Permanent Occupancy | | 5/28/1997 | 5/28/1997 | | DONE |
|
|
|
|
Permanent occupancy | | | 5/28/1997 | | PASS |
|
|
|
Perm. Occ. Cert. #6877 issued 5-28-97 to Jackson's Food Store.
|
INSP - Final | 5/12/1997 | 5/12/1997 | 5/12/1997 | | PASS |
Joe Tawney
|
|
|
/ / 406 - REINSP FOR FINAL OK FOR PERM OCC
|
Temporary occupancy | | | 5/12/1997 | | PASS |
|
|
|
Temp. Occ. Cert. #3403 issued 5-12-97 to Jackson's Food Store.
|
INSP - Final | 5/9/1997 | 5/12/1997 | 5/11/1997 | A | PART |
|
|
|
05/12/97 338 - verbal c/n for the main structure need approved ramp for need ele signoff for the pump canopy OTH-OTHER AGENCIES NOT APPROVED ok for temp occ only signed the temp col the occ rec form
|
INSP-Final Inspection | 5/8/1997 | 5/9/1997 | 5/9/1997 | A | FAIL |
Joe Tawney
|
|
|
05/09/97 406 - FINAL FAIL MAN FLUSH BOLTS EMERG LIGHT WIRING LANDING AT INST & TEST OF SMOKE DET IN AC UNIT
|
Routing for occupancy | 5/9/1997 | 5/9/1997 | 5/9/1997 | | PASS |
|
|
|
Complies w/ DR-54-96/CU-105-95 - Insp. by AY/signed final
|
INSP - Framing/Rough-in | 4/3/1997 | 4/4/1997 | 4/4/1997 | A | PASS |
Carl Dependahl
|
|
|
04/04/97 340 - FRAME REINSPECT, C/N OK
|
INSP - Framing/Rough-in | 4/2/1997 | 4/3/1997 | 4/3/1997 | A | FAIL |
Carl Dependahl
|
|
|
04/03/97 340 - C/N, NEED HD BOLTS, FIREBLOCKS. OK TO INS
|
INSP - Conference | 4/3/1997 | 4/3/1997 | 4/3/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - W/ CONT RE C/N OF 4-3-97
|
INSP - Framing/Rough-in | 4/2/1997 | 4/2/1997 | 4/1/1997 | P | NR |
|
|
|
04/02/97 338 - not ready OTH-OTHER AGENCIES NOT APPROVED
|
INSP - Foundation | 3/7/1997 | 3/7/1997 | 3/5/1997 | P | PASS |
|
|
|
03/07/97 338 - FDN -OK FOUNDATION
|
INSP - Footings | 3/5/1997 | 3/6/1997 | 3/5/1997 | A | PASS |
|
|
|
03/06/97 338 - JACKSON'S FOOD STORES FTG -OK FOOTING
|
Plan assigned to (M_O) | 1/29/1997 | | 3/5/1997 | | PASS |
|
|
|
|
CHANGE STATUS TO (I) | | | 3/5/1997 | | |
|
|
|
|
(F) Reprint permit | | | 3/5/1997 | | |
|
|
|
|
Inspection Record Card- Bld | | | 3/5/1997 | | |
|
|
|
|
Print Pending Permit.LaserJet4 | | | 3/5/1997 | | |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/5/1997 | | PASS |
|
|
|
|
Print Occupancy Form | | | 3/5/1997 | | |
|
|
|
|
CHANGE STATUS TO (I) | | | 3/4/1997 | | |
|
|
|
ALL WORK IS OK PER MIKE O.
|
Routing Off Site - STRUCTURAL | 2/25/1997 | | 3/4/1997 | | PASS |
|
|
|
SET TO CH2M HILL DAR
|
Routing - PUBLIC WORKS | 2/27/1997 | | 2/28/1997 | | PASS |
|
|
|
PACKAGE #2 SECOND DRAINAGE REVIEW FEE CHARGED AND SECOND DRAINAGE FEE CHARGED BY BRIAN MURPHY.
|
Plan Reviewer's activity | | | 2/20/1997 | | PEND |
|
|
|
Faxed and mailed structural review comments to architect 2-20-97. MO
|
Routing Off Site - STRUCTURAL | 1/29/1997 | | 2/20/1997 | | FAIL |
|
|
|
PACKAGE #3 RESUBMITTAL CONTACTED PDQ TO TAKE PLANS OUT TO CH2MHILL ATTEN: CRAIG BARRETT. PACKAGE #3 CAME BACK FROM CH2MHILL 2-20-97. TO PLAN CHECK
|
Routing - FIRE | 2/4/1997 | | 2/19/1997 | | PASS |
|
|
|
PACKAGE #1 RESUBMITTAL
|
Routing Off Site - A.C.H.D | 1/29/1997 | | 2/7/1997 | | PASS |
|
|
|
PACKAGE #4 RESUBMITTAL CONTACTED DALE BINNING AT ###-#### TO TAKE PLANS OUT TO ACHD
|
Routing - PLANNING | 1/30/1997 | | 2/4/1997 | | PASS |
|
|
|
PACKAGE #2 RESUBMITTAL X-ref: CU-105-95 & DR-54-96. Approved by JH & MS.
|
Routing - MECHANICAL | 2/3/1997 | | 2/4/1997 | | PASS |
|
|
|
PACKAGE #1 RESUBMITTAL NO REVIEW WILL FIELD VERIFY. GS
|
Routing - PLAN CHECK | 2/4/1997 | | 2/4/1997 | | |
|
|
|
PACKAGE #1 RESUBMITTAL
|
Routing - PLUMBING | 1/31/1997 | | 2/3/1997 | | PASS |
|
|
|
PACKAGE #1 RESUBMITTAL
|
Routing - ELECTRICAL | 1/29/1997 | | 1/31/1997 | | PASS |
|
|
|
PACKAGE #1 RESUBMITTAL
|
Routing - PUBLIC WORKS | 1/29/1997 | | 1/29/1997 | | FAIL |
|
|
|
PACKAGE #2 RESUBMITTAL REQUIRES DRAINAGE PLAN. BM
|
Plan routing begun/NEW & ADDTN | | | 1/29/1997 | | PASS |
|
|
|
RESUBMITTAL FOUR PACKAGES. KMM THEY ARE ADDING FOUR EXTRA FEET.
|
Plan resubmittals received | | | 1/29/1997 | | PASS |
|
|
|
RESUBMITTALS RECEIVED FOR FOUR PACKAGE ROUTING. KMM THEY ARE ADDING 4 EXTRA FEET
|
(F) Reprint permit | | | 10/21/1996 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 10/18/1996 | | |
|
|
|
|
90 day tracking............. | | 7/19/1996 | 10/17/1996 | | |
|
|
|
|
Telephone call | | | 10/16/1996 | | |
|
|
|
DALE BENNING SAID HE WOULD BRING THE CHECK IN BY FRIDAY, TO PICK UP THE PERMIT.
|
INSP - Misc. complaint | 10/14/1996 | 10/15/1996 | 10/15/1996 | A | PASS |
|
|
|
10/15/96 338 - PERMIT NOT PICKED UP. CHECK OUT. did this the other day
|
INSP - Stop Work Order | 10/10/1996 | 10/11/1996 | 10/11/1996 | A | PASS |
|
|
|
10/11/96 338 - THEY HAVE NOT PICKED UP OR PAID FOR THIS PERMIT. THERE HA MECHANICAL INSPECTIONS DONE. DIX there has been no work as of this time that should be retained against t permit # they have decided to wait until spring to do the work.
|
Routing - PUBLIC WORKS | 9/6/1996 | | 9/25/1996 | | PASS |
|
|
|
PACKAGE 2 TO PLAN CHECKER. 9/25/96 DAR
|
Print Pending Permit.LaserJet4 | | | 9/25/1996 | | |
|
|
|
|
Inspection Record Card- Bld | | | 9/25/1996 | | |
|
|
|
|
Print Occupancy Form | | | 9/25/1996 | | |
|
|
|
|
Telephone call | | | 9/25/1996 | | |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/25/1996 | | PASS |
|
|
|
|
Plan Received by (M_O) | 8/13/1996 | | 9/25/1996 | | PASS |
|
|
|
CORRECTIONS MAILED AND FAXED TO ARCHITECT 8-16-96 MO
|
Routing Off Site - A.C.H.D | 7/22/1996 | | 9/18/1996 | | PASS |
|
|
|
ACKAGE #4 CONTACTED DALE BINNING FOR ACHD PICK UP AT ###-#### PLANS NOT SIGNED BY ACHD. ACHD IMPACT FEES NOT PAID. PACKAGE 4 TO MIKE OTTO 9/10/96 DAR RETURNED PACKAGE 4 TO DAR FOR DELIVERY BACK TO ACHD FOR SIGN OFF 9-10-96 MO. plans have been signed 09-13-96 IMPACT FEES PAID 09-18-96 RECEIPT #96-0854 KMM
|
Routing - MECHANICAL | 9/10/1996 | | 9/12/1996 | | PASS |
|
|
|
|
Routing - PLUMBING | 9/6/1996 | | 9/10/1996 | | PASS |
|
|
|
|
Routing - PUBLIC WORKS | 8/14/1996 | | 8/22/1996 | | FAIL |
|
|
|
PACKAGE #2 INCOMPLETE LEGAL DESCRIPTION. PRO0F OF LEGAL LAND DIVISION. PROP. LINE ADJUSTMENT SURVEY IN PROGRESS
|
Routing - FIRE | 8/16/1996 | | 8/20/1996 | | PASS |
|
|
|
|
Plan resubmittals requested | | | 8/16/1996 | | FAIL |
|
|
|
plan review corrections sent and faxed to architect 8-16-96 MO
|
Routing - PLANNING | 8/9/1996 | | 8/14/1996 | | PASS |
|
|
|
PACKAGE #2 X-ref: CU-105-95, DR-54-96. Approved by JH & MS.
|
Routing Off Site - STRUCTURAL | 7/22/1996 | | 8/13/1996 | | PASS |
|
|
|
package #3 CH2MHILL ATTENTION CRAIG BARRETT OR MARK BOWEN ###-#### PACKAGE #3 CH2HILL CAME BACK ON 08-13-96 IN PLAN CKECK.
|
Unassigned to Plan Reviewer | 7/19/1996 | | 8/13/1996 | | PEND |
|
|
|
|
Routing - PLUMBING | 8/9/1996 | | 8/12/1996 | | FAIL |
|
|
|
|
Plan resubmittals received | | | 8/9/1996 | | PASS |
|
|
|
M-1 AND P-1 SHEETS RECEIVED
|
Plan resubmittals received | | | 8/8/1996 | | PASS |
|
|
|
SHEETS S-1 AND P-1 FOR PACKAGE 2
|
Routing - MECHANICAL | 7/31/1996 | | 8/5/1996 | | FAIL |
|
|
|
PACKAGE #1
|
Routing Off Site - C.D.H | 7/22/1996 | | 7/31/1996 | | PASS |
|
|
|
DALE BINNING FOR CDH PICKUP DALE BINNING PICKUPED PLANS FROM CDH AND TOOK THEM TO HIS OFFICE FOR A STREET LIGHT PLAN AND GREASE TRAP ISSUE FOR P.W.
|
Routing - PLUMBING | 7/23/1996 | | 7/30/1996 | | FAIL |
|
|
|
PACKAGE #1
|
Routing - ELECTRICAL | 7/22/1996 | | 7/23/1996 | | PASS |
|
|
|
PACKAGE #1
|
Plan routing begun/NEW & ADDTN | | | 7/22/1996 | | PASS |
|
|
|
|
Application received | | | 7/19/1996 | | |
|
|
|
|
GAY'S RECEIPT FOR PARTIAL PAY | | | 7/19/1996 | | |
|
|
|
|
Plans taken to Plan Check | | | 7/19/1996 | | |
|
|
|
|
Routing - PLAN CHECK | 9/12/1996 | | | | PEND |
|
|
|
|
Routing - PLAN CHECK | 3/5/1997 | | | | |
|
|
|
PACKAGE #3 FROM CH2MHILL
|
Routing - PLAN CHECK | 9/25/1996 | | | | PEND |
|
|
|
PACKAGE #2 TO PLAN CHECKER. 9/26/96 DAR
|
Routing - PLAN CHECK | 9/13/1996 | | | | PEND |
|
|
|
|
Routing - BUILDING | 8/12/1996 | | | | PEND |
|
|
|
PACKAGE #1
|
Routing - PLAN CHECK | 2/7/1997 | | | | |
|
|
|
Package #4 RESUBMITTAL
|
Routing - PLAN CHECK | 2/19/1997 | | | | |
|
|
|
PACKAGE #1 RESUBMITTAL
|
Routing - PLAN CHECK | 2/20/1997 | | | | |
|
|
|
RESUBMITTAL PACKAGE #3
|
Routing - PLAN CHECK | 2/4/1997 | | | | |
|
|
|
PACKAGE #2 RESUBMITTAL
|
Routing - BUILDING | 8/5/1996 | | | | PEND |
|
|
|
|
Routing - PLAN CHECK | 2/28/1997 | | | | |
|
|
|
PACKAGE #2
|
Routing - BUILDING | 8/22/1996 | | | | PEND |
|
|
|
PACKAGE #2
|