INSP - Final | 1/7/1999 | 1/7/1999 | 1/7/1999 | P | PASS |
Carl Dependahl
|
|
|
change status to "D"...insp notes show final ok.
|
Office final | | | 1/7/1999 | | PASS |
|
|
|
CHANGE STATUS TO "D"...NOTES SHOW ALL INSP'S DONE, CARD SIGNED,ETC. CARL D.
|
INSP - Footings | 6/17/1997 | 6/18/1996 | 6/18/1998 | P | CANC |
Carl Dependahl
|
|
|
FOOTING REBAR
|
INSP - Final | 2/20/1998 | 2/19/1998 | 2/19/1998 | P | PASS |
Carl Dependahl
|
|
|
CONF W/ CATHY RE L/C ONLY
|
Code Occupancy Approval | | | 2/13/1998 | | PASS |
|
|
|
Final Insp. made - Final signed
|
INSP - Final | 2/9/1998 | 2/11/1998 | 2/11/1998 | P | PART |
Carl Dependahl
|
|
|
EARLY PM 2:30 CALL ED HESS ###-#### OR ###-####1 STRUCT OK; CARD TO ED HESS
|
INSP - Final | 2/6/1998 | 2/9/1998 | 2/9/1998 | A | CANC |
Carl Dependahl
|
|
|
CALL ED ###-#### OR ###-#### TO MEET YOU--BLDG 6 resched per ed
|
INSP - Conference | 2/6/1998 | 2/6/1998 | 2/6/1998 | A | PASS |
Carl Dependahl
|
|
|
re final insps, told to call office.
|
INSP - Carpentry | 2/4/1998 | 2/4/1998 | 2/4/1998 | P | PART |
Carl Dependahl
|
|
|
OK PER JOE
|
INSP - Conference | 2/3/1998 | 2/3/1998 | 2/3/1998 | A | PASS |
Carl Dependahl
|
|
|
W/ ERNIE HARPER RE FINAL INSP & TAWNEYS C/N...TOLD TO RECALL WHEN ALL SIGNATURES VERIFIED
|
INSP - Final | 2/3/1998 | 2/3/1998 | 2/3/1998 | P | NR |
Carl Dependahl
|
|
|
BLDG 6--ERNIE SAID HE TALKED TO YOU ABOUT THIS--###-#### OR ###-####--PLEASE CALL HIM FIRST
|
INSP - Final | 2/3/1998 | 2/3/1998 | 2/3/1998 | | PASS |
Joe Tawney
|
|
|
/ / 406 - REINSP FOR FINAL OK FOR CERT OF COMPL
|
INSP - Conference | 10/29/1997 | 10/29/1997 | 10/29/1997 | P | PASS |
Carl Dependahl
|
|
|
W/ MTI RE NON CONFORMING REPORTS
|
INSP - Conference | 10/28/1997 | 10/28/1997 | 10/28/1997 | P | PASS |
Carl Dependahl
|
|
|
W/ SLY; HE REC'D FINAL SPEC. INSP REPORT...WILL FORWARD TO ME.
|
INSP - Conference | 10/14/1997 | 10/14/1997 | 10/14/1997 | P | PASS |
Carl Dependahl
|
|
|
W/ JOE TAWNEY RE FINAL FOR CHILLER....NEED I.D. LABELS ON PRESS. & VALVES FOR CHILLER. PROPERLY SUPPORT VALVES.
|
INSP - Final | 10/8/1997 | 10/10/1997 | 10/10/1997 | P | NR |
Carl Dependahl
|
|
|
HP 6, CHILLER...need fire ok
|
INSP - Framing/Rough-in | 10/13/1997 | 10/10/1997 | 10/10/1997 | P | PASS |
Carl Dependahl
|
|
|
|
INSP - Carpentry | 10/9/1997 | 10/9/1997 | 10/9/1997 | P | PART |
Carl Dependahl
|
|
|
HP 6 CHILLER BLDG
|
INSP - Final | 10/8/1997 | 10/9/1997 | 10/9/1997 | P | FAIL |
Joe Tawney
|
|
|
10/09/97 406 - HP 6, CHILLER BLDG; JULIO OF K2 WILL CONTACT YOU FINAL FAIL FIRE EXT SUPPORT OF STOP VLVS LABELING OF VLVS
|
INSP - Conference | 9/26/1997 | 9/26/1997 | 9/26/1997 | P | PASS |
Carl Dependahl
|
|
|
09/26/97 340 - CON JULIO
|
INSP - Carpentry | 9/22/1997 | 9/22/1997 | 9/22/1997 | P | PART |
Carl Dependahl
|
|
|
09/22/97 340 - INK JET PROJ. CHILLER.
|
INSP - Carpentry | 9/18/1997 | 9/19/1997 | 9/19/1997 | P | PART |
Carl Dependahl
|
|
|
09/19/97 340 - W/JULIO, K2
|
INSP - Conference | 9/18/1997 | 9/18/1997 | 9/18/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - W/ JULIO RE CHILLER PROJECT.
|
INSP - Carpentry | 7/29/1997 | 7/29/1997 | 7/29/1997 | | PART |
Carl Dependahl
|
|
|
07/29/97 340 - BLDG 6 CHILLERPENDING SPEC INSP REPORTS
|
INSP - Masonry | 7/18/1997 | 7/21/1997 | 7/21/1997 | A | CANC |
Jim Sly
|
|
|
07/18/97 316 - Gave To Carl D.
|
INSP - Masonry | 7/18/1997 | 7/18/1997 | 7/18/1997 | P | PART |
Carl Dependahl
|
|
|
07/18/97 340 - SENT TO SLY IN ERROR, ADDED BY 340 ..SPEC INSP REPORT PEN
|
INSP - Masonry | 7/14/1997 | 7/18/1997 | 7/18/1997 | P | CANC |
Jim Sly
|
|
|
07/17/97 316 - Gave to Carl D.
|
INSP - Masonry | 7/14/1997 | 7/16/1997 | 7/16/1997 | P | CANC |
Jim Sly
|
|
|
07/16/97 316 - Gave to Carl D.
|
INSP - Conference | 7/16/1997 | 7/16/1997 | 7/16/1997 | P | PASS |
Carl Dependahl
|
|
|
W/ JULIO OF K2 RE SPEC INSP REPORTS
|
INSP - Masonry | 7/10/1997 | 7/14/1997 | 7/14/1997 | A | PART |
Carl Dependahl
|
|
|
07/14/97 340 - looks ok, pending spec insp report
|
INSP - Masonry | 7/9/1997 | 7/9/1997 | 7/9/1997 | P | PART |
Carl Dependahl
|
|
|
07/09/97 340 - ###-#### digital pager Julio HP; PENDING SPEC INSP, MET W
|
INSP - Conference | 7/8/1997 | 7/8/1997 | 7/8/1997 | | PASS |
Carl Dependahl
|
|
|
/ / 340 - bldg 6 chiller w/ K-2, Julio
|
INSP - Framing/Rough-in | 7/1/1997 | 7/2/1997 | 7/2/1997 | P | PART |
Carl Dependahl
|
|
|
07/02/97 340 - RE-BAR BLD 6 SLAB; PEND SPEC INSP REPORT
|
INSP - Footings | 7/1/1997 | 7/1/1997 | 7/1/1997 | P | PART |
Carl Dependahl
|
|
|
07/01/97 340 - RE-BAR CHILLER. BLD 6 SOUTH SIDE; PART, PENDING SPEC INSP
|
INSP - Footings | 6/25/1997 | 6/26/1997 | 6/26/1997 | P | CANC |
Tom Arcoraci
|
|
|
WALL
|
INSP - Foundation | 6/24/1997 | 6/25/1997 | 6/25/1997 | P | PART |
Carl Dependahl
|
|
|
06/25/97 340 - pend spec insp report
|
INSP - Footings | 6/24/1997 | 6/25/1997 | 6/25/1997 | P | PART |
Carl Dependahl
|
|
|
06/25/97 340 - REBAR SOUTH SIDE OF BLDG 6
|
INSP - Foundation | 6/24/1997 | 6/24/1997 | 6/24/1997 | A | PART |
Carl Dependahl
|
|
|
CHILLER FND; PENDING SPEC INSP REPORT
|
INSP - Foundation | 6/18/1997 | 6/20/1997 | 6/20/1997 | A | PART |
Carl Dependahl
|
|
|
06/20/97 340 - FND.WALL EARLY A.M.... pend spec insp
|
INSP - Foundation | 6/19/1997 | 6/20/1997 | 6/20/1997 | A | PART |
Carl Dependahl
|
|
|
06/20/97 340 - pend spec insp
|
INSP - Conference | 6/19/1997 | 6/19/1997 | 6/19/1997 | A | PASS |
Carl Dependahl
|
|
|
W/ JULIO OF K-2; RE SPEC INSP.REQ'S...I'D BEEN AT SITE 6-17 & MISSED HIM...WORK APPEARED OK
|
INSP - Foundation | 6/17/1997 | 6/17/1997 | 6/17/1997 | P | PART |
Carl Dependahl
|
|
|
06/17/97 340 - FND. WALL REBAR; PENDING SPEC INSP, LOOKS OK
|
INSP - Foundation | 6/17/1997 | 6/17/1997 | 6/17/1997 | P | PART |
Carl Dependahl
|
|
|
06/17/97 340 - FND WALL REBAR ...FTG NO. & WEST; PENDING SPEC INSP REPOR
|
INSP - Foundation | 6/17/1997 | 6/18/1996 | 6/17/1997 | P | |
Jim Sly
|
|
|
FND. REBAR
|
INSP - Footings | 6/16/1997 | 6/16/1997 | 6/16/1997 | P | CANC |
Jim Sly
|
|
|
06/16/97 316 - Gave to Carl D...
|
Telephone call | | | 6/10/1997 | | |
|
|
|
TALKED TO ED HESS/ PERMIT READY, FEE DUE
|
Issue PAID IN FULL permit | | | 6/10/1997 | | |
|
|
|
|
Print Occupancy Form | | | 6/10/1997 | | |
|
|
|
|
Routing - PLAN CHECK | 6/9/1997 | | 6/10/1997 | | PASS |
|
|
|
|
Inspection Record Card- Bld | | | 6/10/1997 | | |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 6/10/1997 | | PASS |
|
|
|
|
Plan assigned to (DRS) | 3/5/1997 | | 6/10/1997 | | PASS |
Dan Stuart
|
|
|
06/10/97 08:33:18 DRS - this action updated by action script from <<>> in Case No. BLD97-0494
|
Routing - FIRE | 6/3/1997 | | 6/9/1997 | | PASS |
|
|
|
|
Plan resubmittals received | | | 6/9/1997 | | |
|
|
|
Architect & Structural Engineer came over and stamped the previously submitted sheet for exit stair design.
|
90 day tracking............. | | 3/5/1997 | 6/3/1997 | | PEND |
|
|
|
|
Routing - PLANNING | 5/28/1997 | | 6/2/1997 | | PASS |
|
|
|
Approved by: TKW
|
Routing - PUBLIC WORKS | 5/21/1997 | | 5/28/1997 | | PASS |
|
|
|
|
Plan resubmittals received | | | 5/27/1997 | | |
|
|
|
Received written response from architect that he has reviewed the plan review requirements & will comply and provide direction to contractor. Also stipulated the special inspection agency and requirements.
|
Telephone call | | | 5/21/1997 | | |
|
|
|
Have received calls from Ed Hess one or more times a week since middle of April to check on progress of plans and permit status. He requests that I call him at any change of status. This generally is a message left on his machine.
|
Print Pending Permit.LaserJet4 | | | 5/21/1997 | | PEND |
|
|
|
Routing to Fire, PW & Zoning for review & approval.
|
Plan resubmittals requested | | | 5/21/1997 | | PEND |
|
|
|
Finished preliminary review. Faxed and mailed comments to John Maulin, CSHQA for response. Routing to Fire , PW & PZ for review and approval.
|
Routing Off Site - STRUCTURAL | 5/14/1997 | | 5/20/1997 | | PASS |
|
|
|
Resubmittal from John Maulin, CSHQA, in response to structural review of 5/8/97, routed back to Atwood- Hinzman-Jones for review and approval. Revieved plans back with note that response & resubmittals are approved on 5/20/97.
|
Routing - PLAN CHECK | 5/15/1997 | | 5/20/1997 | | PEND |
|
|
|
Routed resubmittal for structural review back to Atwood, Hinsman & Jones. Called Scott to let him know they were coming and to ask for return of second set of plans. Plans have not been signed off buy P&Z nor routed to PW. Sent preliminary review comments to architect for response. Checked with Dave Miller, Fire Dept Plan Reviewer to see if he wanted to see the plans - he did. Routing to P&Z, PW & Fire Dept.
|
Routing - PLAN CHECK | 5/8/1997 | | 5/15/1997 | | |
|
|
|
Received resubmittals from CSHQA for structural engineering comments. Routing back to engineer for review.
|
Plan resubmittals received | | | 5/12/1997 | | |
|
|
|
Received response to structural review, new sheet A-1, engineers calc/design sheet and the engineer's stamp on calcs & plan. Routing to structural engineer for re-review.
|
Telephone call | | | 5/12/1997 | | |
|
|
|
Call to John Maulin concerning progress on response to structural review comments. Said plans were at HP and they were working on submittals then plans will come back to CSHQA Engineer, Michael Brown, for review and comment then back to city. Thought we should have plans back on the 13th.
|
Plan resubmittals requested | | | 5/8/1997 | | |
|
|
|
Received plan & comment back from Attwood- Hinzman- Jones with comments needing response. Faxed copy to John Maulin for response.
|
Routing Off Site - STRUCTURAL | 4/21/1997 | | 5/8/1997 | | FAIL |
|
|
|
SENT 2 SETS OF PLANS TO ATWOOD, HINZMAN, JONES FOR STRUCTURAL REVIEW. DAR 5/8/97 - reveived comments from structural plan reviewer with items needing addressed by CSHQA. Faxed copy to John Maulin for response.
|
Routing - PLAN CHECK | 3/13/1997 | | 4/10/1997 | | |
|
|
|
REQUIRES DESIGN REVIEW BY PLANNING AND ZONING. 5/31/97 - DR-50-97 Conditions of Approval issued to Ed Hess, HP Chiller Project. Appeal period end at 5:00 p.m. on April 10 1997.
|
Routing - PLANNING | 3/6/1997 | | 3/12/1997 | | FAIL |
|
|
|
Requires Design Review approval. Contacted John Maulin Architect. Reviewed by MGH.
|
Plan routing begun/TENANTS | | | 3/6/1997 | | |
|
|
|
Route to PLANNING, to STRUCTURAL ENGINEER, to PUBLIC WORKS then back to PLAN CHECK. Provide a copy of plan review and permit to Fire Department.
|
Application received | | | 3/5/1997 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 3/5/1997 | | |
|
|
|
|