Permit Information
Permit NumberBLD20-00181
StatusReady to Issue
Name Tri Ly
Site Address 116 S 6TH ST
Project Name6th & Grove - IA Podium
Customer NumberBLD230-02193
ePlanReviewYes
Description
**2 PERMITS IN EPLAN UNDER BLD20-00181** **PROJECT MANAGEMENT - Angie Brosious** (6TH & GROVE – IA PODIUM) (DRH19-00196) Note: This project to be constructed under City Code 9-3 Special Design Standards for Type V Construction code. Permit to construct a 62,400 sq ft, 7-story mixed-use residential housing project with a 18,400 sq ft Type IA podium at Level 1-2 and a 44,000 sq ft Type VA building above at Levels 3-7 with 60 dwelling units. Work to include: construction of 2-story Type IA podium including foundation, geopiers, structural steel, PT concrete slab and exterior walls; construction of 5-story Type VA under BLD20-02193. Code alternate approved for opening alternate at north wall. Special inspections required per the attached Form 310. Special Inspection survey required to verify low point of grade at beginning of construction, building height of top of podium, 4th flr, and 7th flr at framing stage, at 7th flr final construction. Approval contingent upon adhering to the approved plans on file and attached engineering. This building will be sprinklered with a fully compliant NFPA 13 and NFPA fire alarm system to comply with the 5-story wood construction ordinance, allowable area increase, and story increase. **JAR**
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
OVERRIDE  8/12/2020  
Permit Ready to Issue  8/12/2020 DONE
NEED
ACHD
GC
REV VALUES
Plan assigned to (JAR)2/11/20202/11/20208/10/2020 DONE
DetailsJulie Romig
08/06 (5 days) - 3rd Rev - 1st Rev Comp - 506 6th & Grove Multifamily
Routing - PLAN CHECK7/31/2020 8/10/2020 PASS
DetailsJulie Romig
PLANS/APPL TAKEN TO FRONT DESK  8/10/2020 DONE
Routing PW Drainage7/31/2020 8/4/2020 PASS
DetailsBrian Murphy
Routing Off Site - STRUCTURAL7/31/2020 8/4/2020 PASS
DetailsJulie Romig
Jacobs
Routing PW Drainage7/9/2020 7/22/2020 FAIL
need achd stamp
Routing - PLAN CHECK7/9/2020 7/21/2020 FAIL
DetailsJulie Romig
2nd Review
Routing Off Site - STRUCTURAL7/9/2020 7/21/2020 FAIL
DetailsJulie Romig
Routing - FIRE7/9/20207/9/20207/20/2020 PASS
DetailsErika Akin
Attached comments to case
Routing PW Street Lights7/9/2020 7/10/2020 PASS
DetailsTom Marshall
Route to Impact Fee Review4/30/20205/3/20207/9/2020 PASS
DetailsTravis P Black
Review requested for Commercial Permit
Routing - Design Review7/9/2020 7/9/2020 PASS
DetailsJosh Wilson
Plan Reviewer's activity  7/8/2020 DONE
DetailsJulie Romig
Second Building Plan Review not complete. Sent back at applicants request to upload additional response items for other department reviews prior to copmletion of 2nd building review.
Routing - FIRE7/7/20207/7/20207/7/2020 FAIL
DetailsErika Akin
Attached comments to case and emailed architect
Routing PW Drainage7/7/2020 7/7/2020 FAIL
DetailsBrian Murphy
NEED ACHD STAMP FOR DRAINAGE
Routing PW Solid Waste7/7/2020 7/7/2020 PASS
DetailsEvan Carpenter
Building staff must move compactor units to the alley for servicing.
Routing PW Street Lights7/1/2020 7/1/2020 FAIL
DetailsTom Marshall
Routing - PLUMBING7/1/2020 7/1/2020 PASS
DetailsDan Ediger
Per Plans and ISPC
Routing PW Sewer Design7/1/2020 7/1/2020 PASS
DetailsDeAnn Brown
Routing - MECHANICAL6/30/2020 6/30/2020 PASS
DetailsTroy James
Routing - FIRE2/11/20202/11/20205/1/2020 FAIL
DetailsErika Akin
Attached comments and emailed architect
Routing - PLAN CHECK2/11/2020 4/30/2020 FAIL
DetailsJulie Romig
1st review completed  4/30/2020 FAIL
DetailsJulie Romig
Routing Off Site - STRUCTURAL4/16/2020 4/16/2020 PASS
DetailsJulie Romig
Jacobs 3rd Review
Routing Off Site - STRUCTURAL3/20/2020 4/1/2020 FAIL
DetailsJulie Romig
Jacobs - 2nd Rev
Routing - Design Review2/11/2020 2/26/2020 FAIL
DetailsJosh Wilson
Changemarks Sheet C2.00

a. Ramp for the ADA stall should be outside the limits of the parking space in order to maximize ramp deployment area onto the sidewalk.
b. Ramp should not include truncated domes.
c. There should be no above-grade obstructions (street trees, furnishings, light posts, signs or other obstruction) adjacent to the ADA stall
d. Slope of all concrete sidewalk and brick furnishing zone areas adjacent to the ADA stall should be a max of 2.0%
e. Remove parking meter
f. Gutter pan should not be counted in the 5’ width dimension of asphalt access aisle. 5’ aisle should be treated as part of the ped access route, which should have a max cross slope of 2.0% and doesn’t need cross-hatch striping.
g. ADA pavement marking symbol within the stall not needed.
Routing Off Site - STRUCTURAL2/11/2020 2/26/2020 FAIL
DetailsJulie Romig
Jacobs
Routing PW Drainage2/12/2020 2/25/2020 FAIL
DetailsBrian Murphy
NEED ACHD OK
Routing PW Street Lights2/12/2020 2/24/2020 FAIL
DetailsTom Marshall
Routing - PLUMBING2/11/2020 2/20/2020 FAIL
DetailsDan Ediger
See e-plan
Routing - MECHANICAL2/11/2020 2/19/2020 FAIL
DetailsTroy James
Emailed review comment to applicant.
Routing PW Environmental2/12/2020 2/18/2020 PASS
DetailsRick Christenson
Approved with grease waste line and grease interceptor as shown.
Routing - PUBLIC WORKS2/11/2020 2/13/2020 PASS
DetailsCandy A. Nichols
Routing PW Solid Waste2/12/2020 2/13/2020 FAIL
DetailsEvan Carpenter
For an internal trash room with one 3-yard dumpster and a compactor, a 12-foot-wide door is required to the exterior of the building.
Routing PW Sewer Design2/12/2020 2/12/2020 FAIL
DetailsDeAnn Brown
Make changes requested in changemarks on sheet C5.00.
Routing - PLANNING2/11/2020 2/12/2020 PASS
DetailsDavid Moser
See DRH19-00392
Routing - Addressing2/11/2020 2/12/2020 PASS
DetailsDoug Chausow
Routing - Erosion and Sediment2/11/2020 2/11/2020 PASS
DetailsMichael Zawacki
RP needed, site prep required.
SWPPP provided was for prebid, no prime contractor listed.
Intake Approval  2/7/2020 PASS
DetailsCarl D Madsen
Intake Approval  1/30/2020 FAIL
DetailsBrian McGowan
Please address or provide the following for your Prescreen to be approved;
1. Sheet A9.91 with ceiling details was blank, except for a General Note.
2. There are no actual stair sections showing tread, rise, run information.
3. No building sections were on Sheet S3.01, only wall sections.
4. No Sheet was specified for Fire and Damper locations.
5. Water Heater Details were not on Sheets P1.01-07.
6. I could not locate the Stand Pipe Locations on Sheet P1.01.
Application received  1/17/2020 DONE
Application submitted via PDS Online on Jan 17 2020 4:21PM