Letter of compliance | | | 3/12/1998 | | PASS |
|
|
|
Letter of Compliance #13880 issued 3-12-98.
|
INSP - Final | 3/3/1998 | 3/3/1998 | 3/3/1998 | P | PASS |
|
|
|
03/03/98 333 - FNL -OK FINAL
|
INSP-Final Inspection | 2/19/1998 | 2/20/1998 | 2/20/1998 | A | PASS |
Joe Tawney
|
|
|
02/19/98 406 - CALL DEL BEFORE YOU GO ###-####..REINSPECT REINSP FOR FINAL OK FOR CERT OF COMPLETION
|
90 day tracking............. | | 11/17/1997 | 2/15/1998 | | PEND |
|
|
|
|
INSP-Final Inspection | 1/16/1998 | 1/16/1998 | 1/16/1998 | P | PART |
Rick Jackson
|
|
|
exit sign installed. speakersare ceiling mount. strobes to be moved by 2/15/98.
|
INSP-Final Inspection | 1/15/1998 | 1/16/1998 | 1/16/1998 | A | FAIL |
Rick Jackson
|
|
|
01/16/98 409 - BILL ###-####\CARD TO SIGN ON BOARD BY DOOR.\\IDAHO POWER exit sign not installed indicated on plans. strobes installed, plans ca SPEAKER/STROBES (they were installed too high)
|
INSP - Final | 1/13/1998 | 1/13/1998 | 1/13/1998 | P | PART |
|
|
|
01/13/98 333 - ceiling ok
|
Issue PAID IN FULL permit | | | 12/3/1997 | | |
|
|
|
|
Routing - PLAN CHECK | 11/18/1997 | | 11/20/1997 | | PASS |
|
|
|
|
Print Occupancy Form | | | 11/20/1997 | | |
|
|
|
|
Inspection Record Card- Bld | | | 11/20/1997 | | |
|
|
|
|
Plan assigned to (DRS) | 11/17/1997 | | 11/20/1997 | | PASS |
Dan Stuart
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/20/1997 | | PASS |
|
|
|
|
Telephone call | | | 11/19/1997 | | |
|
|
|
Called Larry Kalousek to verify that the corridor construction and smoke/fire dampers indicated as well as duct work at existing shafts & through corridor walls is existing. Larry verified that only interior modifications to the tenant space were involved. Existing fire-resistive construction would not be involved in theis project. I told Larry of my concern for smoke detector shutoff for the VAV unit 2 that provides over 2000 cfm of air-supply and requires the shutoff capability per sec. 608 UMC. Larry said he would note the requirement.
|
Print Pending Permit.LaserJet4 | | | 11/19/1997 | | PASS |
|
|
|
|
Telephone call | | | 11/18/1997 | | |
|
|
|
Call from Larry Kalousek to see if plans had been reviewed for either 24 hour or desk permit status. I hadn't had a chance to look at them yet. Will let him know tommorrow.
|
Application received | | | 11/17/1997 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 11/17/1997 | | PEND |
|
|
|
|
Plan assigned to (MYS) | 11/17/1997 | | 11/17/1997 | | PEND |
Marlene Southard
|
|
|
Dan Stuart received plans to review for approval under 24 hour permit process.
|