Permit Information
Permit NumberBLD19-04843
StatusIssued
Name JEREMY JENSEN
Site Address 10470 W OVERLAND RD
Project NameRidgeline Bike & Ski
Customer Number 
ePlanReviewNo
Description
**(RIDGELINE BIKE & SKI)** NO NEW WORK IS AUTHORIZED UNDER THIS PERMIT. Application for inspection to determine requirements for issuance of a Certificate of Occupancy for a 5,643 sq. ft. existing retail tenant space previously occupied by “Ken Bicycles” under BLD10-00354. There will be no change to the occupancy. This building is fully Fire Sprinklered. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JG**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final1/6/20201/7/20201/7/2020PNR
DetailsMike Jordan
Jeremy Phone #: ###-####. No city approved plans on site.
FIRE-Final Inspection1/6/20201/7/20201/7/2020AFAIL
DetailsTroy Cobbley
Provide single action hardware on the rear exit door and remove deadbolts, repair exit signs and emergency lights, hang/tag fire extinguisher in back room, provide sprinkler permit for the sprinkler modifications.

not open until 10 // Jeremy Phone #: ###-####
Issue PAID IN FULL permit  1/6/2020 DONE
Permit Ready to Issue  12/20/2019 DONE
Print Occupancy Form  12/20/2019 DONE
Plan assigned to (JG)12/13/201912/13/201912/19/2019 PASS
DetailsJavier Guzman
12/19 L2 RIDGELINE BIKE & SKI Occ Eval paper
Routing - PLAN CHECK12/13/2019 12/19/2019 PASS
DetailsJavier Guzman
Case Summary (BLD)  12/19/2019 DONE
DetailsJavier Guzman
1st review completed  12/19/2019 DONE
DetailsJavier Guzman
PLANS/APPL TAKEN TO FRONT DESK  12/19/2019 DONE
Routing - FIRE12/13/201912/13/201912/18/2019 PASS
DetailsErika Akin
No work to be done under this permit. No change of use or occupancy. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems.
Fire extinguishers will be required on each level within a 75 foot travel distance of any location. Inspector to field verify life safety.
No comments attached.
Routing - PUBLIC WORKS12/13/2019 12/16/2019 PASS
DetailsMorgan Webb
Routing - Addressing12/13/2019 12/13/2019 PASS
DetailsDoug Chausow
Plans ACCEPTED BY PLAN TECH  12/13/2019 DONE
Intake Approval  12/13/2019 PASS
Recd Pcfee & Taken To Pln CK  12/13/2019 DONE
Application received 12/13/2019