Fee Review-notes | 2/14/2000 | 2/14/2000 | 2/14/2000 | | DONE |
|
|
|
|
(F) Reprint permit | | | 1/27/2000 | | DONE |
|
|
|
|
(F) Reprint permit | | | 5/28/1999 | | |
|
|
|
|
INSP - Final | 3/25/1999 | 3/26/1999 | 3/26/1999 | A | PASS |
|
|
|
L.C. #16385 issued 3-26-99 - 338
|
INSP-Final Inspection | 3/24/1999 | 3/25/1999 | 3/25/1999 | A | PASS |
Rick Jackson
|
|
|
RON ###-#### occ approved
|
INSP-Final Inspection | 3/24/1999 | 3/24/1999 | 3/24/1999 | P | CANC |
Rick Jackson
|
|
|
###-#### RON//FINAL FIRE rescheduled for 3/25
|
Temporary occupancy | | | 1/27/1999 | | PASS |
|
|
|
Temp. Occ. Cert. #3779 issued 1-27-99 to Mtn. States Tumor Institute - Phase I only.
|
Temporary occupancy | | | 1/27/1999 | | PASS |
|
|
|
Temp. Occ. Cert. #3780 issued 1-27-99 to Mtn. States Tumor Institute - Phase II.
|
Temporary occupancy | | | 1/27/1999 | | PASS |
|
|
|
Temp. Occ. Cert. #3781 issued 1-27-99 to MSTI, Phase III.
|
INSP-Final Inspection | 10/29/1998 | 10/30/1998 | 11/2/1998 | P | PART |
Rick Jackson
|
|
|
ron cell ###-#### fn insp
|
INSP - Final | 10/29/1998 | 10/30/1998 | 10/30/1998 | A | PASS |
|
|
|
10/30/98 333 - ok to sign for perm
|
INSP - Final | 10/21/1998 | 10/22/1998 | 10/23/1998 | P | FAIL |
|
|
|
10/22/98 333 - RON ###-#### CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
|
INSP-Final Inspection | 10/21/1998 | 10/22/1998 | 10/22/1998 | P | FAIL |
Rick Jackson
|
|
|
RON ###-#### door hold-opens didn't release on alarm; sprinkler issues
|
INSP-Conference | 10/12/1998 | 10/12/1998 | 10/12/1998 | P | PART |
Rick Jackson
|
|
|
fire pump room requires sprinklering and remove combustibles from above gridded ceiling
|
INSP-Sprinkler Rough-in/Hydro | 10/9/1998 | 10/9/1998 | 10/9/1998 | A | FAIL |
Rick Jackson
|
|
|
combustibles above in corridors; head needed in bathroom; sway bracing needed; smoke detector too close to diffuser;
|
INSP - Wall cover | 10/8/1998 | 10/9/1998 | 10/9/1998 | A | FAIL |
Jim Storey
|
|
|
10/09/98 301 - RON ###-#### CEILING COVER CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
|
INSP-Final Inspection | 10/8/1998 | 10/9/1998 | 10/9/1998 | A | FAIL |
Jim Storey
|
|
|
10/09/98 301 - RON ###-#### TRY TO BE THERE WITH STRUCTURAL INSPECTOR CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
|
INSP-Sprinkler Rough-in/Hydro | 10/9/1998 | 10/9/1998 | 10/9/1998 | A | FAIL |
Rick Jackson
|
|
|
sway bracing not done; combustibles above drop ceiling; needs head in bathroom by dressing rooms; smoke detector within 3 feet of diffuser
|
INSP - Framing/Rough-in | 6/29/1998 | 6/29/1998 | 6/29/1998 | P | PASS |
|
|
|
06/29/98 333 - FRAM-OK FRAMING
|
INSP - Framing/Rough-in | 3/17/1998 | 3/18/1998 | 3/18/1998 | A | PART |
|
|
|
03/18/98 333 - framing ok BASEMENT CT SIMILATOR ROOM--RON ###-####
|
INSP - Final | 2/27/1998 | 3/2/1998 | 3/2/1998 | P | PART |
|
|
|
03/02/98 333 - card signed for tempRON ###-####--MSTI
|
INSP-Final Inspection | 2/26/1998 | 2/27/1998 | 2/27/1998 | A | PASS |
Rick Jackson
|
|
|
PLEASE MEET RON AT 10:00--###-####--MSTI alarms, mag-hold opens, dampers all operational
|
INSP-Sprinkler Rough-in/Hydro | 2/26/1998 | 2/26/1998 | 2/26/1998 | A | PASS |
Rick Jackson
|
|
|
hydro completed/rough-in okay
|
INSP-Sprinkler Rough-in/Hydro | 2/13/1998 | 2/13/1998 | 2/13/1998 | A | FAIL |
Rick Jackson
|
|
|
additional hangers needed in south/west end. comm. lines strapped to sprinkler piping.
|
INSP-Final Inspection | 2/12/1998 | 2/13/1998 | 2/13/1998 | A | PASS |
Rick Jackson
|
|
|
RON ###-####-###-####-KIM WILL BE GOING OUT ALSO-FIRE DAMPERS smoke/fire dampers operated correctly.
|
INSP - Framing/Rough-in | 2/12/1998 | 2/13/1998 | 2/13/1998 | A | PART |
|
|
|
02/13/98 333 - RON ###-####-CEILING GRID RICK WILL BE SCHEDULED TO GO OUT ALSO YOU MIGHT WANT TO GET WITH HIM. ceilings ok to cover dampers ok
|
INSP - Framing/Rough-in | 2/2/1998 | 2/3/1998 | 2/3/1998 | P | PASS |
|
|
|
02/03/98 333 - SCLG-OK SUSPENDED CEILING
|
Inspection Record Card- Bld | | | 1/30/1998 | | |
|
|
|
|
Print Occupancy Form | | | 1/30/1998 | | |
|
|
|
|
INSP - Framing/Rough-in | 1/14/1998 | 1/14/1998 | 1/14/1998 | | PASS |
|
|
|
/ / 333 - phase 2frame ok 1st floor
|
INSP - Framing/Rough-in | 10/15/1997 | 10/16/1997 | 10/16/1997 | P | PART |
Jim Storey
|
|
|
10/16/97 301 - 4 hr gyp atchment ok work in progess.
|
INSP - Carpentry | 10/16/1997 | 10/16/1997 | 10/16/1997 | A | PART |
Carl Dependahl
|
|
|
GYP AT 4HR WALL...GOT FASTENER SCHED. FOR 4-LAYER GYP...301 WILL INSP AT PM.
|
INSP - Framing/Rough-in | 10/14/1997 | 10/15/1997 | 10/15/1997 | A | PART |
Carl Dependahl
|
|
|
four hour wall exterior...333 AREA. NW CORNER 1ST FL EXT WALL. NEED TO SEE ATTACHMENT OF MULTI-LAYER GYPSUM.
|
INSP - Carpentry | 10/15/1997 | 10/15/1997 | 10/15/1997 | P | NR |
Carl Dependahl
|
|
|
333 AREA NW CORNER 1ST FL MSTI; CHK GYP LAYERS AT 4 HR WALL SECTION...nr, need recall insp.
|
INSP-Final Inspection | 8/7/1997 | 8/7/1997 | 8/7/1997 | P | PASS |
|
|
|
1PM, RON all phase 1 items complete
|
INSP - Occupancy Sign-off | 7/30/1997 | 7/31/1997 | 7/31/1997 | A | PART |
|
|
|
07/31/97 333 - first phase ok for temp
|
INSP-Final Inspection | 7/30/1997 | 7/31/1997 | 7/31/1997 | A | FAIL |
|
|
|
ELEV RECAL DOES NOT WORK
|
INSP - Temporary occupancy | 7/22/1997 | 7/23/1997 | 7/23/1997 | A | FAIL |
|
|
|
07/23/97 333 - cn not made
|
INSP-Final Inspection | 7/23/1997 | 7/23/1997 | 7/23/1997 | P | PART |
|
|
|
C.N ISSUED WITH ITEMS TO BE RESOLVED, OK FOR EMPLOYEES ONLY
|
INSP-Final Inspection | 7/21/1997 | 7/22/1997 | 7/23/1997 | P | FAIL |
|
|
|
REINSPECT, ALARM TWESTING, C/N ISSUED
|
INSP-Final Inspection | 7/18/1997 | 7/21/1997 | 7/21/1997 | A | NR |
|
|
|
NOT READY YET
|
INSP - Temporary occupancy | 7/17/1997 | 7/18/1997 | 7/18/1997 | P | FAIL |
|
|
|
07/17/97 333 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
|
INSP-Final Inspection | 7/16/1997 | 7/18/1997 | 7/18/1997 | A | FAIL |
|
|
|
ALARM TESTING, SPRINKLER TESTING, EXITING alarms not complete, list of other items left
|
INSP-Sprinkler Rough-in/Hydro | 7/16/1997 | 7/16/1997 | 7/16/1997 | A | PASS |
|
|
|
FINISH FLRS B&1, SHELL ONLY 2-P, NEED FDC FOR STANDPIPE FOR FINAL, ALL HYDRO TESTED
|
INSP-Sprinkler Rough-in/Hydro | 6/16/1997 | 6/16/1997 | 6/16/1997 | P | PART |
|
|
|
electrical room, marv wants heads moved ok to relo to center under beam
|
INSP-Sprinkler Rough-in/Hydro | 5/30/1997 | 5/30/1997 | 5/30/1997 | A | PART |
|
|
|
ALLOWED EXTENSIONS TO NW TOWER HOSE CONN AT 2.5 INCH, CHECKED FOR SPACING/ OBSTRUCTIONS. PROBLEMS WITH DECORATIVE SOFFITS NOTED. WILL RECHECK AT HYDRO.
|
INSP-Conference | 5/6/1997 | 5/8/1997 | 5/8/1997 | A | PASS |
|
|
|
9 am mtg w/ simplex at eidam assoc, 815 park, st 230 on alarm plans G Eidam to revise floor plans, simplex to follow with ness revs to schematic
|
INSP-Sprinkler Rough-in/Hydro | 5/7/1997 | 5/7/1997 | 5/7/1997 | P | PART |
|
|
|
basement hydro ( not tied to riser), told stan ok to tie cross connection in on 2nd flr of stairwell ( base of standpipe)
|
INSP-Sprinkler Rough-in/Hydro | 4/30/1997 | 4/30/1997 | 4/30/1997 | P | PART |
|
|
|
clarified correction notice on alarm system w/ st lukes staff ( ron & D Maloney), walked through sprinkler issues w/ shilo & st lukes, will resubmit proposed changes to fdc/piv locations. Want to appeal sprinkling under drive under canopy. want to route dry standpipe on 2nd floor.
|
INSP-Conference | 4/11/1997 | 4/10/1997 | 4/10/1997 | P | PART |
|
|
|
PICKED UP PLANS AND REVIEWED, STILL MISSING FLOOR PLANS AND PRODUCT DATA SHEETS TO COMPLETE REVIEW
|
INSP-Conference | 4/10/1997 | 4/10/1997 | 4/10/1997 | A | NR |
|
|
|
meeting at simplex office to review alarm plan correction list - T. Kyle PLANS NOT READY AT SCHEDULED TIME OF 11 AM,
|
INSP-Conference | 3/27/1997 | 3/31/1997 | 3/31/1997 | P | PASS |
|
|
|
alarm plan review, return to ron w/ correction list, 2 pgs, resubmittal required
|
INSP-Conference | 3/27/1997 | 3/26/1997 | 3/26/1997 | P | PART |
|
|
|
meeting w/ maurer, ron, and maloney on exiting issues and phased const.
|
INSP - Wall cover | 3/25/1997 | 3/26/1997 | 3/25/1997 | A | PASS |
|
|
|
03/26/97 333 - INTERIOR WALLS FRAM-OK FRAMING
|
INSP - Wall cover | 2/25/1997 | 2/26/1997 | 2/25/1997 | A | PASS |
|
|
|
02/26/97 333 - EXTERIOR WALLS PENTHOUSE LEVEL ok
|
INSP - Wall cover | 2/13/1997 | 2/14/1997 | 2/14/1997 | A | PART |
|
|
|
02/14/97 333 - partial frame
|
Issue PAID IN FULL permit | | | 11/6/1996 | | |
|
|
|
|
Telephone call | | | 11/5/1996 | | |
|
|
|
LEFT MESSAGE FOR JEFF HULL
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/4/1996 | | PASS |
|
|
|
Passed with conditions of plan review compliance and letter on file from Jeff Hull of SLRMC.
|
Print Pending Permit.LaserJet4 | | | 11/4/1996 | | PASS |
|
|
|
|
Routing - PLAN CHECK | 9/19/1996 | | 11/4/1996 | | PASS |
|
|
|
Have received submittals for plan review concerns and am processing plans for a permit.
|
Inspection Record Card- Bld | | | 11/4/1996 | | |
|
|
|
|
Print Occupancy Form | | | 11/4/1996 | | |
|
|
|
|
Plan Received by (DRS) | 7/15/1996 | | 11/4/1996 | | PASS |
Dan Stuart
|
|
|
11/04/96 16:02:36 DRS - this action updated by action script from <<>> in Case No. BLD96-1321
|
Telephone call | | | 11/1/1996 | | |
|
|
|
Told Russ Phillips that I needed a letter from Jeff Hull, St. Lukes RMC stating that as the Architect of Record he would make sure that requirements of the plan review would be completed even if they had to change somthing they had already completed. A copy of the letter is included on the plans.
|
Telephone call | | | 10/30/1996 | | |
|
|
|
Russ Phillips called and asked if it would be possible to issue the permit prior to reveiving full size sheets for the corrections as originally agreed. Olsen & Assoc. will send someone down to install the 8-1/2 x 11 sheets into both sets of plans if we can issue. I told Russ to send them over & I would review the plans for ability to follow after the small sheets had benn inserted by their employee. An employee spent two days 10/24/96 & 10/25/96 installing copies.
|
Plan Reviewer's activity | | | 10/30/1996 | | |
|
|
|
Started to review the plan with inserts installed. I found that some of the copies were not legible and were on the wrong sheets. I have removed several of the inserts and red lined the plans to help clarify areas needing corrected. 11/04/96 - completed the rework of plans for permit processing. I have attached copies of my plan review comments & architect rsponse to both sets of plans.
|
Plan resubmittals received | | | 10/18/1996 | | |
|
|
|
RECEIVED RESPONSE THAT ANSWERED CONCERNS. SENT FAX AND HARD COPY TO RUSS PHILLIPS AT OLSEN & ASSOC. STATING THAT AS SOON AS FULL SIZE DRAWINGS ARE RECEIVED FOR PLANS AS ORIGINALLY AGREED I WOULD INSTALL THEM IN THE PLANS AND PREPARE FOR PERMIT ISSUANCE.
|
Meeting | | | 10/11/1996 | | |
|
|
|
Met with Russ Phillips to review areas still in question. Russ will resubmitt ASAP.
|
Meeting | | | 10/2/1996 | | |
|
|
|
Meeting at my office with Russ Phillips, Architect, to review comments from preliminary plan review still needing clarification as noted on 09/30/96 letter to Mr. Phillips.
|
Plan resubmittals requested | | | 9/30/1996 | | |
|
|
|
RESUBMITTALS OF 9/11/96 INCOMPLETE. REQUESTED MORE CLARIFICATION.
|
Plan Reviewer's activity | | | 9/23/1996 | | |
|
|
|
Started to review the resubmittals for the MSTI project.
|
Plan resubmittals received | | | 9/11/1996 | | |
|
|
|
Recieved plan resubmittals for MSTI basement & 1st floor project. 8-1/2 x 11 inch sheets sent for review. When details are approved as correct Russ Phillips will then have the details put on the full sized plans and resubmitt a clean set for approval.
|
Routing - FIRE | 8/2/1996 | | 8/9/1996 | | PASS |
|
|
|
|
Routing - BUILDING | 7/15/1996 | | 8/2/1996 | | |
|
|
|
Began plan review. Prepared preliminary plan check comments and faxed and mailed hard copy to Russ Phillips of Olsen & Assoc. Routing plans to Fire Dept. for review.
|
Plan resubmittals requested | | | 8/1/1996 | | |
|
|
|
Faxed copy of preliminary review to Russ Phillips and mailed copy.
|
Meeting | | | 8/1/1996 | | |
|
|
|
Meeting with Russ Phillips & associate to review plan review comments prior to issuing written review and forwarding plans to the fire dept. for review.
|
Plan Reviewer's Copy of Permit | | | 8/1/1996 | | PASS |
|
|
|
|
Unassigned to Plan Reviewer | 5/23/1996 | | 7/15/1996 | | PASS |
|
|
|
07/15/96 13:02:51 DRS - this action updated by action script from <<>> in Case No. BLD96-1321
|
Routing - MECHANICAL | 6/11/1996 | | 6/13/1996 | | PASS |
|
|
|
|
Routing - PLUMBING | 6/5/1996 | | 6/10/1996 | | PASS |
|
|
|
|
Routing - PUBLIC WORKS | 5/29/1996 | | 6/4/1996 | | PASS |
|
|
|
|
Plan routing begun/TENANTS | | | 5/29/1996 | | |
|
|
|
Route to Public Works, Plumbing and Mechanical then back to Plan Check. After Plan Check route to Fire Department.
|
Plans ACCEPTED BY PLAN CHECK | | | 5/23/1996 | | |
|
|
|
|
Application received | | | 5/23/1996 | | |
|
|
|
|
GAY'S RECEIPT FOR PARTIAL PAY | | | 5/23/1996 | | |
|
|
|
|
Routing - BUILDING | 6/13/1996 | | | | PEND |
|
|
|
|
Routing - BUILDING | 8/8/1996 | | | | PEND |
|
|
|
|