BLD-Framing/Rough-in | 8/12/2020 | 8/12/2020 | 8/12/2020 | P | NR |
Tell Riley
|
|
|
SCREENED // Greg Phone #: ###-####//used as conference//
|
Issue PAID IN FULL permit | | | 5/12/2020 | | DONE |
|
|
|
|
Inspection Record Card- Bld | | | 5/12/2020 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 5/11/2020 | | DONE |
|
|
|
MET
GC Form
Revised Cert of Value
|
Plan assigned to (JAR) | 3/9/2020 | 3/9/2020 | 5/8/2020 | | DONE |
Julie Romig
|
|
|
05/08 (10 days) - 2nd Rev - 1st Rev Comp - L3 Crescent Rim Condo Remodel
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/8/2020 | | DONE |
|
|
|
|
Routing - PLAN CHECK | 5/8/2020 | | 5/8/2020 | | PASS |
Julie Romig
|
|
|
3rd Review
|
Routing - PLAN CHECK | 4/27/2020 | | 5/7/2020 | | FAIL |
Julie Romig
|
|
|
2nd Rev
|
Route to Impact Fee Review | 4/19/2020 | 4/22/2020 | 4/20/2020 | | PASS |
Shannon Cade
|
|
|
Review requested for Commercial Permit
|
1st review completed | | | 4/19/2020 | | FAIL |
Julie Romig
|
|
|
|
Routing - PLAN CHECK | 3/9/2020 | | 4/19/2020 | | FAIL |
Julie Romig
|
|
|
|
Routing - FIRE | 3/9/2020 | 3/9/2020 | 4/1/2020 | | PASS |
Erika Akin
|
|
|
No comments attached. Modification to the exisiting sprinkler system may be required for the improvements planned. The plans shall be reviewed by a licensed Idaho sprinkler contractor to determine modification necessary to provide required coverage. The sprinkler system shall comply with NFPA 13 and the fire alarm sytem with NFPA 72.Seperate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification on the fire protection systems.
|
Routing - MECHANICAL | 3/9/2020 | | 3/16/2020 | | PASS |
Troy James
|
|
|
Field verify any mechanical work
|
Routing - Addressing | 3/9/2020 | | 3/11/2020 | | PASS |
Doug Chausow
|
|
|
|
Routing - PLUMBING | 3/9/2020 | | 3/10/2020 | | PASS |
Daryl Spivey
|
|
|
|
Routing - PUBLIC WORKS | 3/9/2020 | | 3/9/2020 | | PASS |
Candy A. Nichols
|
|
|
NO NEW FEES
|
Intake Approval | | | 3/5/2020 | | PASS |
Julie Romig
|
|
|
Prescreen passed by JAR.
|
Intake Approval | | | 3/2/2020 | | FAIL |
Julie Romig
|
|
|
2. It appears that there will be penetrations through either the rated party wall or rated horizontal assembly (either above or below) in order to put in the new gas fire place. Provide UL listed penetration details for this and any other new penetrations through the rated walls or rated horizontal assemblies.
3. Wall construction type of new walls (sections/details). Provide UL listed rated assembly where constructing new walls around existing building elements required to be protected for Type VA construction. This includes the columns, which are being exposed. Columns are required to be individually encased. Please provide UL listed assemblies.
|
Intake Approval | | | 2/14/2020 | | FAIL |
Julie Romig
|
|
|
To complete your application, please provide the following:
1. Completed and signed 520 Application (download the PDF application here: https://www.cityofboise.org/departments/planning-and-development-services/building/building-permits/commercial-construction-500/520-major-tenant-improvement/)
2. Identify locations of rated assemblies (building elements, dwelling separation walls, corridor walls, rated horizontal assemblies) on plans. Provide penetration details, wall sections/details, ceiling details, etc showing how the rated assemblies are maintained.
3. Wall construction type of new walls (sections/details). Provide UL listed rated assembly where constructing new walls around existing building elements required to be protected for Type VA construction.
4. Ceiling details showing construction of new ceilings.
5. Door hardware schedule for user passage doors.
6. Address the Type B accessibility requirements showing required clearances in plan and interior elevations.
7. Provide lighting fixture schedule showing compliance with 2015 IECC lighting requirements for multi-family dwelling unit (can comply with either commercial or residential requirements).
Record drawings can be request from Planning & Development Services for reference (ask for BLD06-02322):
https://www.cityofboise.org/departments/finance-and-administration/city-clerk/public-records/public-records-access-research-request/
|
Application received | | | 2/13/2020 | | DONE |
|
|
|
Application submitted via PDS Online on Feb 13 2020 4:33PM
|