INSP - Permanent occupancy | | | 8/12/1996 | | PASS |
|
|
|
Perm. Occ. Cert. #6520 issued 8-9-96 to the L.D.S. Church Meridian 7, 8, & 19 Wards (additions).
|
INSP - Final | 8/9/1996 | 8/9/1996 | 8/9/1996 | | PASS |
Jim Storey
|
|
|
/ / 301 - FNL -OK FINAL
|
Permanent Occupancy | | 8/9/1996 | 8/9/1996 | | DONE |
|
|
|
|
INSP - Fire Dept. Request | 7/30/1996 | 7/30/1996 | 8/1/1996 | | FAIL |
|
|
|
alarm system did not function: no voice evac message, strobes cut out on silence, smoke alarms self clear w/o acknowlegement, would not dial off site. address not visible, sw hall e-lights do not operate when hall lights are disconnected. chk fe size for kitchen.
|
INSP - Final | 7/30/1996 | 7/31/1996 | 7/31/1996 | P | NR |
Jim Storey
|
|
|
07/31/96 301 - OTH-OTHER AGENCIES NOT APPROVED fire dept.
|
(F) Reprint permit | | | 6/11/1996 | | |
|
|
|
|
INSP - Carpentry | 5/13/1996 | 5/13/1996 | 5/13/1996 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - CHK ALL GYP FOR 1HR CONST...OK; NEED FIRESTOPS AS APPROPRIAT
|
INSP - Carpentry | 5/13/1996 | 5/13/1996 | 5/13/1996 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - CHK ALL GYP FOR 1HR CONST...OK; NEED FIRESTOPS AS APPROPRIAT
|
INSP - Carpentry | 5/9/1996 | 5/9/1996 | 5/9/1996 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - CHK GYP AT INFILL, EXT WALLS AT WINDOW REPLACEMENT...OK; MAS AREAS, WIP ,
|
INSP - Conference | 5/7/1996 | 5/7/1996 | 5/7/1996 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - DICUSSED FIRESTOP REQ'S...1HR BLDG
|
INSP - Wall cover | 5/3/1996 | 5/3/1996 | 5/3/1996 | | PART |
Carl Dependahl
|
|
|
/ / 340 - still need 1hr gyp at soffit & entry area west side, also fi protection...lids inside ok
|
INSP - Framing/Rough-in | 4/30/1996 | 4/30/1996 | 4/30/1996 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - 09 OK,CHK FIRE STOP AS NEED ED AT WALL FINISH
|
INSP - Wall cover | 4/29/1996 | 4/30/1996 | 4/30/1996 | A | PART |
Carl Dependahl
|
|
|
04/30/96 340 - NEED FASTENERS AT W. EXT. PER SCHED...2ND LAYER OK AT NEW
|
INSP - Carpentry | 4/29/1996 | 4/29/1996 | 4/29/1996 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - 1ST LAYER LIDS OK, NEED FIRESTOPS AT HVAC
|
INSP - Framing/Rough-in | 4/26/1996 | 4/26/1996 | 4/26/1996 | | PART |
Carl Dependahl
|
|
|
/ / 340 - OK TO COVER, NEED FIRESTOP AT HVAC AT EXT BRG WALL AT E. & W 1ST LAYER GYP AT LID OK
|
INSP - Framing/Rough-in | 4/25/1996 | 4/26/1996 | 4/26/1996 | A | PART |
Carl Dependahl
|
|
|
04/26/96 340 -
|
INSP - Framing/Rough-in | 4/24/1996 | 4/25/1996 | 4/25/1996 | P | PART |
Carl Dependahl
|
|
|
04/25/96 340 - PARTIAL ON S/ENTRY WAY FOYER OK, NEED FIRESTOP AT HVAC THRU BRG WALL
|
INSP - Carpentry | 4/24/1996 | 4/24/1996 | 4/24/1996 | | PART |
Carl Dependahl
|
|
|
/ / 340 - CHK FIRESTOP ABOVE CLG AT FOYER, N SIDE & WEST
|
INSP - Energy code compliance | 4/23/1996 | 4/23/1996 | 4/23/1996 | | PART |
Carl Dependahl
|
|
|
/ / 340 - INSUL INSTALLED AT EXT WALLS, NEW AREAS,OK
|
INSP - Framing/Rough-in | 4/22/1996 | 4/23/1996 | 4/23/1996 | A | PART |
Carl Dependahl
|
|
|
/ / 340 - OK TO COVER EXCEPT SO. ENTRY AND MAIN CORRID
|
INSP - Framing/Rough-in | 4/19/1996 | 4/22/1996 | 4/22/1996 | A | PART |
Carl Dependahl
|
|
|
04/19/96 340 - KEEP C/N; OK TO COVER PERIMETER CLASSROOMS & SMALL RMS OF S.) ONLY. NEED ENG'S OK FOR STAPLE SUBSTITUTION & STAMP ON LETTERS
|
INSP - Framing/Rough-in | 4/18/1996 | 4/18/1996 | 4/18/1996 | P | FAIL |
Carl Dependahl
|
|
|
04/18/96 340 - PM...KEEP C/N, CHK FIRESTOPS,VOIDS AT 1HR LID,GYP ATTACHM OK TO INSULATE WEST PORTIONS & REMODELED WINDOW AREAS
|
INSP - Framing/Rough-in | 4/16/1996 | 4/17/1996 | 4/17/1996 | P | NR |
Carl Dependahl
|
|
|
04/17/96 340 - NEED DETAIL PER C/N
|
INSP - Conference | 4/12/1996 | 4/15/1996 | 4/15/1996 | A | PASS |
Carl Dependahl
|
|
|
04/12/96 340 - 9 a.m. appointment MET W/ STEVE SIMMONS, LOMBARD CONRAD ARCH'S RE DETAILS FOR 1HR ASSY'S... WILL HAVE STAPELY ENG'S' SUBMIT FOR EXISTING FRAMING, ARCH. FOR FULL HT WALLS AT EXT & FIRESTOPPING
|
INSP - Framing/Rough-in | 4/10/1996 | 4/10/1996 | 4/15/1996 | P | FAIL |
Carl Dependahl
|
|
|
04/10/96 340 - CN, NEED ARCH'S DETAIL, FIRESTPPING\
|
INSP - Conference | 4/8/1996 | 4/8/1996 | 4/8/1996 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - NEED 5/8'' GYP BOTH SIDES WALL AT ALL NEW CONST PER DETAIL O
|
INSP - Conference | 4/2/1996 | 4/2/1996 | 4/2/1996 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - observe plan notes & resubmittal re 1hr const w/ Kim, supt.
|
INSP - Carpentry | 3/14/1996 | 3/14/1996 | 3/14/1996 | | FAIL |
Carl Dependahl
|
|
|
/ / 340 -
|
INSP - Foundation | 3/5/1996 | 3/6/1996 | 3/6/1996 | A | PART |
Carl Dependahl
|
|
|
03/06/96 340 - LATE A.M.
|
INSP - Conference | 3/6/1996 | 3/6/1996 | 3/6/1996 | | PASS |
Carl Dependahl
|
|
|
/ / 340 -
|
INSP - Footings | 3/1/1996 | 3/1/1996 | 3/1/1996 | P | PART |
Carl Dependahl
|
|
|
03/01/96 340 -
|
INSP - Foundation | 3/1/1996 | 3/1/1996 | 3/1/1996 | | PART |
Carl Dependahl
|
|
|
/ / 340 -
|
INSP - Footings | 2/26/1996 | 2/27/1996 | 2/27/1996 | A | PART |
Carl Dependahl
|
|
|
02/26/96 340 - FOOTING REBAR
|
INSP - Footings | 2/26/1996 | 2/26/1996 | 2/26/1996 | | PART |
Carl Dependahl
|
|
|
/ / 340 -
|
INSP - Footings | 2/20/1996 | 2/20/1996 | 2/20/1996 | P | PART |
Carl Dependahl
|
|
|
02/20/96 340 - LATE PM
|
Issue PAID IN FULL permit | | | 2/2/1996 | | |
|
|
|
|
Inspection Record Card- Bld | | | 1/30/1996 | | |
|
|
|
|
Permit taken to Permit Desk | | | 1/30/1996 | | PASS |
|
|
|
|
Plan Received by (JCM) | 12/6/1995 | | 1/30/1996 | | PASS |
John Menard
|
|
|
01/30/96 14:34:54 JCM - this action updated by action script from <<>> in Case No. BLD95-2101
|
Routing Off Site - A.C.H.D | 1/22/1996 | | 1/24/1996 | | PASS |
|
|
|
IMPACT FEES PAID 01/24/96 - CERT. #96-0085.
|
Plan resubmittals received | | | 1/12/1996 | | PASS |
|
|
|
PLAN RESUBMITTALS RECEIVED AND REVIEWED 01/12/96 - APPROVAL FOR ONE ACCESSIBLE ENTRY RECEIVED FROM TIM HOGLAND 01/30/96.
|
Routing - FIRE | 12/8/1995 | | 12/21/1995 | | PASS |
|
|
|
|
Plan resubmittals requested | | | 12/8/1995 | | PEND |
|
|
|
PRELIMINARY PLAN REVIEW COMPLETED AND CORRECTION LIST SENT TO STEVE SIMMONS AT LOMBARD-CONRAD.
|
Unassigned to Plan Reviewer | 11/16/1995 | | 12/6/1995 | | PASS |
|
|
|
12/06/95 14:46:24 JCM - this action updated by action script from <<>> in Case No. BLD95-2101
|
Routing - MECHANICAL | 11/22/1995 | | 11/29/1995 | | PASS |
|
|
|
|
Routing - PLUMBING | 11/21/1995 | | 11/28/1995 | | PASS |
|
|
|
|
Routing - PLANNING | 11/21/1995 | | 11/21/1995 | | PASS |
|
|
|
|
Routing - PUBLIC WORKS | 11/17/1995 | | 11/21/1995 | | PASS |
|
|
|
|
Plan routing begun/NEW & ADDTN | | | 11/17/1995 | | PASS |
|
|
|
|
Application received | | | 11/16/1995 | | PASS |
|
|
|
|
Received Certificate of Value | | | 11/16/1995 | | PASS |
|
|
|
|
Routing - BUILDING | 1/24/1996 | | | | |
|
|
|
|
Routing - BUILDING | 12/1/1995 | | | | PEND |
|
|
|
|
Routing - BUILDING | 12/21/1995 | | | | |
|
|
|
|