Permit Information
Permit NumberBLD96-00002
StatusFinaled
Name MICRON TECH
Site Address 8000 S FEDERAL WAY
Project NameMIC #17C (INT. FIN.)
Customer Number 
ePlanReviewNo
Description
(MICRON BLDG. #17C) (CP-8) (BUILDING INTERIOR FINISH) THIS PERMIT IS TO DO THE INTERIOR FINISH ON A 247,959 SQ. FT., FOUR STORY OFFICE ADDITION TO THE EXISTING 79,910 SQ. FT., THREE STORY ADMINISTRATIVE BUILDING #17. THE NEW ADDITION IS BEING SEPARATED FROM THE EXISTING BUILDING BY A FOUR-HOUR AREA SEPARATION WALL. THIS BUILDING PERMIT INCLUDES ALL INTERIOR FINISH CONSTRUCTION, AS WELL AS, CONSTRUCTION OF A 1400 SQ. FT. COVERED ENTRY, AND A BRIDGE LINK BETWEEN BUILDING #17C AND EXISTING BUILDING #1 (FAB 1) AND A GROUND LINK BETWEEN BUILDINGS #17C AND EXISTING BUILDING #2 (TA 1). THIS PERMIT INCLUDES ALL INTERIOR FINISHES AND IMPROVEMENTS APPROVED UNDER THE CP-8 PORTION OF THIS PROJECT. THIS BUILDING ADDITION INCLUDES GENERAL OFFICE SPACE, A "CAFETORIUM" AND AN AUDIO-VISUAL PRODUCTION STUDIO. THE FOURTH FLOOR IS NOT BEING FINISHED UNDER THIS PERMIT. ALL CONSTRUCTION PER THE APPROVED PLANS AND ATTACHED REQUIREMENT LIST. PC#829-95/JCM
Contact Information
See Activities list for contact information
Color Key
Current location of plans being reviewed:  
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Permanent occupancy  2/8/2000 DONE
Perm. Occ. Cert. #8127 issued 2-8-00 to Micron Technology.
Permanent Occupancy 2/3/20002/3/2000 DONE
Details
CHANGE STATUS TO (TMP)  10/29/1999 DONE
INSP-Final Inspection8/31/19999/1/19999/1/1999AFAIL
DetailsRick Jackson
smoke gaurd test for second elevator; third floor door track problems
INSP - Wall cover8/6/19998/6/19998/6/1999PPASS
DetailsJim Storey
08/06/99 301 - ceilling ok for cover 3hird floor north end
Temporary occupancy  7/27/1999 PASS
temp issued to linda (gc)-issued 7/27/99-temp occ #3877
INSP-Final Inspection7/21/19997/22/19997/22/1999PPASS
DetailsRick Jackson
Ron Young 1:30 occ approved
INSP - Final7/21/19997/22/19997/22/1999PPASS
DetailsJim Storey
07/22/99 301 - final ok pending bond release for code enforcment out sid
INSP - Final7/21/19997/21/19997/21/1999PPART
DetailsJim Storey
07/21/99 301 - Rob ###-####
INSP-Final Inspection7/21/19997/21/19997/21/1999PPART
DetailsRick Jackson
Rob ###-#### okay to occupy offices at north corridor
INSP - Final7/1/19997/2/19997/2/1999PNH
DetailsJim Storey
07/02/99 301 - fire fail no insp performed
INSP - Framing/Rough-in6/28/19996/28/19996/29/1999PPASS
DetailsJim Storey
06/28/99 301 - ceiling Rob ###-####
INSP-Final Inspection6/21/19996/22/19996/22/1999PPART
DetailsRick Jackson
AROUND 2:00 IF POSSIBLE RON ###-#### final inspection to use cafetorium for special events - okay to use
INSP - Final6/21/19996/22/19996/22/1999PPART
DetailsJim Storey
06/22/99 301 - a2.1 ok pending kitchen seprated from and not operational
INSP - Final6/17/19996/18/19996/18/1999PFAIL
DetailsJim Storey
06/18/99 301 - ###-####
INSP-Final Inspection6/17/19996/18/19996/18/1999PPART
DetailsRick Jackson
###-#### cafetorium okay to use for special event
INSP-Final Inspection6/11/19996/15/19996/15/1999AFAIL
DetailsRick Jackson
10 am on the 15th Joe ###-#### Coiling Doors c/n issued for cafetorium and kitchen areas
INSP-Alarm Testing6/14/19996/14/19996/14/1999PPART
DetailsRick Jackson
Rob ###-#### audible okay in cafetorium
Code Occupancy Approval  6/14/1999
Final requested by Joe Taraf ###-#### Mobile.
INSP - Framing/Rough-in6/8/19996/9/19996/9/1999APASS
DetailsJim Storey
06/09/99 301 - ###-#### JOE//CAFETERIA CEILING
INSP-Final Inspection6/8/19996/8/19996/8/1999PFAIL
DetailsRick Jackson
###-#### JOE//CAFETERIA FINAL SPRINKLERS 3:00 PLEASE heads within 6 feet in kitchen area
INSP - Framing/Rough-in6/7/19996/8/19996/8/1999PPASS
DetailsJim Storey
06/08/99 301 - ceilling ok for cover calfatearia and kitchen
Routing - FIRE6/2/1999 6/8/1999 PASS
FED EXED SHEETS B2.1A, B2.1B, B2.2A, B2.2B, B5.1. WAS ONLY GIVEN ONE COPY TO FED EX. THE PLANS WERE NOT SIGNED. KMM PLANS ARE 1ST FLOOR AND 2ND FLOOR - JWA
INSP - Framing/Rough-in5/25/19995/25/19995/25/1999PPART
DetailsJim Storey
05/25/99 301 - ceiling grid at cafeteria joe ###-####
SUPER- Supervisor's review5/24/19995/24/19995/24/1999
all corrections made on ceiling ok
SUPER- Supervisor's review5/18/19995/18/19995/18/1999
corrections to ceiling grid made ok
SUPER- Supervisor's review5/7/19995/7/19995/7/1999
reviewd ceiling suspension system and location of pods. ok
INSP-Final Inspection5/4/19995/5/19995/4/1999PPART
DetailsRick Jackson
Rob ###-#### okay to use ground link only
INSP-Final Inspection5/3/19995/4/19995/4/1999AFAIL
DetailsRick Jackson
###-#### ROB//FINAL FIRE #17C sprinklers not complete in the ground link
INSP - Final5/3/19995/4/19995/4/1999PNR
DetailsJim Storey
05/04/99 301 - ###-#### ROB//FINAL #17C
INSP - Final4/29/19994/30/19994/30/1999APART
DetailsJim Storey
04/30/99 301 - vending area/ Joe ###-#### ceilling ok
INSP - Framing/Rough-in4/27/19994/29/19994/30/1999APASS
DetailsJim Storey
04/29/99 301 - ceiling/ Joe ###-####
INSP - Final4/23/19994/26/19994/26/1999PPART
DetailsJim Storey
04/26/99 301 - conf. only
Plan resubmittals received  4/13/1999 PEND
Received plan resubmittals from Micron, David White, forwarded same to Jim Storey. DAR 4/13/99
INSP-Final Inspection4/7/19994/7/19994/7/1999APART
DetailsRick Jackson
occ approved for office on 2nd floor southwest corner - rooms 217 A/B/C only. special letter used for this occupancy
INSP - Final4/2/19994/6/19994/6/1999PPART
DetailsJim Storey
04/06/99 301 - 2nd floor rm# 217 a,b,c ok for temp occ. pending fire and
INSP-Final Inspection4/2/19994/6/19994/6/1999AFAIL
DetailsRick Jackson
###-#### JAY 99524MICRON PGR//FINAL FIRE BLD 17C 2ND FLR rated 1 hr corridor not complete; damper problems; alarm not installed in mechanical room
INSP - Wall cover3/31/19993/31/19993/31/1999 PASS
DetailsJim Storey
/ / 301 - FIRE PROOFING OK PENDING SPECIAL INSP REPORT FO CALFATRIA.
INSP - Final3/29/19993/30/19993/30/1999PFAIL
DetailsJim Storey
03/30/99 301 - ###-#### JAY//PART FINAL 17C 2ND FLR
Fee Review-notes11/2/1998 3/23/1999
INSP - Framing/Rough-in3/9/19993/9/19993/9/1999 NR
DetailsJim Storey
03/03/99 301 - fire proofing must be re applied w/special insp.
INSP - Framing/Rough-in2/8/19992/8/19992/8/1999PFAIL
DetailsJim Storey
02/08/99 301 - n/r for insp. recall
INSP-Conference2/8/19992/8/19992/8/1999PPART
DetailsRick Jackson
walk thru of cafeteria and penthouse areas with 301
INSP-Conference2/3/19992/4/19992/4/1999APART
DetailsRick Jackson
ROB ###-#### reviewed voice evac plans for cafeteria - need voltage/ battery calcs; cut sheets; strobe candela info; vending and smoking area notification
INSP - Framing/Rough-in1/21/19991/25/19991/25/1999APART
DetailsJim Storey
01/25/99 301 - 4 th floor 2 hr shaft ceilling assembly ok
INSP - Framing/Rough-in1/19/19991/20/19991/20/1999PPART
DetailsJim Storey
01/20/99 301 - rob- ###-#### consoltation insp
INSP - Wall cover1/12/19991/12/19991/13/1999PPART
DetailsJim Storey
01/12/99 301 - FRAM-OK FRAMING forth floor 2 hr ceilling applaction of s
INSP - Framing/Rough-in1/8/19991/11/19991/12/1999PNR
DetailsJim Storey
01/11/99 301 - ROB ###-####
INSP - Final12/10/199812/11/199812/11/1998APART
DetailsJim Storey
12/11/98 301 - temp occ approved for area on file 1st floor ok
INSP - Final12/4/199812/9/199812/9/1998AFAIL
DetailsJim Storey
12/09/98 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
INSP-Final Inspection12/4/199812/9/199812/9/1998APART
DetailsRick Jackson
rob ###-#### fn fire insp temp occ approved per areas indicated on letter dated Sept 15 from Micron
INSP - Framing/Rough-in12/7/199812/8/199812/8/1998APART
DetailsJim Storey
12/08/98 301 - bottom of shaft above kitchen ok shaft wall/
INSP - Final11/18/199811/20/199811/20/1998APART
DetailsJim Storey
11/20/98 301 - tenp ok for first floor area as noted on the master plan
INSP-Final Inspection11/18/199811/20/199811/20/1998APART
DetailsRick Jackson
ROB...###-#### occ approved for "Benefits" area only
INSP-Final Inspection11/17/199811/17/199811/17/1998PFAIL
DetailsRick Jackson
final inspection for the Benefits occupancy failed. 3 dampers not working or blocked by obstructions; need to test the alarms for the first floor
INSP - Final11/10/199811/13/199811/13/1998APART
DetailsJim Storey
11/13/98 301 - temp occ of 2nd floor north west office area as highlight
INSP-Final Inspection11/10/199811/13/199811/13/1998APART
DetailsRick Jackson
ROB ###-#### FN FIRE INSP tested alarms for 2nd floor bullpen area (room 208 area). okay to occupy
INSP-Final Inspection11/9/199811/12/199811/12/1998AFAIL
DetailsJim Storey
11/12/98 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED this was only
INSP - Final11/10/199811/10/199811/10/1998 FAIL
DetailsJim Storey
10/29/98 301 - n/r
INSP - Final11/9/199811/10/199811/10/1998AFAIL
DetailsRick Jackson
JOE ###-#### all items from previous correction notice not complete
INSP - Final11/5/199811/9/199811/9/1998PFAIL
DetailsJim Storey
11/09/98 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
INSP-Final Inspection11/5/199811/9/199811/9/1998PFAIL
DetailsRick Jackson
ROB ###-#### test alarms, exit sign needed at hall per plans
INSP-Final Inspection10/7/199810/22/199810/22/1998AFAIL
DetailsRick Jackson
DICK ###-#### alarms not complete
INSP-Conference10/21/199810/21/199810/21/1998PPART
DetailsRick Jackson
discussed requirements for the use of cafetorium with Jim Storey and contractors
INSP-Final Inspection11/10/199811/12/199810/12/1998AFAIL
DetailsRick Jackson
items from previous c/n not complete
INSP - Framing/Rough-in10/6/199810/7/199810/7/1998PPASS
DetailsJim Storey
10/07/98 301 - rob ###-#### cover inspec FRAM-OK FRAMING
INSP - Final10/2/199810/2/199810/5/1998PFAIL
DetailsJim Storey
10/02/98 301 - remainder 1st floor joe ###-#### CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
SUPER- Supervisor's review10/2/199810/1/199810/1/1998
special inspection reports and documentation for archiving reviewed. need for future completion of the job
INSP-Conference9/29/19989/29/19989/29/1998PPART
DetailsRick Jackson
discussed c/n issued to open first floor areas; alarm problems addressed
INSP - Framing/Rough-in9/28/19989/29/19989/29/1998APASS
DetailsJim Storey
09/29/98 301 - bob ###-#### ceiling grid SCLG-OK SUSPENDED CEILING
INSP-Conference9/22/19989/22/19989/22/1998APART
DetailsRick Jackson
issued c/n and reviewed with Dick Singer. tunnel required for exiting in areas they want to occupy per letter.
INSP-Final Inspection9/21/19989/21/19989/21/1998PFAIL
DetailsRick Jackson
requested occ for 1st floor per letter from Ron Young. strobes not correct, sprinkler problems, alarm testing required, signs in stair towers, detection in corridors, check dampers, c/n issed (3 pages)
INSP - Wall cover9/17/19989/17/19989/17/1998 PART
DetailsJim Storey
/ / 301 - small hood duct rap ok first layer.
INSP - Framing/Rough-in9/14/19989/14/19989/14/1998 PASS
DetailsJim Storey
/ / 301 - fire proofing patch on beams ok
INSP - Wall cover9/10/19989/14/19989/14/1998ACANC
DetailsRuss Owen
09/14/98 407 - trans to 301
INSP - Framing/Rough-in8/14/19988/17/19988/18/1998APART
DetailsJim Storey
08/17/98 301 - rob ###-#### cell ###-#### CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
INSP - Framing/Rough-in7/8/19987/9/19987/9/1998APART
DetailsJim Storey
07/09/98 301 - ceiling bld#17c/ bill ###-#### CORR-CORREC-CALL FOR REINSP WHEN COMPLETED pending mech.
INSP - Final6/25/19986/26/19986/26/1998APART
DetailsJim Storey
06/26/98 301 - dick ###-#### set for arround noon per you. bld 17 c
INSP - Final6/22/19986/24/19986/24/1998PFAIL
DetailsJim Storey
06/24/98 301 - Lobby area Joe Taras ###-####
INSP-Conference6/1/19986/2/19986/2/1998APASS
DetailsJim Storey
06/02/98 301 - agreed to plan and matrix document for tco as we progess.
INSP-Conference5/7/19985/8/19985/8/1998APASS
DetailsJim Storey
05/08/98 301 - reviewed sch. for first floor rm. and coridor temp occ. o
INSP - Foundation4/29/19985/4/19985/4/1998AFAIL
DetailsJim Storey
05/04/98 301 - wrong insp requisted
INSP - Framing/Rough-in4/27/19984/30/19984/30/1998ACANC
Details
04/30/98 333 - rescheduled for mon
INSP - Framing/Rough-in4/27/19984/28/19984/28/1998APART
DetailsJim Storey
04/28/98 301 - GEN -GENERAL INSPECTION review of fire stopping method of
INSP-Sprinkler Rough-in/Hydro4/16/19984/17/19984/17/1998APART
DetailsRick Jackson
MICRON #17--PARTIAL FINAL ON ROOMS 1170,1189,1192--JOE ###-#### okay to cover. not approved for occ. need alarm system installed
INSP - Framing/Rough-in4/15/19984/17/19984/17/1998AFAIL
DetailsJim Storey
04/17/98 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED list of c/n to
INSP-Final Inspection3/23/19983/24/19983/24/1998APART
DetailsRick Jackson
###-#### joe libray training room temp occ approved. spacing of strobes in training rooms incorrect.
INSP - Framing/Rough-in3/23/19983/23/19983/23/1998PFAIL
DetailsJim Storey
03/23/98 301 - REINSP ON LIBRARY--JOE ###-#### pending fire stopping and smoke seal/ele and fire insp.
INSP - Framing/Rough-in3/19/19983/19/19983/20/1998PFAIL
DetailsJim Storey
03/20/98 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
INSP - Conference3/12/19983/12/19983/12/1998 PART
DetailsJim Storey
/ / 301 - resubmital c/n transmital delived back to H.R. for revisions
INSP - Framing/Rough-in2/23/19982/24/19982/24/1998PFAIL
DetailsJim Storey
02/24/98 301 - SCHEDULED FOR 2:00 WITH DLIGHTFOOT--JOHN PAGER ###-####-B submitals required.
INSP - Conference2/5/19982/5/19982/5/1998 FAIL
DetailsJim Storey
/ / 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED kitchen/hood/2hrwrap/shaft an finshed ceilling elv. rfi for design review two copies requsted.
INSP - Framing/Rough-in1/14/19981/15/19981/15/1998AFAIL
DetailsJim Storey
01/14/98 301 - BLDG #17C--CONTACT BILL AT ###-#### CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
INSP - Framing/Rough-in1/9/19981/9/19981/12/1998PPART
DetailsJim Storey
01/09/98 301 - FIRE DAMPER AT BRIDGE LINK--CALL JOE AT ###-#### NWP -GENERAL INSPECTION - NO WORK IN PROGRESS danper to be instaled
INSP - Framing/Rough-in12/31/199712/31/199712/31/1997PPASS
DetailsJim Storey
12/31/97 301 - BLGD 17C ENTERY LOBBY LID ok for cover
INSP-Alarm Testing11/19/199711/19/199711/19/1997APART
DetailsRick Jackson
tested duct detectors for air handlers - passed. tested smoke detectors in 2nd floor corridor, smoke dampers operated - passed. tested strobes/alarms in 2nd floor bullpen - passed.
INSP - Partial final11/17/199711/17/199711/17/1997 PASS
DetailsJim Storey
11/14/97 301 - 2ND FLOOR ok for temp occ. of defined area attched to occ
INSP-Final Inspection11/13/199711/14/199711/14/1997APART
DetailsRick Jackson
MIC #17C tested alarms for 2nd floor. temp/occ approved for second floor only
INSP - Framing/Rough-in11/10/199711/12/199711/12/1997AFAIL
DetailsJim Storey
11/12/97 301 - CEILING BLD 17C CFRM-OK CEILING FRAMING
INSP-Sprinkler Rough-in/Hydro11/10/199711/12/199711/12/1997PPART
DetailsRick Jackson
BLD 17C tested flow/tampers passed
INSP-Sprinkler Rough-in/Hydro11/5/199711/7/199711/7/1997PPASS
DetailsRick Jackson
hydro pass for 3rd and 4th floors.
INSP - Framing/Rough-in11/5/199711/6/199711/7/1997AFAIL
DetailsJim Storey
11/06/97 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
INSP - Framing/Rough-in10/28/199710/29/199710/29/1997APART
DetailsJim Storey
10/29/97 301 - 2nd floor work inprogess fire stopping and patching of fi
INSP - Framing/Rough-in10/22/199710/22/199710/23/1997PFAIL
DetailsJim Storey
10/22/97 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED fire proofing, membrane penatrations, light support wires, shaft wall bottom completion, coridor assembley at corner colum wrap
INSP - Framing/Rough-in10/8/199710/9/199710/9/1997AFAIL
DetailsJim Storey
10/09/97 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
INSP - Wall cover10/3/199710/3/199710/3/1997 FAIL
DetailsJim Storey
/ / 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED OCC.SEP. AND AREA SEPTRATION FLOOR STAIR ANGLE IRON .
INSP-Supply line flush9/25/19979/26/19979/26/1997APASS
DetailsRick Jackson
INSP-Sprinkler Rough-in/Hydro9/25/19979/26/19979/26/1997APASS
DetailsRick Jackson
INSP - Framing/Rough-in9/22/19979/23/19979/23/1997AFAIL
DetailsJim Storey
09/23/97 301 - MIC 17C CORR-CORREC-CALL FOR REINSP WHEN COMPLETED 2hr horizontal exit plumbing walls and membrane not to bottom of floor/ceilling.
INSP - Framing/Rough-in9/15/19979/18/19979/19/1997PCANC
DetailsJim Storey
09/18/97 301 - mic #17c dominic ###-####
INSP - Framing/Rough-in9/15/19979/16/19979/16/1997PPASS
DetailsJim Storey
09/16/97 301 - mic #17c-dominic-###-####- GWB -OK SHEETROCK NAILING 4 hr wall ok
INSP - Conference9/9/19979/9/19979/9/1997APART
DetailsJim Storey
09/09/97 301 - GEN -GENERAL INSPECTION will come back tomarow.
INSP - Framing/Rough-in8/14/19978/15/19978/15/1997APART
DetailsJim Storey
08/15/97 301 - recieved submital for oversized rated wall penatrations f 2nd floor inprogess one side gyp ok screw sch. to be reinsp.
INSP - Framing/Rough-in8/4/19978/6/19978/6/1997APART
DetailsJim Storey
08/06/97 301 - area septration wall at ele room in progess first layer g progess.
INSP-Conference7/30/19977/31/19977/31/1997PPASS
Details
JERRY HINES, MIKE BUTTE. ADVISED THEM THAT ALARMS WERE NOT MANDATORY FOR TEMP, PARTIAL OCCUPANCY. IF DEVICES ARE INSTALLED THEY MUST BE TO CODE. ALL AREAS MUST HAVE SPRINKLER COVERAGE
INSP - Framing/Rough-in7/17/19977/18/19977/18/1997APASS
DetailsJim Storey
07/18/97 301 - infill of gyp at windows at 17-b outside shell framing an first and 2nd where area assembly is to start.
INSP - Framing/Rough-in7/7/19977/8/19977/8/1997ACANC
DetailsRuss Owen
07/08/97 407 - MIC 17C CONTACT JERRY HINE ###-#### TRAN TO 301
INSP - Conference6/25/19976/26/19976/26/1997PPART
DetailsJim Storey
06/26/97 301 - 2 P.M. ok
INSP - Framing/Rough-in6/19/19976/19/19976/19/1997PPART
DetailsJim Storey
06/19/97 301 - GEN -GENERAL INSPECTION
INSP - Conference6/16/19976/16/19976/16/1997 PASS
DetailsJim Storey
/ / 301 - TYPE II FR OK
Issue FEE-WAIVED permit  9/4/1996
Plan Received by (JCM)1/8/1996 8/20/1996 PASS
DetailsJohn Menard
08/20/96 13:05:19 JCM - this action updated by action script from <<>> in Case No. BLD96-0002
(F) Reprint permit  8/20/1996
Print Occupancy Form  8/20/1996
Inspection Record Card- Bld  8/20/1996
Permit taken to Permit Desk  8/20/1996 PASS
Plan resubmittals received  8/19/1996 PASS
FINAL PLAN CORRECTIONS AND ADDITIONAL REQUEATED INFORMATION RECEIVED AND APPROVED.
Plan resubmittals requested  8/12/1996 PEND
FINAL CORRECTIONS REQUESTED TO FINISH PLAN REVIEW.
Plan resubmittals received  7/26/1996 PEND
PLAN RESUBMITTALS RECEIVED FROM JACOB-SIRRINE.
Plan resubmittals requested  6/20/1996 PEND
RESUBMITTALS REQUESTED FOR FINAL PLAN RESUBMITTALS.
Plan resubmittals received  6/3/1996 PEND
PLAN RESUBMITTALS RECEIVED FROM JACOB-SIRRINE.
Meeting  5/20/1996
A BOARD OF APPEALS HEARING WAS HELD TO APPEAL THE CITY'S REQUIREMENT FOR EXITING FROM THE SMOKING AREA OF THE CAFETORIUM. THE BOARD FOUND IN FAVOR OF THE CITY'S INTERPRETATION.
Plan resubmittals requested  5/3/1996 PEND
SENT ROD MERRICK A RESPONSE AND CORRECTION LETTER BASED ON THE RESPONSE LETTER RECEIVED FROM JACOB-SIRRINE, DATED 04/17/96. I ALSO INDICATED THAT REVISED PLANS WERE REQUIRED.
Meeting  4/23/1996
MEETING W/ J. MENARD, AND D. MILLER OF CITY, L. ARENA, R. HELSER & G. DAILY OF JSE, AND F. KVAPIL OF MICRON MET TO DISCUSS FIRE DAMPERS, STAIR ENCLOSURE CONSTRUCTION AND STANDPIPE REQUIREMENTS.
Routing Off Site - C.D.H4/11/1996 4/17/1996 PASS
CONTACTED ROGER HELSER AT ###-####, FOR CDH PICKUP.
Plan resubmittals received  4/17/1996 PEND
RECEIVED RESPONSE LETTER FROM ARCHITECT, NO REVISED PLANS, FOR THE PLAN REVIEW CORRECTION LIST SENT 04/04/96.
Routing - FIRE4/8/1996 4/11/1996 PASS
Plan resubmittals requested  4/4/1996 PEND
CORRECTION LIST WAS SENT TO ROGER HELSER AT JACOBS-SIRRINE ON 04/04/96, P.M.. COPIES OF THE PLANS REVIEW CORRECTION LIST WERE SENT TO FRANK KVAPIL AT MICRON AND MICRON CONSTRUCTION.
Plan resubmittals requested  4/4/1996 PEND
PLAN REVIEW CORRECTION LIST BASED ON NEW TYPE II-FR CONSTRUCTION SENT TO ARCHITECT FOR PLAN REVISIONS.
Unassigned to Plan Reviewer12/29/1995 4/4/1996 PASS
04/04/96 16:33:49 JCM - this action updated by action script from <<>> in Case No. BLD96-0002
Plan resubmittals received  3/14/1996 PEND
PLANS WERE RECEIVED FOR REVIEW OF THE PLANS AFTER THEY WERE REVISED TO REFLECT THE NEW TYPE II-FR CONSTRUCTION. THE PLANS THAT WERE SUBMITTED WERE NOT SIGNED BY THE ARCHITECT OF RECORD. ROGER HELSER CAME TO THE CITY OFFICES AND SIGNED THE PLANS 03/21/96.
Plan resubmittals received  3/13/1996 PEND
AFTER SEVERAL MEETINGS AND TELEPHONE CONVERSATIONS IT WAS DETERMINED AND AGREED THAT THIS BUILDING SHOULD BE REDESIGNED TO COMPLY WITH TYPE II-FR CONSTRUCTIONS. NEW II-FR PLANS WERE SUBMITTED FOR REVIEW THIS DATE.
Routing - PLUMBING2/27/1996 3/4/1996 PASS
Meeting  3/1/1996 PEND
MEETING HELD WITH RGG & JCM FROM PLAN CHECK AND ROD MERRICK AND ROGER HELSER OF JSE TO DISCUSS EXITING QUESTIONS AND CHANGES BASED ON CHANGE OF CONSTRUCTION TYPE.
Routing - MECHANICAL2/22/1996 2/27/1996 PASS
Meeting  2/14/1996 PEND
MEETING HELD WITH RGG & JCM OF PLAN CHECK AND ROD MERRICK AND ROGER HELSER OF JSE TO VERIFY CHANGE OF CONSTRUCITON TYPE FOR THE BUILDING FROM TYPE II-ONE-HOUR TO TYPE II-FR AND TO DISCUSS SOME OF THE DETAILS REQUIRED FOR THE NEW CONSTRUCTION TYPE.
Meeting  2/9/1996 PEND
A MEETING WITH RGG & JCM OF CITY PLAN CHECK AND ROD MERRICK AND ROGER HELSER OF JACOBS-SIRRINE WAS HELD TO DISCUSS RGG'S LETTER ON AREAS OF CONCERN DATED 01/01/96 AND ARCHITECTS RESPONSE LETTER DATED 01/31/96.
Plan resubmittals received  1/31/1996 PEND
RESPONSE LETTER FROM ROD MERRICK, PROJECT ARCHITECT FOR JACOB -SIRRINE. NO REVISED PLANS WERE SENT WITH THIS RESPONSE LETTER.
Plan Reviewer's activity  1/2/1996 PEND
BOB GARRISON SENT A LETTER TO THE ARCHITECT OUTLINING AREAS OF CONCERN ON THE ORIGINAL PLANS SUBMITTED.
Plan routing begun/NEW & ADDTN  1/2/1996 PASS
Waiting for Cert. of Value  1/2/1996 PEND
Application received  12/29/1995
Plan resubmittals requested  12/28/1995 PEND
INITIAL PLAN REVIEW COMMENTS FROM BOB GARRISON.
Routing - BUILDING4/17/1996   PEND
SUPER- Supervisor's review5/27/1999  
Routing - PLANNING4/13/1999  
Routing - BUILDING1/2/1996   PEND