BLD-Final | 8/7/2020 | 8/10/2020 | 8/10/2020 | A | PASS |
Jim Storey
|
|
|
Scrrened- Dave Phone #: ###-####
|
DOC - Permit Finaled | 8/10/2020 | 8/10/2020 | 8/10/2020 | P | PASS |
Jim Storey
|
|
|
|
FIRE-Final Inspection | 8/7/2020 | 8/7/2020 | 8/7/2020 | P | PASS |
Jim Page
|
|
|
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extingiushers are placed wtih current inspection tags. Final life fire safety inspection for area of work is comlpete, signatures provided on permit sign off card.
|
Inspection Record Card- Bld | | | 6/11/2020 | | DONE |
|
|
|
|
Issue PAID IN FULL permit | | | 6/10/2020 | | DONE |
|
|
|
|
Telephone call | | | 6/10/2020 | | DONE |
|
|
|
No contact information to send Permit too. Reached out to contractor and applicant and left voice mail
|
Route to Impact Fee Review | 6/5/2020 | 6/8/2020 | 6/8/2020 | | PASS |
Shannon Cade
|
|
|
Review requested for Commercial Permit
|
Routing - FIRE | 6/8/2020 | 6/8/2020 | 6/8/2020 | | PASS |
Greg Ruxton
|
|
|
Attached comments to case.
|
Plan assigned to (CDM) | 6/5/2020 | 6/5/2020 | 6/8/2020 | | PASS |
Carl D Madsen
|
|
|
Norco Fill Plant Paint Booth L-2
|
Routing - Design Review | 6/8/2020 | | 6/8/2020 | | PASS |
Josh Wilson
|
|
|
CZC20-00175
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/8/2020 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 6/8/2020 | | DONE |
|
|
|
MET Ryan Drew
Need GC
Need Revised Value
|
Routing - FIRE | 5/27/2020 | 5/27/2020 | 6/5/2020 | | FAIL |
Greg Ruxton
|
|
|
Attached comments to case and emailed architect.
|
1st review completed | | | 6/5/2020 | | FAIL |
|
|
|
Applicant will provide additional information to upload. CDM
|
Plan assigned to (M_H) | 5/27/2020 | | 6/5/2020 | | DEFR |
Michael Hanson
|
|
|
06/08 L2 Norco Fill Plant-Paint Booth ePlan
|
Routing - PLAN CHECK | 5/27/2020 | | 6/5/2020 | | PASS |
Carl D Madsen
|
|
|
|
Routing - MECHANICAL | 5/27/2020 | | 5/29/2020 | | PASS |
Troy James
|
|
|
|
Routing - PUBLIC WORKS | 5/27/2020 | | 5/29/2020 | | PASS |
Morgan Webb
|
|
|
NO NEW PLUMBING
|
Routing PW Environmental | 5/29/2020 | | 5/29/2020 | | PASS |
Zach Conde
|
|
|
PER ZACH: Passed on ePlan with no comments. Please pass on Tidemark.
|
Routing - Addressing | 5/27/2020 | | 5/28/2020 | | PASS |
Doug Chausow
|
|
|
|
Routing - Design Review | 5/27/2020 | | 5/28/2020 | | FAIL |
Josh Wilson
|
|
|
Design Review approval required for exterior HVAC equipment
|
Intake Approval | | | 5/26/2020 | | PASS |
Javier Guzman
|
|
|
|
Intake Approval | | | 5/21/2020 | | FAIL |
Brian McGowan
|
|
|
PLease provide or address the following for your Prescreen to be approved;
1. No information on the actual paint booth being installed is provided.
2. No structural details were provided for tyhe roof modification, just a letter.
3. No specific information on the fire proofing was provided. What are you using, what rating is required/proposed, special inspections required?
|
Application received | | | 5/14/2020 | | DONE |
|
|
|
Application submitted via PDS Online on May 14 2020 1:52PM
|
First Notice | 8/10/2020 | 8/10/2020 | | | |
Jim Storey
|
|
|
|