BLD-Final | 8/11/2020 | 8/12/2020 | 8/12/2020 | P | PASS |
Tell Riley
|
|
|
Kristin *screened Phone #: ###-####//back room and mezzanine were cleaned up per daves entry//
|
Temporary Occupancy | 6/10/2020 | 9/8/2020 | 6/10/2020 | | DONE |
Tiffany Carson-Herker
|
|
|
|
Print Occupancy Form | | | 6/10/2020 | | DONE |
|
|
|
|
BLD-Final | 6/5/2020 | 6/5/2020 | 6/8/2020 | P | PART |
Dave Hannah
|
|
|
call for access, around 4pm please- Christin screened Phone #: ###-#### ok for tco needs to clean up site
|
FIRE-Final Inspection | 6/4/2020 | 6/5/2020 | 6/5/2020 | A | PASS |
Jim Page
|
|
|
Previously noted items have been corrected, door hardware was being changed at time of inspection, will be completed before BLD final. No fire sprinklers, no fire alarms, firee xtinguishers are placed with current inspection tags. Final life fire safety inspection for area of work is complete, signature provided on permit sign off card.
call for access- August *screened* Phone #: ###-####
|
FIRE-Final Inspection | 6/2/2020 | 6/3/2020 | 6/3/2020 | A | FAIL |
Jim Page
|
|
|
Provide single action door hardware on doors that did not unlock upon handle action. Provide correct signage on main entry reading "Door to remain unliocked whilke building is occupied". Service or replace non-functioning exit signs, west side of tenant space.
call ahead 30 minutes - screened // August Phone #: ###-####
|
Issue PAID IN FULL permit | | | 3/24/2020 | | DONE |
|
|
|
|
Print Occupancy Form | | | 3/24/2020 | | DONE |
|
|
|
|
Telephone call | | | 3/23/2020 | | DONE |
|
|
|
Emailed Kristin letting her know she needs to sign the 302 and emailed her the fees due.
|
Permit Ready to Issue | | | 3/19/2020 | | DONE |
|
|
|
all met: kkuborn@icloud.com
Need GC
Need Revised Values
|
Plan assigned to (JAR) | 12/5/2019 | 12/5/2019 | 3/18/2020 | | DONE |
Julie Romig
|
|
|
1st Rev Comp - 3rd comp - L3 Amethyst Salon
|
Routing - PLAN CHECK | 3/17/2020 | | 3/18/2020 | | PASS |
Julie Romig
|
|
|
4th Review - no additional fees, extra review for items missed in previous review.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/18/2020 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 3/11/2020 | | 3/16/2020 | | FAIL |
Julie Romig
|
|
|
|
Routing - MECHANICAL | 3/11/2020 | | 3/12/2020 | | PASS |
Troy James
|
|
|
|
Routing - PLUMBING | 3/11/2020 | | 3/12/2020 | | PASS |
Daryl Spivey
|
|
|
Per plan and ISPC.
|
Routing - PLAN CHECK | 2/18/2020 | | 3/6/2020 | | FAIL |
Julie Romig
|
|
|
|
Routing - MECHANICAL | 2/18/2020 | | 2/19/2020 | | FAIL |
Troy James
|
|
|
Talked to architect. He is going to provide a detail of pedicure with exhaust.
|
Routing - PLUMBING | 2/18/2020 | | 2/18/2020 | | FAIL |
Daryl Spivey
|
|
|
1. RPBP's need to be listed on plumbing fixture schedule and HS-1's cannot be on same water lines downstream of RPBP's feeding SP-1's. Vacuum breakers required on HS-1's.
|
Route to Impact Fee Review | 1/14/2020 | 1/17/2020 | 1/15/2020 | | PASS |
Travis P Black
|
|
|
Review requested for Commercial Permit
|
Routing - FIRE | 12/5/2019 | 12/5/2019 | 1/14/2020 | | PASS |
Erika Akin
|
|
|
Attached comments to case
|
1st review completed | | | 1/14/2020 | | FAIL |
Julie Romig
|
|
|
|
Routing - PLAN CHECK | 12/5/2019 | | 1/14/2020 | | FAIL |
Julie Romig
|
|
|
|
Routing - PLANNING | 12/5/2019 | | 12/10/2019 | | PASS |
Karla Nelson
|
|
|
use allowed by right and parking is not required in P-1 parking overlay. If there are any exterior changes design review approval would be required.
|
Routing - MECHANICAL | 12/5/2019 | | 12/9/2019 | | FAIL |
Troy James
|
|
|
See eplan
|
Routing - PLUMBING | 12/5/2019 | | 12/9/2019 | | FAIL |
Daryl Spivey
|
|
|
See change mark notes on P1-1`
|
Routing - Addressing | 12/5/2019 | | 12/6/2019 | | PASS |
Doug Chausow
|
|
|
|
Routing - PUBLIC WORKS | 12/5/2019 | | 12/6/2019 | | PASS |
Morgan Webb
|
|
|
|
Intake Approval | | | 12/2/2019 | | PASS |
|
|
|
|
Intake Approval | | | 11/27/2019 | | FAIL |
Michael Hanson
|
|
|
Provide vicinity map and key plan indicated on G1.1 but missed from that sheet.
Provide new reflected ceiling plan A2.1 as indicated in checklist.
|
Application received | | | 11/19/2019 | | DONE |
|
|
|
Application submitted via PDS Online on Nov 19 2019 11:22AM
|
BLD-Aging Inspection | 8/5/2020 | 8/5/2020 | | | |
Dave Hannah
|
|
|
|