Permanent Occupancy | | 3/26/1997 | 3/26/1997 | | DONE |
|
|
|
|
Permanent occupancy | | | 3/26/1997 | | PASS |
|
|
|
Perm. Occ. Cert. #6816 issued 3-26-97 to St. Al's Regional Medical Center for the library.
|
INSP - Final | 3/16/1997 | 3/16/1997 | 3/16/1997 | | PASS |
|
|
|
/ / 338 - made ok all signoffs ok FNL -OK FINAL
|
INSP - Final | 3/12/1997 | 3/12/1997 | 3/11/1997 | P | PART |
|
|
|
03/12/97 338 - LIBRARY - 2ND FLR. P.M. no singoff card
|
INSP-Sprinkler Rough-in/Hydro | 3/5/1997 | 3/6/1997 | 3/6/1997 | P | PASS |
Joe Tawney
|
|
|
03/06/97 406 - CECIL - (V.P.) ###-#### FINAL OK FOR LETTER OF COMPL
|
INSP - Framing/ Rough-in | 12/10/1996 | 12/10/1996 | 12/10/1996 | | PASS |
|
|
|
/ / 338 - FRAM-OK FRAMING
|
INSP - Framing/Rough-in | 12/10/1996 | 12/10/1996 | 12/10/1996 | P | CANC |
|
|
|
12/10/96 338 - LIBRARY.... out of time will catch first thing in the a.
|
Issue PAID IN FULL permit | | | 9/3/1996 | | |
|
|
|
|
Print Occupancy Form | | | 9/3/1996 | | |
|
|
|
|
Inspection Record Card- Bld | | | 9/3/1996 | | |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/3/1996 | | PASS |
|
|
|
Plans, resubmittals, notes & attachments to plans approved.
|
Plan resubmittals received | | | 9/3/1996 | | |
|
|
|
Received resubmittals. Prteparing plans for permit processing.
|
Routing - BUILDING | 5/29/1996 | | 9/3/1996 | | PASS |
|
|
|
Preliminary plan review FAXED & mailed to David Johnson, Gerald Nichols & Assoc., requesting resubmittals. Routing plans to Fire Dept. for review. 8/27/96 - Requested additional clarification of David Jophnson, architect. Sent fax & hard copy of items needing clarrified to Dave and then talked to him on phone after he had reviewed them. 09/03/96 - Received resubmittals from Dave Johnson. Processing plans for issuing of permit.
|
Plan Received by (DRS) | 5/29/1996 | | 9/3/1996 | | PASS |
Dan Stuart
|
|
|
09/03/96 08:58:13 DRS - this action updated by action script from <<>> in Case No. BLD96-0976
|
Plan resubmittals requested | | | 8/27/1996 | | |
|
|
|
Further clarification required. Had meeting with Mark Van Gulick of Kreizenbeck Constructors and phone review with Dave Johnson of Gerald Nichols in addition to sending a fax and follow up hard copy requesting clarifications.
|
Plan resubmittals received | | | 8/27/1996 | | |
|
|
|
PLAN RESUB. SHEETS A2.1, A3.1, AND A8.1 RECEIVED. KMM GAVE TO DAN STUART.
|
Meeting | | | 8/27/1996 | | |
|
|
|
Meeting with Mark VanGulick of Kreizenbeck Const., contractor for this project. Reviewed the requirements for ceiling finishes within the rated corridor. Sec. 803 & Tbl 8-B require minimum Class II finish in corridor & Class III in other library areas. The wood finish listed in the specs indicates a Class III rating which will not work in the corridor. The wall portions woth wood finish indicate furr outs greater than the 1-3/4" allowed per Sec. 803 & has wood used as support that is not within a fire resistive assembly per Sec. 602. Also have question on method being used to support the wood structure being hung on the wall. Mark to review with architect and I will send comments to architect at the same time.
|
Telephone call | | | 8/19/1996 | | |
|
|
|
Phone call to David Johnson, GRN Arch., to check on progress of resubmittal. David said project was still a go and he hoped something would be coming to me this week for review.
|
90 day tracking............. | | 4/25/1996 | 7/24/1996 | | |
|
|
|
|
Routing - FIRE | 6/7/1996 | | 6/10/1996 | | PASS |
|
|
|
|
Unassigned to Plan Reviewer | 4/25/1996 | | 6/7/1996 | | PASS |
|
|
|
06/07/96 13:33:05 DRS - this action updated by action script from <<>> in Case No. BLD96-0976
|
Plan resubmittals requested | | | 6/7/1996 | | |
|
|
|
|
Plan Reviewer's Copy of Permit | | | 6/7/1996 | | PEND |
|
|
|
|
Routing - MECHANICAL | 4/29/1996 | | 5/1/1996 | | PASS |
|
|
|
|
Routing - PUBLIC WORKS | 4/26/1996 | | 4/29/1996 | | PASS |
|
|
|
|
Plan routing begun/TENANTS | | | 4/26/1996 | | |
|
|
|
Route to Public Works, Mechanical then back to Plan Check. After Plan Check route to Fire Department.
|
Plans taken to Plan Check | | | 4/25/1996 | | |
|
|
|
|
GAY'S RECEIPT FOR PARTIAL PAY | | | 4/25/1996 | | |
|
|
|
|
Application received | | | 4/25/1996 | | |
|
|
|
|
Routing - BUILDING | 5/1/1996 | | | | PEND |
|
|
|
|
Routing - BUILDING | 6/11/1996 | | | | PEND |
|
|
|
|