Plan Mod Northview Apts Bldg 1 ePlan, pend Mech
Permit Ready to Issue  6/4/2020 DONE
**DO NOT REISSUE - PLAN MOD**
Routing - MECHANICAL6/3/2020 6/4/2020 PASS
DetailsTroy James
Signed off in ePlan by Mechanical Troy James
BLD-Wall cover6/3/20206/3/20206/3/2020PPART
DetailsTell Riley
screened // Matt Phone #: ###-####//3rd set of 2nd floor units for pre-rock areas//need to fire caulk areas discussed//looked at gyp on first 4 units--need to extend down walls on rated wall side and exterior walls, or provide detail from architect//
BLD-Wall cover6/2/20206/3/20206/3/2020ACANC
DetailsTell Riley
screened // Matt Phone #: ###-####//moved to pm//no one onsite//
Routing - PLAN CHECK6/3/2020 6/3/2020 PASS
DetailsJavier Guzman
Routing - PLAN CHECK6/1/2020 6/2/2020 PASS
DetailsJavier Guzman
Routing - MECHANICAL6/1/2020 6/2/2020 FAIL
DetailsTroy James
Emailed corrections to A1 heating
Plan Modification Accepted  5/26/2020 DONE
plan mod #2 for manual J
BLD-Wall Bracing5/21/20205/22/20205/22/2020APASS
DetailsBrandon Shaw
screened// exterior shear and fire caulk 2nd fix fir down// Pat Phone #: ###-####
BLD-Other5/19/20205/19/20205/19/2020PPART
DetailsTell Riley
rough to cover .. screened // Matt Phone #: ###-####//2nd floor east end 2 apartments//cover ceiling for fur downs only//
BLD-Wall Bracing5/18/20205/18/20205/18/2020PFAIL
DetailsTell Riley
Matt *screened* Phone #: ###-####//Still need RFI for densglass shear walls in corridors//plans show all shear walls to be wood structural panels, and plans do not have nailing or shear schedule for densglass//
BLD-Wall Bracing5/11/20205/12/20205/12/2020AFAIL
DetailsTell Riley
Matt Phone #: ###-####//CN issued see onsite//
BLD-Other5/8/20205/8/20205/8/2020PCANC
DetailsTell Riley
rough to cover // Matt Phone #: ###-####//not ready, need to have rough ins inspected in areas wanting to cover for soffits//
BLD-Wall Bracing4/16/20204/17/20204/17/2020PPART
DetailsDave Hannah
Screened- Matt Phone #: ###-#### thrid floor int sheer walls ok to cover
BLD-Wall Bracing4/3/20204/3/20204/3/2020PPART
DetailsTell Riley
*cleared* Please call ahead so site can cleared Pat Phone #: ###-####///second story interior shear walls prior to gyp cover//
BLD-Wall Bracing3/19/20203/20/20203/20/2020APART
DetailsTell Riley
please call .... shear // Pat Phone #: ###-####/interior shear on level one ok to cover with gyp//
CHANGE STATUS TO (ISS)  3/18/2020 DONE
Plan assigned to (JG)3/4/20203/4/20203/17/2020 PASS
DetailsJavier Guzman
03/17 plan mod Northview Apts ePlan
Routing - PLAN CHECK3/11/2020 3/17/2020 PASS
DetailsJavier Guzman
Permit Ready to Issue  3/17/2020 DONE
plan mod approved
Plan Reviewer's activity  3/6/2020 DONE
DetailsJavier Guzman
Provide the following to pass plan modification prescreen:
• Revise: On the plan modification application revise and include the revised S sheets to the application list of all applicable revised sheet numbers to item 3
• Provide revised structural plan sheets S1.00, S1.01, S4.00, S4.10 stamped by an Idaho license engineer
Plan Modification Accepted  3/4/2020 DONE
plan mod #1
BLD-Framing/Rough-in2/18/20202/18/20202/18/2020PFAIL
DetailsTell Riley
Pat - Sheer Wall Inspection Phone #: ###-####//interior fire walls and shear walls--do not meet specifications on plans for UL assembly and sound//discussed with contractor UL assembly per plans and shear walls per structurals//
Issue PAID IN FULL permit  2/14/2020 DONE
Print Occupancy Form  2/14/2020 DONE
Telephone call  2/13/2020 DONE
Sheryl from Biltmore requested that we add the ACHD case to our BLD so she can pay the fee.
Plan assigned to (JG)10/15/201910/21/20192/12/2020 PASS
DetailsJavier Guzman
3rd rev comp, 01/16 2nd rev, 506 Northview Apts Building pend fire
Routing - PLAN CHECK2/5/2020 2/12/2020 PASS
DetailsJulie Romig
PLANS/APPL TAKEN TO FRONT DESK  2/12/2020 DONE
Permit Ready to Issue  2/12/2020 DONE
met (in ePlan) Need GC
Routing - PLAN CHECK1/30/2020 2/4/2020 FAIL
DetailsJavier Guzman
See email from Julie Romig regarding corrections required.
Routing - PLUMBING1/30/2020 2/4/2020 PASS
DetailsDan Ediger
Per plans and the ISPC
Routing - FIRE1/30/20201/30/20201/30/2020 PASS
DetailsJoe Bruce
1-Hour fire rated riser room now shown on plans (A101 and A102).
Routing - FIRE1/10/20201/10/20201/28/2020 FAIL
Details
Resubmittal Northview Apt - Update the plans to show the required fire rated assemblies at walls and ceiling for the fire riser room. **JHB**
Plan resubmittals requested  1/28/2020 DONE
DetailsJoe Bruce
Sent an email to Sheryl Smith with Biltmore Co. for a resubmittal.
Routing - PLAN CHECK1/10/2020 1/21/2020 FAIL
DetailsJavier Guzman
Routing - PLUMBING1/10/2020 1/16/2020 FAIL
DetailsDan Ediger
See Changemark
Routing PW Sewer Design1/10/2020 1/15/2020 PASS
DetailsDeAnn Brown
Routing - MECHANICAL1/10/2020 1/15/2020 PASS
DetailsTroy James
Outside air duct shall run to return plenum for all units.
Route to Impact Fee Review11/27/201911/30/201911/29/2019 PASS
DetailsTravis P Black
Review requested for Commercial Permit
1st review completed  11/27/2019 FAIL
DetailsJavier Guzman
Routing - PLAN CHECK10/21/2019 11/27/2019 FAIL
DetailsJavier Guzman
Routing - FIRE10/15/201910/21/201911/25/2019 FAIL
DetailsErika Akin
Attached comments to case and emailed architect
Routing Off Site - STRUCTURAL10/21/2019 11/19/2019 PASS
DetailsJavier Guzman
signed off in ePlan by AHJ Engineers
Routing - PLANNING10/21/2019 11/5/2019 PASS
DetailsCeline Acord
Comply with Design Review conditions / PUD18-00022
Routing - PLUMBING10/21/2019 10/26/2019 FAIL
DetailsDan Ediger
See changemarks
Routing - MECHANICAL10/21/2019 10/25/2019 FAIL
DetailsTroy James
Emailed manual j designer and applicant corrections.
Routing PW Street Lights10/22/2019 10/23/2019 PASS
DetailsTom Marshall
Routing PW Sewer Design10/22/2019 10/23/2019 FAIL
DetailsDeAnn Brown
Show sewer services as installed. Refer to changemarks.
Routing PW Solid Waste10/22/2019 10/23/2019 PASS
DetailsEvan Carpenter
Routing PW Drainage10/22/2019 10/22/2019 PASS
DetailsBrian Murphy
Routing - Addressing10/21/2019 10/22/2019 PASS
DetailsDoug Chausow
Routing - PUBLIC WORKS10/21/2019 10/22/2019 PASS
DetailsMorgan Webb
Routing - Erosion and Sediment10/21/2019 10/22/2019 PASS
DetailsMichael Zawacki
Please refer to ESC19-00034 for main site esc permit
Routing - Design Review10/21/2019 10/22/2019 PASS
DetailsKatelyn Menuge
Redlined parking dimensions and need for parking blocks or 6-inch curbing. If covered bicycle parking is under the stairs we need three bicycle spaces under each stairwell.
Intake Approval  10/15/2019 PASS
DetailsJavier Guzman
Intake Approval  10/14/2019 FAIL
DetailsJavier Guzman
For prescreen review provide and upload the following:
• A portion of the previous request below was not addressed Per ePlan submittal standards the reserve the bottom right corner on the drawing plans for the City electronic stamps. Leave a blank 4” x 2” space located 3” off the right sheet edge to allow for the title block on plan sheet A205. see ePlan standards at https://www.cityofboise.org/media/7025/electronic_submittal_standards.pdf
• Revised plan sheets A401, A404, A405 came back sized 11” x 8” and are required per checklist to be a minimum 18” x 24” and Per ePlan submittal standards the reserve the bottom right corner on the drawing plans for the City electronic stamps. Leave a blank 4” x 2” space located 3” off the right sheet edge to allow for the title block on plan sheet A401, A404, A405. see ePlan standards at https://www.cityofboise.org/media/7025/electronic_submittal_standards.pdf
Intake Approval  10/9/2019 FAIL
DetailsJavier Guzman
For prescreen review provide and upload the following:
• Uploaded engineering calculations are required to be stamped, signed and dated by an Idaho licensed engineer
• Per checklist Include on site plan A1.1 Site Plan Clearly marked “Fire Department Access Roadways”
• Per checklist clearly mark on site plan A1.1 Site Plan location of Fire Hydrants
• Per ePlan submittal standards the reserve the bottom right corner on the drawing plans for the City electronic stamps. Leave a blank 4” x 2” space located 3” off the right sheet edge to allow for the title block on plan sheet L1, A101, A103, A205, A401, A404, A405, S0.00. see ePlan standards at https://www.cityofboise.org/media/7025/electronic_submittal_standards.pdf
Application received  10/8/2019 DONE
Application submitted via PDS Online on Oct 8 2019 11:20AM
FIRE-Final Inspection8/13/20208/14/2020 A 
DetailsJim Page
Matt *screened Phone #: ###-####
Routing - Design Review1/16/2020   PASS
DetailsKatelyn Menuge
Updated Redlines, parkng striping, curbing and bike rack requirements