BLD-Foundation | 7/23/2020 | 7/24/2020 | 7/24/2020 | A | PASS |
Brandon Shaw
|
|
|
Chris - */Screened*/ 2pm pour time Phone #: ###-####
|
(F) Reprint permit | | | 7/22/2020 | | DONE |
|
|
|
|
Telephone call | | | 1/8/2020 | | DONE |
|
|
|
talked to GC and verify the email and resend the permit to be sign
|
Issue PAID IN FULL permit | | | 1/6/2020 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 1/6/2020 | | DONE |
|
|
|
|
Telephone call | | | 1/6/2020 | | DONE |
|
|
|
emailed inspection card and permit to be sign to- joe@joy.us.com Eplan needs to be release
|
Plan assigned to (JG) | 12/12/2019 | 12/12/2019 | 12/27/2019 | | PASS |
Javier Guzman
|
|
|
12/24 L2 AT&T ePlan, pend fire
|
Routing - FIRE | 12/12/2019 | 12/12/2019 | 12/27/2019 | | PASS |
Erika Akin
|
|
|
No comments attached. Diesel generator to be installed with new cell tower and supporting equipment. Tank capacity 190 gallons. Normal and emergency venting details provided. Signage per NFPA 704 will be required.
|
Routing Off Site - STRUCTURAL | 12/12/2019 | | 12/27/2019 | | PASS |
Javier Guzman
|
|
|
Signed off in ePlan by AHJ Engineers
|
1st review completed | | | 12/27/2019 | | DONE |
Javier Guzman
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/27/2019 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 12/27/2019 | | DONE |
|
|
|
emailed GC with fees due.
|
Routing - PLAN CHECK | 12/12/2019 | | 12/27/2019 | | PASS |
Javier Guzman
|
|
|
|
Routing - PLANNING | 12/12/2019 | | 12/18/2019 | | PASS |
David Moser
|
|
|
See CAA19-00108
|
Intake Approval | | | 12/11/2019 | | PASS |
Javier Guzman
|
|
|
|
Intake Approval | | | 10/15/2019 | | FAIL |
Julie Romig
|
|
|
1. Upload all drawings at 22"x34" sheet size in order to have scaled drawings at the city's minimum sheet size.
2. On each drawing, leave a 4"x2" blank space at the bottom right hand corner located 3" off the right sheet edge for the City of Boise permit stamp. On the Cover sheet, leave a 4"x4" blank space in this location.
Please refer to the electronic plan review submittal standards for additional information.
https://www.cityofboise.org/media/7025/electronic_submittal_standards.pdf
3. Complete Form 310 for special inspections. Form must be completed and stamped/signed by engineer and signed by owner.
|
Application received | | | 10/10/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Oct 10 2019 2:48PM
|