Fee Review-notes | 7/14/1998 | | 9/10/1998 | | |
|
|
|
|
Plan resubmittals received | | | 7/10/1998 | | |
|
|
|
RECEIVED 1 COPY OF PHOTO OF KITCHEN EXHAUST HOOD 1 COPY OF 3M FIREMASTER PRODUCT LITERATURE (3 PG) ROUTED TO RICK JACKSON
|
INSP - Final | 1/26/1998 | 1/26/1998 | 1/26/1998 | P | PASS |
|
|
|
01/26/98 333 - CARD SIGNED FOR PERM PHASE 1
|
Permanent Occupancy | | 1/26/1998 | 1/26/1998 | | DONE |
|
|
|
|
Permanent occupancy | | | 1/26/1998 | | PASS |
|
|
|
Perm. Occ. Cert. #7112 issued 1-26-98 to the Boise Senior Center for the addn.
|
INSP-Final Inspection | 1/20/1998 | 1/20/1998 | 1/20/1998 | P | PASS |
Rick Jackson
|
|
|
Phase 1 completed. strobe device relocated and functional. c/o approved - card not on-site to sign.
|
INSP-Final Inspection | 1/13/1998 | 1/13/1998 | 1/13/1998 | P | PART |
Rick Jackson
|
|
|
tested alarms - pass. kitchen extinguishing system, outside sprinkler control valve and monitoring to be part of Phase 2 permit. dampers in corridor functioned properly
|
INSP-Final Inspection | 1/9/1998 | 1/9/1998 | 1/9/1998 | P | NR |
Rick Jackson
|
|
|
alarms not ready. sprinkler riser/PIV not monitored.
|
INSP - Final | 1/8/1998 | 1/9/1998 | 1/9/1998 | P | PASS |
|
|
|
01/09/98 333 - OTH-OTHER AGENCIES NOT APPROVED
|
INSP-Final Inspection | 1/7/1998 | 1/8/1998 | 1/9/1998 | P | PART |
Rick Jackson
|
|
|
01/08/98 409 - he will call you. checked devices/placement. will test in 1/9/98
|
INSP - Final | 1/7/1998 | 1/8/1998 | 1/8/1998 | P | FAIL |
|
|
|
01/08/98 333 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
|
INSP-Sprinkler Rough-in/Hydro | 12/16/1997 | 12/16/1997 | 12/16/1997 | A | PASS |
Rick Jackson
|
|
|
hydro test of anti-freeze system
|
INSP - Framing/Rough-in | 12/16/1997 | 12/16/1997 | 12/16/1997 | P | PASS |
|
|
|
12/16/97 333 - BOISE SENIOR CENTER/ LAST PARTIAL OF CH STUD CEILING. WOULD LIKE AROUND 4:00 ceiling ok will check firestops later
|
INSP - Framing/Rough-in | 12/11/1997 | 12/11/1997 | 12/11/1997 | P | PART |
|
|
|
12/11/97 333 - CLG -OK CEILING COVER
|
INSP-Sprinkler Rough-in/Hydro | 12/10/1997 | 12/11/1997 | 12/11/1997 | P | CANC |
Rick Jackson
|
|
|
12/11/97 409 - ANTI-FREEZE FLUSH--PAGE DOUG AT ###-#### TO MEET YOU doug didn't answer page at 4:00 pm.
|
INSP-Final Inspection | 12/4/1997 | 12/5/1997 | 12/5/1997 | P | PASS |
Rick Jackson
|
|
|
after 1:00 Doug ###-#### sprinkler hydro only - passed. not a final inspection for occupancy
|
INSP - Framing/Rough-in | 12/2/1997 | 12/3/1997 | 12/3/1997 | A | PASS |
|
|
|
12/03/97 333 - ch studs in phase 1 senior center corridor ceilings ok
|
INSP - Framing/Rough-in | 11/13/1997 | 11/14/1997 | 11/14/1997 | A | PASS |
|
|
|
11/14/97 333 - late am FRAM-OK FRAMING
|
INSP - Framing/Rough-in | 11/12/1997 | 11/12/1997 | 11/12/1997 | P | PART |
|
|
|
11/12/97 333 - one side only
|
INSP - Roof | 11/6/1997 | 11/7/1997 | 11/7/1997 | A | PASS |
|
|
|
11/07/97 333 - ok
|
INSP - Framing/Rough-in | 10/31/1997 | 11/3/1997 | 11/3/1997 | A | PASS |
|
|
|
11/03/97 333 - roof ok to cover
|
INSP - Roof | 10/28/1997 | 10/28/1997 | 10/28/1997 | P | PASS |
|
|
|
10/28/97 333 - mansard ok
|
INSP - Conference | 10/23/1997 | 10/23/1997 | 10/23/1997 | P | PASS |
|
|
|
10/23/97 333 - ok on soffit detail
|
INSP - Carpentry | 10/10/1997 | 10/10/1997 | 10/10/1997 | A | PASS |
|
|
|
10/10/97 333 - resubmittal
|
INSP - Foundation | 10/9/1997 | 10/9/1997 | 10/9/1997 | P | PASS |
|
|
|
10/09/97 333 - STEM WALL FDN -OK FOUNDATION
|
INSP - Footings | 10/8/1997 | 10/8/1997 | 10/8/1997 | P | PASS |
|
|
|
10/08/97 333 - FTG -OK FOOTING
|
Issue PAID IN FULL permit | | | 9/25/1997 | | |
|
|
|
|
Plan assigned to (M_P) | 6/20/1997 | | 8/19/1997 | | PASS |
Mike Phillips
|
|
|
08/19/97 13:38:16 DAR - this action updated by action script from <<>> in Case No. BLD97-0876
|
PLANS/APPL TAKEN TO FRONT DESK | | | 8/19/1997 | | PASS |
|
|
|
|
Print Occupancy Form | | | 8/19/1997 | | |
|
|
|
|
Inspection Record Card- Bld | | | 8/19/1997 | | |
|
|
|
|
Print Pending Permit.LaserJet4 | | | 8/19/1997 | | PASS |
|
|
|
NEED CONTRACTOR INFORMATION.
|
Plan Reviewer's activity | | | 8/19/1997 | | PASS |
|
|
|
NEED CONTRACTOR.
|
Telephone call | | | 8/19/1997 | | |
|
|
|
CALLED DEAN..PERMIT READY
|
Plan resubmittals received | | | 8/14/1997 | | |
|
|
|
Received plan resubmittals.
|
Routing - MECHANICAL | | | 7/15/1997 | | PASS |
|
|
|
PACKAGE #1 FIELD REVIEW.
|
Routing - FIRE | 7/1/1997 | | 7/14/1997 | | PASS |
|
|
|
PACKAGE #1
|
90 day tracking............. | | 4/10/1997 | 7/9/1997 | | |
|
|
|
|
Print Pending Permit.LaserJet4 | | | 6/30/1997 | | FAIL |
|
|
|
SENT CORRECTION LIST
|
Plan Reviewer's activity | | | 6/30/1997 | | FAIL |
|
|
|
sent correction list to architect.
|
Plan assigned to (RGG) | 5/30/1997 | | 6/20/1997 | | |
|
|
|
|
Routing Off Site - A.C.H.D | 6/2/1997 | | 6/11/1997 | | PASS |
|
|
|
PACKAGE #4 CONTACTED DEAN SHULTZ AT ###-#### TO TAKE PLANS OUT TO ACHD. NO IMPACT FEES DUE.
|
Routing - PLANNING | 6/6/1997 | | 6/11/1997 | | PASS |
|
|
|
PACKAGE #2 X-REF: AA-37-97, CU-87-78, FPR-10-95. APPROVED BY BB.
|
Routing - PUBLIC WORKS | 6/2/1997 | | 6/6/1997 | | PASS |
|
|
|
PACKAGE #2
|
Routing - ELECTRICAL | 6/4/1997 | | 6/6/1997 | | PASS |
|
|
|
PACKAGE #1 FIELD VERIFY PER 324.
|
Routing Off Site - STRUCTURAL | 6/2/1997 | | 6/4/1997 | | PEND |
|
|
|
PACKAGE #3 CONTACTED PDQ TO TAKE PLANS OUT TO STAPLEY ENGINEERING CORRECTION LIST RETURNED, FOLLOW UP REVIEW WILL BE DONE BY PLAN REVIEWER AT CITY.
|
Routing - PLUMBING | 6/2/1997 | | 6/4/1997 | | PASS |
|
|
|
PACKAGE #1
|
Plan routing begun/NEW & ADDTN | | | 6/2/1997 | | PASS |
|
|
|
|
Plans ACCEPTED BY PLAN CHECK | | | 5/30/1997 | | PASS |
|
|
|
PROJECT RECEIVED CUMOD #37-97. RECEIVED ADDITIONAL SET FOR PACKAGE #3 4-11-97.
|
Gay Receipt For Partial Pay | | | 5/8/1997 | | |
|
|
|
|
FEE REVIEW-NOTES | | | 4/14/1997 | | FEES |
|
|
|
HAD PAID PLAN CHECK. AND BEFORE DEPOSIT THEY TOOK CHECK BACK. TOOK FEES OUT LH
|
Plans ACCEPTED BY PLAN CHECK | | | 4/11/1997 | | HOLD |
|
|
|
PLANS ARE ON HOLD AWAITING CONFIRMATION FROM P&Z AS TO A DR OR CU BEING REQUIRED. PACKAGE #3 REQUIRES AN ADDITIONAL SET. A SIGNED CERT. OF VALUE IS REQUIRED. I CONTACTED DEAN SHULTZ OF THESE NEEDS AT ###-#### KMM ROBERT HOBBS OF P&Z SAID PLANS REQUIRE A STAFF LEVEL CU MOD. HE CONTACTED DEARN SHULTZ AND TOLD HIM OF THIS NEED. KMM 4-11-97 AMY OF FINANCE CAME UP AND PUT A HOL ON THIS PROJECT. WAY OVER BUDGET, WILL CONTACT MAYORS OFFICE TO SEE IF MORE MONEY IS AVAILABLE OR IF THE PROJECT HAS BEEN DOWNSIZED. DAR 4/11/97
|
Plan routing begun/NEW & ADDTN | | | 4/11/1997 | | HOLD |
|
|
|
SEE ACTION 007
|
Received Certificate of Value | | | 4/11/1997 | | FAIL |
|
|
|
CERT. OF VALUE NEEDS TO BE SIGNED. I CONTACTED DEAN SHULTZ AT ###-#### AND TOLD HIM OF THIS NEED. KMM
|
Received Certificate of Value | | | 4/11/1997 | | PASS |
|
|
|
DEAN SIGNED CERT. OF VALUE.
|
Application received | | | 4/10/1997 | | |
|
|
|
|
Routing - PLAN CHECK | 6/11/1997 | | | | |
|
|
|
PACKAGE #4 NO ACHD FEES DUE.
|
Routing - PLAN CHECK | 6/13/1997 | | | | |
|
|
|
PACKAGE #2
|
Routing - PLAN CHECK | 7/15/1997 | | | | |
|
|
|
PACKAGE #1
|