Case Summary (BLD) | | | 1/11/2016 | | |
|
|
|
|
Case Summary (BLD) | | | 11/20/2008 | | |
|
|
|
|
Permanent occupancy | | | 9/5/1997 | | DONE |
|
|
|
Perm. Occ. Cert. #6968 issued 9-5-97 to Ecco Electronics.
|
Permanent Occupancy | | 8/29/1997 | 8/29/1997 | | DONE |
|
|
|
|
INSP-Final Inspection | 8/29/1997 | 8/29/1997 | 8/29/1997 | P | PASS |
Rick Jackson
|
|
|
|
INSP - Final | 8/29/1997 | 8/29/1997 | 8/29/1997 | | PASS |
Jim Storey
|
|
|
/ / 301 - FNL -OK FINAL
|
INSP - Final | 8/26/1997 | 8/27/1997 | 8/27/1997 | P | NR |
Jim Storey
|
|
|
08/27/97 301 - i gave floyd his for 8/26/97 all other trades finaled. ca CORR-CORREC-CALL FOR REINSP WHEN COMPLETED HI JIM.....I FAILED THEM TUESDAY PM, ALARM ZONES STILL NOT RIGHT
|
INSP-Final Inspection | 8/26/1997 | 8/26/1997 | 8/26/1997 | P | FAIL |
|
|
|
cathy has card to sign off. ALARM RESPONCE STILL WRONG ( 5/23 CORRECTION LIST) FD CALLED FOR EVERYTHING... TO CORRECT ASAP
|
Routing for occupancy | 5/29/1997 | 5/29/1997 | 5/29/1997 | | PASS |
|
|
|
Art Y. inspected for final - meets compliance with DR-65-96/Signed Final.
|
INSP - Final | 5/29/1997 | 5/29/1997 | 5/29/1997 | | PASS |
Jim Storey
|
|
|
/ / 301 - TCO -TEMP C OF O ISSUED CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
|
Temporary occupancy | | | 5/29/1997 | | PASS |
|
|
|
Temp. Occ. Cert. #3411 issued 5-29-97 to Ecco Electronic.
|
INSP - Final | 5/23/1997 | 5/27/1997 | 5/27/1997 | P | NR |
Jim Storey
|
|
|
05/27/97 301 -
|
INSP-Final Inspection | 5/23/1997 | 5/23/1997 | 5/23/1997 | P | PART |
|
|
|
supervisorys still tranmit as alarms, need nfpa 72
|
INSP-Final Inspection | 5/21/1997 | 5/21/1997 | 5/21/1997 | P | FAIL |
|
|
|
address not visible, piv not monitored, all signals transmit as fire alarms, panel troubles do not transmit, 1 head too close to unit heater for temp rating
|
INSP-Final Inspection | 5/12/1997 | 5/12/1997 | 5/12/1997 | P | FAIL |
|
|
|
c/n issued, lots of details to wrap up, advised egress control devices must have auto, manual, fire alarm and power out release
|
INSP - Framing/Rough-in | 5/9/1997 | 5/9/1997 | 5/9/1997 | P | PASS |
Jim Storey
|
|
|
05/09/97 301 - FRAM-OK FRAMING Resubmital wall
|
INSP - Framing/Rough-in | 4/24/1997 | 4/25/1997 | 4/25/1997 | A | PASS |
Jim Storey
|
|
|
04/25/97 301 - ceiling wall SCLG-OK SUSPENDED CEILING and draft stop ok
|
INSP-Sprinkler Rough-in/Hydro | 4/24/1997 | 4/25/1997 | 4/25/1997 | A | PASS |
|
|
|
hydro test, todd will call when pressurized replaced test orifice w/ correct size
|
INSP-Sprinkler Rough-in/Hydro | 4/24/1997 | 4/24/1997 | 4/24/1997 | A | PART |
|
|
|
correction list given to herb on missing sprinklers. also gave notice that approved plans do not allow storage over 12 ft. sprinklers designed for 16 ft, no racks over 8 ft since no seismic was provided
|
INSP-Sprinkler Rough-in/Hydro | 4/23/1997 | 4/23/1997 | 4/23/1997 | P | PART |
|
|
|
herb dock area not complete, need to check 2nd floor storage
|
INSP - Conference | 4/21/1997 | 4/21/1997 | 4/21/1997 | | PART |
Jim Storey
|
|
|
/ / 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
|
INSP - Carpentry | 4/3/1997 | 4/2/1997 | 4/3/1997 | | PASS |
Jim Storey
|
|
|
sheer nailling on walls
|
INSP - Framing/Rough-in | 4/1/1997 | 4/1/1997 | 4/1/1997 | P | PASS |
Jim Storey
|
|
|
sheer nailling ok mezanine fr ok
|
INSP - Framing/Rough-in | 3/25/1997 | 3/25/1997 | 3/25/1997 | P | PART |
Jim Storey
|
|
|
03/25/97 301 - INTER STUD WALLS ALL BUT SHEER OK
|
INSP - Footings | 3/11/1997 | 3/12/1997 | 3/12/1997 | P | PASS |
Jim Storey
|
|
|
03/12/97 301 - covered by si. recieved eifs submital and approved system
|
INSP - Foundation | 12/12/1996 | 12/13/1996 | 12/13/1996 | A | PASS |
Jim Storey
|
|
|
12/13/96 301 - CALLED IN A FLOOR POUR FDN -OK FOUNDATION hair pins
|
90 day tracking............. | | 9/10/1996 | 12/9/1996 | | |
|
|
|
|
Plan resubmittals received | | | 12/5/1996 | | PASS |
|
|
|
A RESUBMITTAL WAS RECEIVED FOR BRS ARCHITECTS THAT CONTAINED REVISIONS TO THE PROPOSED HAZARDOUS MATERIALS MANAGEMENT PLAN, THE QUANTITIES OF HAZARDOUS MATERIALS TO BE STORED AND USED AND THE LOCATION OF THE STORED MATERIALS, INCLUDING THE DELETION OF THE PROPOSED EXTERIOR ATTACHED STORAGE ROOMS. THE PROPOSAL ALSO INCLUDED A CHANGE IN THE EXTERIOR FINISH MATERIALS FOR THE ECCO BUILDING. THE EXTERIOR FINISH CHANGES WOULD HAVE REQUIRED A MODIFICATION TO THE DESIGN REVIEW AND SO THAT REVISION WAS WITHDRAWN. THE HAZARDOUS MATERIALS USED AND THE STORAGE LOCATION CHANGES WERE REVIEWED BY JOHN MENARD AND DAVE MILLER AND APPROVED PER THE INFORMATION SUBMITTED FOR THE PROPOSED REVISION. THE PROPOSED CHANGES WERE SUBMITTED FOR APPROVAL AFTER THE ISSUANCE OF THE BUILDING PERMIT AND CONSTRUCTION HAS CONTINUED DURING THIS REVIEW.
|
INSP - Footings | 11/26/1996 | 11/27/1996 | 11/27/1996 | P | PASS |
Jim Storey
|
|
|
/ / 301 - READY AT 1PM PLEASE. FRMS-OK FORMS-REBAR special insp on site
|
INSP - Footings | 11/26/1996 | 11/26/1996 | 11/26/1996 | P | PART |
Jim Storey
|
|
|
11/26/96 301 - WIP -WORK IN PROGRESS special insp. on site pending repor
|
INSP - Footings | 11/25/1996 | 11/25/1996 | 11/25/1996 | P | NR |
Wes Worcester
|
|
|
still placing dobbies and getting side clearance...spec insp to be on site
|
INSP - Foundation | 11/25/1996 | 11/25/1996 | 11/25/1996 | P | PART |
Wes Worcester
|
|
|
poured with special insp on site...pending report as some dowels had less than 1" cover between them at jambs
|
INSP - Foundation | 11/21/1996 | 11/21/1996 | 11/21/1996 | P | PART |
Wes Worcester
|
|
|
special insp on site
|
INSP - Footings | 11/19/1996 | 11/19/1996 | 11/19/1996 | P | PASS |
Wes Worcester
|
|
|
APPT. 3 P.M.
|
INSP - Footings | 11/19/1996 | 11/19/1996 | 11/19/1996 | A | NR |
Wes Worcester
|
|
|
|
INSP - Site Preparation | 11/19/1996 | 11/19/1996 | 11/19/1996 | A | PART |
Wes Worcester
|
|
|
cleaning out mud and having soils tested
|
INSP - Conference | 11/19/1996 | 11/19/1996 | 11/19/1996 | A | PASS |
Wes Worcester
|
|
|
ck on lean concrete fill - going to pour at 3pm w/sp insp
|
INSP - Footings | 11/14/1996 | 11/15/1996 | 11/15/1996 | A | FAIL |
Wes Worcester
|
|
|
inadequate cover, special inspectors report rejected, eng of record and special inspector to meet on site. several 100'poured
|
(F) Reprint permit | | | 11/14/1996 | | |
|
|
|
|
Routing - PLAN CHECK | 11/12/1996 | | 11/13/1996 | | PASS |
|
|
|
|
Issue PAID IN FULL permit | | | 11/13/1996 | | |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/13/1996 | | PASS |
|
|
|
|
Issue PAID IN FULL permit | | | 11/13/1996 | | |
|
|
|
|
Print Occupancy Form | | | 11/13/1996 | | |
|
|
|
|
Telephone call | | | 11/13/1996 | | |
|
|
|
LEFT MESSAGE WITH SECRETARY
|
Inspection Record Card- Bld | | | 11/13/1996 | | |
|
|
|
|
Plan assigned to (JCM) | 9/19/1996 | | 11/13/1996 | | PASS |
John Menard
|
|
|
|
Routing - FIRE | 11/5/1996 | | 11/12/1996 | | PASS |
|
|
|
PACKAGE #1
|
Routing Off Site - A.C.H.D | 11/12/1996 | | 11/12/1996 | | PASS |
|
|
|
No impact fees were required for this project. See letter on file from A.C.H.D..
|
Routing - PLANNING | 11/5/1996 | | 11/6/1996 | | PASS |
|
|
|
PACKAGE #2 X-ref: DR-65-96. Approved by TKW.
|
Routing Off Site - A.C.H.D | 9/11/1996 | | 11/5/1996 | | PEND |
|
|
|
PACKAGE #4 CONTACTED CLINTON YAKA AT ###-#### TO TAKE PLANS TO ACHD ACHD FEES NOT PAID.
|
Routing - PLAN CHECK | 10/30/1996 | | 11/5/1996 | | PASS |
|
|
|
|
Plan resubmittals received | | | 10/31/1996 | | PASS |
|
|
|
|
Routing - FIRE | 10/24/1996 | | 10/30/1996 | | FAIL |
|
|
|
PACKAGE 1
|
Routing - PUBLIC WORKS | 10/18/1996 | | 10/21/1996 | | PASS |
|
|
|
|
Application received | | | 10/18/1996 | | |
|
|
|
|
Routing Off Site - STRUCTURAL | 9/12/1996 | | 10/10/1996 | | PEND |
|
|
|
PCKAGE#3 CONTACTED PDQ TO TAKE PLANS TO CH2MHILL ATTEN. CRAIG BARRETT OR MARK BOWEN FOR OUTSIDE ENGINEERING. KMM 9-12-96 RETURN 10-10-96 BACK AT JOHN DESK. COPY OF STRUCTURAL CORRECTION COMMENTS FAXED TO CLINTON YAKA AT BRS FOR REQUIRED REVISIONS. 10/11/96 JCM
|
Plan resubmittals requested | | | 10/8/1996 | | PEND |
|
|
|
ADDITIONAL RESUBMITTALS REQUESTED OF THE ARCHITECT.
|
Routing - FIRE | 10/1/1996 | | 10/4/1996 | | FAIL |
|
|
|
PACKAGE #1
|
Plan resubmittals received | | | 10/3/1996 | | PEND |
|
|
|
|
Routing - MECHANICAL | 9/25/1996 | | 10/1/1996 | | PASS |
|
|
|
PACKAGE #1
|
Routing - PLANNING | 9/20/1996 | | 9/25/1996 | | FAIL |
|
|
|
PACKAGE #2 X-ref: DR-65-96. Modification pending. Reviewed by TKW.
|
Plan resubmittals requested | | | 9/24/1996 | | PEND |
|
|
|
PRELIMINARY PLAN REVIEW COMMENTS SENT TO CLINTON YAKA, BRS ARCHITECTS FOR REQUIRED REVISIONS.
|
Routing - PUBLIC WORKS | 9/11/1996 | | 9/20/1996 | | FAIL |
|
|
|
PACKAGE #2 REQUIRES DRAINAGE PLAN REVISION
|
Routing - PLUMBING | 9/13/1996 | | 9/18/1996 | | PASS |
|
|
|
PACKAGE#1
|
Routing - ELECTRICAL | 9/11/1996 | | 9/13/1996 | | PASS |
|
|
|
PACKAGE#1
|
CHANGE STATUS TO (P) | | | 9/12/1996 | | PEND |
|
|
|
|
Plan routing begun/NEW & ADDTN | | | 9/11/1996 | | PASS |
|
|
|
|
Gay Receipt For Partial Pay | | | 9/11/1996 | | PEND |
|
|
|
|
Application received | | | 9/10/1996 | | |
|
|
|
|
Received Certificate of Value | | | 9/10/1996 | | PASS |
|
|
|
|
Routing - PLAN CHECK | 9/19/1996 | | | | PEND |
|
|
|
PACKAGE #1
|
Routing - PLAN CHECK | 10/4/1996 | | | | PEND |
|
|
|
PACKAGE #1
|
Routing - PLAN CHECK | 10/21/1996 | | | | PEND |
|
|
|
PACKAGE #2
|
Routing - PLAN CHECK | 11/12/1996 | | | | |
|
|
|
|
Routing - PLAN CHECK | 11/7/1996 | | | | |
|
|
|
PACKAGE #2
|
Routing - PLAN CHECK | 9/25/1996 | | | | PEND |
|
|
|
PACKAGE #2
|