Permit Information
Permit NumberBLD20-00330
StatusFinaled
Name SEAN CAFFERTY ENTERPRISES
Site Address 3939 S TRANSPORT ST
Project NameTreabar Financial
Customer NumberCZC20-00030
ePlanReviewYes
Description
(TREBAR) Permit is to remodel an existing 6,536 sq. ft. tenant space. **NOTE: ANY FUTURE SUBSTANTIAL TENANT IMPROVEMNTS SHALL REQUIRE THE BUIDING TO BE SEPERATED INTO TWO SEPARATE BUILDINGS AND OR FIRE SPRINKLERED TO BECOME IN COMPLIANCE WITH BUILDING AREA, CURRENTLY BUILDING IS IN NONCOMPLIANCE WITH THE CODE IN EFFECT WHEN THE ADDITIONS WERE BUILT (UNDER THE 1976 UBC AND WITH THE CURRENTS CODES 2015 IBC). SINCE THERE WAS NO CHANGE IN USE OR OCCUPANCY UNDER THIS PERMIT THERE WAS NO TRIGGER TO MAKE BUILDING COMPLY.** Approval is contingent upon adhering to the approved plans on file, attached engineering and plan review report. Work to include: removal of select exterior windows, removal of select exterior wall, removal of select exterior and interior door/door frames, removal of select interior nonbearing walls, removal of select interior stairs and frame infill floor, removal of select plumbing fixtures, removal of Rail-Lift system beam and column, construction of select exterior wall per design, construction of interior non-bearing walls, select exterior and interior wall infill, new door/door frames, new exterior overhead door, new exterior windows, new 1-hour rated exit stairway, new Hi/Lo drinking fountain, new acoustic suspended and gypsum ceiling, three new accessible restrooms, new accessible shower, electrical work, plumbing work, mechanical work and interior finishes in compliance with Ch. 8 of the 2015 IBC. This building is not Fire Sprinklered. **JG**
Contact Information
See Activities list for contact information
Color Key
Current location of plans being reviewed:  
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Print Occupancy Form  8/7/2020 DONE
Permanent Occupancy  8/7/2020 DONE
BLD-Final8/4/20208/4/20208/4/2020PDONE
DetailsJim Storey
*Screened* Bob Phone #: ###-####
BLD-Final8/4/20208/4/20208/4/2020APASS
DetailsJim Storey
final ok
FIRE-Final Inspection8/3/20208/4/20208/4/2020APASS
DetailsJim Page
Previously noted items have been corrected, no fire sprinklers, no fire alarms, duct detectors are stand-alone and functional with annuciators, fire extingiushers are placed with current inspection tags. Final life fire safety inspection complete, signature card not available at time of inspection.

Sean *screened* Phone #: ###-####
FIRE-Final Inspection7/31/20207/31/20207/31/2020PFAIL
DetailsTroy Cobbley
Remove deadbolt at the west door, provide exit discharge light at the south facing door per approved plans, install duct smoke detector per installation guide (narrow side) and provide testing, provide tagged and mounted fire extinguisher up stairs.


SCREENED // Bob Phone #: ###-####
BLD-Energy code compliance5/19/20205/21/20205/21/2020APASS
DetailsJim Storey
screeened / Bob Phone #: ###-####
BLD-Framing/Rough-in5/19/20205/21/20205/21/2020APASS
DetailsJim Storey
screeened / Bob Phone #: ###-####
BLD-Conference5/19/20205/20/20205/20/2020APASS
DetailsJim Storey
screeened / Bob Phone #: ###-####
Print Occupancy Form  4/14/2020 DONE
Issue PAID IN FULL permit  4/13/2020 DONE
Plan assigned to (JG)2/12/20202/12/20204/8/2020 PASS
DetailsJavier Guzman
04/08 2nd rev, L3 TreBar ePlan
Routing - PLAN CHECK3/26/2020 4/8/2020 PASS
DetailsJavier Guzman
PLANS/APPL TAKEN TO FRONT DESK  4/8/2020 DONE
Permit Ready to Issue  4/8/2020 DONE
ALL MET

Need GC
Need Revised Values
Routing Off Site - STRUCTURAL3/26/2020 4/7/2020 PASS
DetailsJavier Guzman
signed off in ePlan by AHJ Engineers
Route to Impact Fee Review3/12/20203/15/20203/13/2020 PASS
DetailsShannon Cade
Review requested for Commercial Permit
Routing - FIRE2/12/20202/12/20203/12/2020 PASS
DetailsErika Akin
No comments attached. The fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems.
1st review completed  3/12/2020 FAIL
DetailsJavier Guzman
Routing - PLAN CHECK2/12/2020 3/12/2020 FAIL
DetailsJavier Guzman
Routing - PLANNING2/12/2020 2/20/2020 PASS
DetailsNicolette Womack
Allowed use, route to DR.
Routing - Design Review2/20/2020 2/20/2020 PASS
DetailsMichaella Owens
Routing - MECHANICAL2/12/2020 2/18/2020 PASS
DetailsChad Schwendiman
Routing - PLUMBING2/12/2020 2/13/2020 PASS
DetailsDaryl Spivey
Per plan and ISPC
Routing - Addressing2/12/2020 2/13/2020 PASS
DetailsDoug Chausow
Routing - PUBLIC WORKS2/12/2020 2/13/2020 PASS
DetailsCandy A. Nichols
DREDIT FOR DEMO
Intake Approval  2/12/2020 PASS
Intake Approval  2/5/2020 FAIL
Application received  2/3/2020 DONE
Application submitted via PDS Online on Feb 3 2020 10:26AM
First Notice 8/17/2020   
Routing - PLANNING3/27/2020   PASS
Allowed use, route to DR.