Code Occupancy Approval | | | 5/21/1998 | | PASS |
|
|
|
Cathy asked me to inspect - no place on Occupancy Card ref: Planning - DR-29-97. Inspected - complies w/DR - Pass (CAM).
|
Permanent occupancy | | | 5/21/1998 | | PASS |
|
|
|
Perm. Occ. Cert. #7257 issued 5-21-98 to Pojo's.
|
Permanent Occupancy | | 5/20/1998 | 5/20/1998 | | DONE |
|
|
|
|
INSP - Final | 5/18/1998 | 5/19/1998 | 5/19/1998 | P | PASS |
Jim Sly
|
|
|
05/19/98 316 - OK for perm OCC.
|
INSP-Final Inspection | 5/13/1998 | 5/14/1998 | 5/14/1998 | P | FAIL |
Joe Tawney
|
|
|
05/14/98 406 - ###-#### REINP FAIL NEED INFO ON HOOD AND DUCT DETECTOR
|
INSP - Framing/Rough-in | 2/4/1998 | 2/5/1998 | 2/5/1998 | A | PART |
Jim Sly
|
|
|
02/04/98 316 - framing for towers Ext. front....OK
|
Temporary occupancy | | | 1/13/1998 | | PASS |
|
|
|
Temp. Occ. Cert. 3534 issued 1-13-98 to Pojo's (addn.)
|
INSP-Final Inspection | 1/9/1998 | 1/12/1998 | 1/12/1998 | A | PASS |
Joe Tawney
|
|
|
01/12/98 406 - PoJo's Rod Hunt ###-#### REINSP OK FOR TEMP OCC SPKLR IN COOLER DUCT DET DOOR HDWRE HOOD CURBS
|
INSP - Final | 1/9/1998 | 1/12/1998 | 1/12/1998 | A | FAIL |
Jim Sly
|
|
|
01/09/98 316 - C/N...Need required signatures..
|
INSP - Final | 1/12/1998 | 1/12/1998 | 1/12/1998 | | PASS |
Jim Sly
|
|
|
/ / 316 - Temp Occ.
|
INSP - Final | 1/9/1998 | 1/9/1998 | 1/9/1998 | P | NR |
Jim Sly
|
|
|
01/09/98 316 - Cancelled by owner....
|
INSP-Conference | 1/7/1998 | 1/7/1998 | 1/7/1998 | P | PASS |
Joe Tawney
|
|
|
/ / 406 - CONF ON CONNECTING COOK HOOD EXT SYSTEM TO ALARM SYSTEM
|
INSP - Final | 1/6/1998 | 1/6/1998 | 1/6/1998 | | FAIL |
Joe Tawney
|
|
|
/ / 406 - ALARM SYSTEM TEST FAIL NO APPR SUB ON SITE DUCT DET & FIRE D
|
INSP - Final | 1/6/1998 | 1/6/1998 | 1/6/1998 | | FAIL |
Joe Tawney
|
|
|
/ / 406 - ALARM SYSTEM TEST FAIL NO APPR SUB ON SITE DUCT DET & FIRE D
|
INSP - Final | 12/30/1997 | 1/6/1998 | 1/6/1998 | A | NR |
Jim Sly
|
|
|
01/05/98 316 - Not Ready.
|
INSP - Framing/Rough-in | 12/18/1997 | 12/19/1997 | 12/19/1997 | A | PART |
Jim Sly
|
|
|
12/18/97 316 - pojo column pads S.W Addition...OK pending special insp a
|
INSP - Framing/Rough-in | 12/12/1997 | 12/15/1997 | 12/15/1997 | A | PART |
Jim Sly
|
|
|
12/12/97 316 - Framing of East addition OK
|
INSP-Final Inspection | 12/11/1997 | 12/12/1997 | 12/12/1997 | A | PART |
Rick Jackson
|
|
|
12/12/97 409 - rough in of new dining addition okay
|
INSP - Framing/Rough-in | 12/11/1997 | 12/12/1997 | 12/12/1997 | A | FAIL |
Jim Sly
|
|
|
12/11/97 316 - C/N..Arch to supply detail for light penitrations in 1hr
|
INSP - Framing/Rough-in | 12/2/1997 | 12/2/1997 | 12/2/1997 | P | NR |
Tom Arcoraci
|
|
|
POJO'S no elec inspec will recall
|
INSP - Miscellaneous | 12/1/1997 | 12/1/1997 | 12/1/1997 | P | PASS |
Jim Sly
|
|
|
12/01/97 316 - pojo's fire shaft For Class A hood OK
|
INSP - Conference | 11/6/1997 | 11/7/1997 | 11/7/1997 | A | PASS |
Jim Sly
|
|
|
11/06/97 316 - Discussed issues on type 5 1hr bld....
|
INSP - Framing/Rough-in | 11/7/1997 | 11/7/1997 | 11/7/1997 | P | PASS |
Jim Sly
|
|
|
11/07/97 316 - POJO'S OK to Cover South bay addition only.
|
INSP - Framing/Rough-in | 10/27/1997 | 10/27/1997 | 10/27/1997 | P | PART |
Jim Sly
|
|
|
10/27/97 316 - Partial insp only..Kitch ceiling and firdowns OK only...
|
INSP-Sprinkler Rough-in/Hydro | 10/21/1997 | 10/22/1997 | 10/22/1997 | A | PART |
Joe Tawney
|
|
|
10/22/97 406 - POJO'S OK ON SPKLR ROUGH IN FOR KITCHEN AREA
|
INSP - Framing/Rough-in | 10/20/1997 | 10/21/1997 | 10/21/1997 | A | FAIL |
Jim Sly
|
|
|
10/20/97 316 - Arch to submit firestop assemb for 1hr rated constr....
|
INSP - Wall cover | 10/14/1997 | 10/14/1997 | 10/14/1997 | P | PART |
Jim Sly
|
|
|
10/14/97 316 - STEM WALL OK pending special inspection and approval...
|
INSP - Footings | 10/13/1997 | 10/13/1997 | 10/13/1997 | P | PART |
Jim Sly
|
|
|
10/13/97 316 - OK pending spec insp and approval...
|
INSP - Foundation | 10/6/1997 | 10/7/1997 | 10/7/1997 | A | PART |
Jim Sly
|
|
|
10/07/97 316 - REBAR FOR STEM WALL East side OK pending special insp app
|
INSP - Footings | 10/3/1997 | 10/6/1997 | 10/6/1997 | A | PART |
Jim Sly
|
|
|
10/06/97 316 - Footings East Wall OK pending special inspection and appr
|
INSP - Footings | 10/1/1997 | 10/1/1997 | 10/1/1997 | P | PART |
Jim Sly
|
|
|
10/01/97 316 - STEMWALL At Carousel..OK pending spec insp and approval.
|
INSP - Footings | 9/29/1997 | 9/29/1997 | 9/29/1997 | P | PART |
Jim Sly
|
|
|
09/29/97 316 - POJO'S Special inspection Req...Foot carousell area OK pe
|
Inspection Record Card- Bld | | | 9/26/1997 | | |
|
|
|
|
Telephone call | | | 9/26/1997 | | |
|
|
|
CALLED TRENT PERMIT READY
|
Issue PAID IN FULL permit | | | 9/26/1997 | | |
|
|
|
|
Print Occupancy Form | | | 9/26/1997 | | |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/26/1997 | | PASS |
|
|
|
|
Routing - PLAN CHECK | 9/22/1997 | | 9/25/1997 | | PASS |
|
|
|
|
Print Pending Permit.LaserJet4 | | | 9/25/1997 | | PASS |
|
|
|
|
Plan assigned to (R_H) | 9/3/1997 | | 9/25/1997 | | PASS |
|
|
|
09/25/97 15:04:29 R_H - this action updated by action script from <<>> in Case No. BLD97-1808
|
90 day tracking............. | | 6/25/1997 | 9/23/1997 | | |
|
|
|
|
Routing - FIRE | 9/8/1997 | | 9/12/1997 | | PASS |
|
|
|
|
Plan Reviewer's activity | | | 9/5/1997 | | FAIL |
|
|
|
Faxed required corrections to Architect/Billy Ray, needed one-hour construction and modifications to one-hour shaft duct enclosure.
|
Routing - ELECTRICAL | 8/24/1997 | | 9/3/1997 | | PASS |
|
|
|
FIELD VERIFY
|
Plan assigned to (RGG) | 6/27/1997 | | 9/3/1997 | | PASS |
|
|
|
|
Routing - PLUMBING | 8/21/1997 | | 8/22/1997 | | PASS |
|
|
|
|
Routing Off Site - C.D.H | 8/7/1997 | | 8/20/1997 | | PASS |
|
|
|
CONTACTED TRENT KOCI AT ###-#### TO TAKE PLANS OUT TO CDH PLANS NOT SIGNED AT CDH. CONTACTED TRENT TO TAKE PLANS OUT TO CDH FOR THEM TO SIGN OFF. 8-18-97
|
Routing - PUBLIC WORKS | 8/12/1997 | | 8/15/1997 | | PASS |
|
|
|
|
Routing - PLANNING | 8/7/1997 | | 8/12/1997 | | PASS |
|
|
|
X-REF: DRH97-0029. APPROVED BY MGS.
|
Routing Off Site - A.C.H.D | 6/27/1997 | | 8/7/1997 | | PEND |
|
|
|
CONTACTED TRENT KOCI AT###-#### TO TAKE PLANS OUT TO ACHD ACHDFEES NOT PAID.
|
Plans ACCEPTED BY PLAN CHECK | | | 6/27/1997 | | PASS |
|
|
|
|
Plan assigned to (MYS) | 6/25/1997 | | 6/27/1997 | | PEND |
Marlene Southard
|
|
|
|
Plan routing begun/NEW & ADDTN | | | 6/27/1997 | | PASS |
|
|
|
ROUTE TO CDH, THEN PW, PLUMB., P&Z, ACHD, AND PC THEN FIRE.
|
Received Certificate of Value | | | 6/27/1997 | | PASS |
|
|
|
|
Application received | | | 6/25/1997 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 6/25/1997 | | |
|
|
|
|