Case Summary (BLD) | | | 3/14/2013 | | DONE |
|
|
|
|
Print Occupancy Form | | | 3/14/2013 | | DONE |
|
|
|
|
Case Summary (BLD) | | | 3/14/2013 | | DONE |
|
|
|
|
Print Occupancy Form | | | 2/28/2013 | | DONE |
Christina Prado
|
|
|
|
Case Summary (BLD) | | | 1/10/2002 | | DONE |
|
|
|
|
INSP-Conference | 9/22/1998 | 9/22/1998 | 9/22/1998 | | PART |
Joe Tawney
|
|
|
/ / 406 - CONF W/ MITCH MILES CONTR ON REMAINING ITEMS FOR PERM OCC
|
INSP-Final Inspection | 6/18/1998 | 6/19/1998 | 6/19/1998 | A | CANC |
Joe Tawney
|
|
|
06/19/98 406 - Scheduled by Hello!. Contact phone is [3717146]. CANCEL SHOULD HAVE BEEN STRUCTURAL INSPECTION
|
INSP-Final Inspection | 6/16/1998 | 6/16/1998 | 6/16/1998 | P | PART |
Joe Tawney
|
|
|
06/16/98 406 - Scheduled by Hello!. Contact phone is [3717146]. REINSP OK FOR TEMP OCC FOR ENTIRE FACILITY
|
INSP-Final Inspection | 6/11/1998 | 6/12/1998 | 6/12/1998 | A | FAIL |
Joe Tawney
|
|
|
06/12/98 406 - Scheduled by Hello!. Contact phone is [4241922]. REINSP FAIL S/F DAMPERS OK MOVE ONE DETECTOR
|
INSP-Final Inspection | 6/10/1998 | 6/11/1998 | 6/12/1998 | P | CANC |
Joe Tawney
|
|
|
06/11/98 406 - Scheduled by Hello!. Contact phone is [4241922]. CANCELLED
|
INSP-Final Inspection | 6/3/1998 | 6/3/1998 | 6/3/1998 | P | CANC |
Joe Tawney
|
|
|
06/03/98 406 - Scheduled by Hello!. Contact phone is [3717146]. CANCEL
|
INSP-Final Inspection | 6/1/1998 | 6/2/1998 | 6/3/1998 | A | PART |
Joe Tawney
|
|
|
06/02/98 406 - Scheduled by Hello!. Contact phone is [3717146]. REINSP OK FOR TEMP OCC OF OFFICE AREA ONLY
|
DOC - T/O Approved | 6/2/1998 | 6/2/1998 | 6/2/1998 | | PART |
Jim Storey
|
|
|
/ / 301 - OFFICE ONLY SEPRATE OCC CARD SIGNED AND ONSITE. SHOP AREA NO
|
INSP-Final Inspection | 5/29/1998 | 6/1/1998 | 6/1/1998 | P | FAIL |
Joe Tawney
|
|
|
05/31/98 406 - Scheduled by Hello!. Contact phone is [3717146]. REINSP FAIL ALARM SYSTEM
|
Print Occupancy Form | | | 6/1/1998 | | |
|
|
|
|
INSP-Final Inspection | 5/27/1998 | 5/28/1998 | 5/28/1998 | P | FAIL |
Joe Tawney
|
|
|
05/28/98 406 - Mitch ###-#### FINAL FAIL SPKLR MONITORING BLDG ADDRESS EXIT SIGNS EXIT DOORS
|
Code Occupancy Approval | | | 5/28/1998 | | PASS |
|
|
|
SITE INSPECTION SHOWED TREES AND HYDROSEEDING IN, PARKING LOT IS OK PER PLANS, FINAL SIGNED OFF.
|
INSP - Wall cover | 5/12/1998 | 5/12/1998 | 5/12/1998 | P | PART |
Jim Storey
|
|
|
05/12/98 301 - CORR-CORREC-CALL FOR REINSP WHEN COMPLETED
|
INSP-Sprinkler Rough-in/Hydro | 4/27/1998 | 4/27/1998 | 4/27/1998 | | PART |
Joe Tawney
|
|
|
/ / 406 - OK ON SPKLR HYDRO TEST ADD HEAD UNDER STAIRS AND ADDRESS CAN
|
INSP - Wall cover | 4/20/1998 | 4/22/1998 | 4/22/1998 | A | PART |
Jim Storey
|
|
|
04/22/98 301 - ceilling ok for tile
|
INSP-Sprinkler Rough-in/Hydro | 4/9/1998 | 4/9/1998 | 4/9/1998 | | PART |
Joe Tawney
|
|
|
/ / 406 - OK ON UNDERGROUND HYDRO TEST
|
INSP-Supply line flush | 4/9/1998 | 4/9/1998 | 4/9/1998 | | PART |
Joe Tawney
|
|
|
/ / 406 - OK ON UNDERGROUND FLUSH
|
INSP - Framing/Rough-in | 3/24/1998 | 3/25/1998 | 3/25/1998 | P | PART |
Jim Storey
|
|
|
03/25/98 301 - ###-#### he says you told him around 2:00 conf ok resubmtal recieved
|
INSP - Framing/Rough-in | 3/18/1998 | 3/19/1998 | 3/20/1998 | A | PASS |
Jim Storey
|
|
|
03/20/98 301 - CRAC-PRMT CANCLD BY APPLIC/CONTR REQ
|
INSP - Mono pour | 3/6/1998 | 3/6/1998 | 3/6/1998 | | PART |
Jim Storey
|
|
|
/ / 301 - WIP -WORK IN PROGRESS special insp. pasted pending report unable to insp call for insp.
|
INSP - Framing/Rough-in | 2/12/1998 | 2/13/1998 | 2/13/1998 | A | PASS |
|
|
|
02/13/98 338 - -BUS STATION--BRIAN ###-#### on the office interior ok to
|
INSP - Framing/Rough-in | 1/23/1998 | 1/26/1998 | 1/26/1998 | A | PASS |
Jim Storey
|
|
|
01/26/98 301 - REBAR ###-#### MITCH FRMS-OK FORMS-REBAR
|
INSP - Framing/Rough-in | 1/21/1998 | 1/22/1998 | 1/22/1998 | A | PASS |
Jim Storey
|
|
|
01/22/98 301 - OFFICE ONLY\MITCH ###-#### FRAM-OK FRAMING center office ok to hang gyp. for sound wall.
|
INSP - Framing/Rough-in | 1/20/1998 | 1/20/1998 | 1/21/1998 | P | NR |
Russ Owen
|
|
|
01/20/98 407 - slab covered not ready for inspection. might have special
|
INSP - Framing/Rough-in | 1/13/1998 | 1/13/1998 | 1/13/1998 | P | PASS |
Jim Storey
|
|
|
01/13/98 301 - concrete flat work. ###-####-Mitch Miles. slab on grade ok as per plan
|
INSP - Framing/Rough-in | 12/31/1997 | 1/5/1998 | 1/5/1998 | A | PASS |
Jim Storey
|
|
|
01/05/98 301 - masonary block MASN-REBAR OK
|
INSP - Framing/Rough-in | 12/30/1997 | 12/30/1997 | 12/30/1997 | P | PART |
Jim Storey
|
|
|
12/30/97 301 - concrete wall s/i on site pending report ì
|
INSP - Framing/Rough-in | 12/22/1997 | 12/23/1997 | 12/23/1997 | P | PASS |
Jim Storey
|
|
|
12/23/97 301 - MASN-REBAR OK
|
INSP - Wall cover | 12/22/1997 | 12/22/1997 | 12/23/1997 | P | CANC |
Russ Owen
|
|
|
12/22/97 407 - CONCRETE BLOCK WALL,unable to do gave to jim.
|
INSP - Framing/Rough-in | 12/18/1997 | 12/19/1997 | 12/19/1997 | A | PASS |
Jim Storey
|
|
|
12/19/97 301 - recieved approval from arch/engineer that over height gro robertson @ morrison knudsen.
|
INSP - Miscellaneous | 12/17/1997 | 12/17/1997 | 12/18/1997 | P | FAIL |
Jim Storey
|
|
|
12/18/97 301 - grouted w/o engineering approval to do so over 5ft
|
INSP - Miscellaneous | 12/15/1997 | 12/16/1997 | 12/16/1997 | A | FAIL |
Jim Storey
|
|
|
12/16/97 301 - BOISE URBAN STAGES/ MASONARY BLOCK WALL CORR-CORREC-CALL FOR REINSP WHEN COMPLETED provide clean outs for grout over 4 ft. or provide engineering aproval.
|
(F) Reprint permit | | | 11/24/1997 | | |
|
|
|
|
Inspection Record Card- Bld | | | 11/21/1997 | | |
|
|
|
|
Telephone call | | | 11/21/1997 | | |
|
|
|
LEFT MESSAGE ON JAKE'S VOICE MAIL - PERMIT READY
|
Print Occupancy Form | | | 11/21/1997 | | |
|
|
|
|
Inspection Record Card- Bld | | | 11/21/1997 | | |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/21/1997 | | PASS |
|
|
|
|
Issue PAID IN FULL permit | | | 11/21/1997 | | |
|
|
|
|
Plan assigned to (M_O) | 7/16/1997 | | 11/20/1997 | | PASS |
|
|
|
|
Routing Off Site - STRUCTURAL | 10/29/1997 | | 11/19/1997 | | PASS |
|
|
|
REVISED PLANS SENT OUT TO CH2MHILL VIA PDQ 11-17-97 STRUCTURAL REVIEW LETTER BY CH2MHILL DATED 11-14-97 ORIGINAL REVIEW RESPONSES REVISED ARCHITECTURAL DRAWINGS AND STRUCTURAL DRAWINGS (1 SET) METAL BUILDING DRAWINGS (1 SET) METAL BUILDING STRUCTURAL CALCULATIONS (1SET) ALL ABOVE ITEMS RETURNED 11-17-97 CORRECTIONS MAILED AND FAXED TO ARCHITECT 11-17-97. MO RESPONSE RECEIVED FROM ARCHITECT RESOLVING CORRECTIONS. 11-19-97. MO
|
Plan resubmittals received | | | 11/19/1997 | | PASS |
|
|
|
RESPONSE TO STRUCTURAL CORRECTIONS RECEIVED. MO
|
Plan resubmittals requested | | | 11/17/1997 | | FAIL |
|
|
|
CORRECTIONS FROM CH2MHILL FAXED AND MAILED TO ARCHITECT ON 11-17-97. MO
|
Routing - PLAN CHECK | 10/29/1997 | | 10/31/1997 | | PASS |
|
|
|
|
Plan resubmittals received | | | 10/29/1997 | | PEND |
|
|
|
PLAN RESUBMITTALS FOR ARCHITECTURAL AND STRUCTURAL RECEIVED 10-29-97.MO
|
90 day tracking............. | | 6/18/1997 | 9/16/1997 | | |
|
|
|
|
Routing - PLANNING | 7/14/1997 | | 8/4/1997 | | PASS |
|
|
|
PACKAGE #2 X-REF: CU-47-94. APPROVED BY RC.
|
Routing - FIRE | 7/23/1997 | | 7/28/1997 | | PASS |
|
|
|
PACKAGE #1
|
Plan resubmittals requested | | | 7/23/1997 | | FAIL |
|
|
|
corrections sent to architect 7-23-97. MO
|
Routing - PLAN CHECK | 7/16/1997 | | 7/23/1997 | | FAIL |
|
|
|
corrections mailed and faxed to architect. MO
|
Plan assigned to (RGG) | 6/23/1997 | | 7/16/1997 | | |
|
|
|
|
Routing Off Site - A.C.H.D | 6/23/1997 | | 7/16/1997 | | PASS |
|
|
|
PACKAGE #4 CONTACTED DICK ROBERTSON AT ###-#### TO TAKE PLANS OUT TO ACHD. NO IMPACT FEES DUE PER MARKUS GREEN AT ACHD.
|
Routing - PUBLIC WORKS | 6/23/1997 | | 7/14/1997 | | PASS |
|
|
|
PACKAGE #2
|
Routing Off Site - STRUCTURAL | 6/23/1997 | | 7/11/1997 | | FAIL |
|
|
|
PACKAGE #3 CONTACTED PDQ TO TAKE PLANS OUT TO CH2MHILL
|
Routing - ELECTRICAL | 7/3/1997 | | 7/9/1997 | | PASS |
|
|
|
PACKAGE #1
|
Routing - PLUMBING | 6/23/1997 | | 6/30/1997 | | PASS |
|
|
|
PACKAGE #1
|
(F) Reprint permit | | | 6/24/1997 | | |
|
|
|
|
Plans ACCEPTED BY PLAN CHECK | | | 6/23/1997 | | PASS |
|
|
|
|
Received Certificate of Value | | | 6/23/1997 | | PASS |
|
|
|
|
Plan routing begun/NEW & ADDTN | 6/23/1997 | | 6/23/1997 | | PASS |
|
|
|
GAVE DICK AN H-OCCUPANCY TO FILL OUT FOR PACKAGE #1. 6-25-97 RECEIVED AN H-OCCUPANCY. PUT IN WALL FILE UNTIL I RECEIVE PACKAGE #1 BACK FROM ROUTING. KMM
|
Plan assigned to (MYS) | 6/18/1997 | | 6/23/1997 | | |
Marlene Southard
|
|
|
|
Application received | | | 6/18/1997 | | |
|
|
|
|