Letter of compliance | | | 5/26/1998 | | PASS |
|
|
|
Letter of Compliance #15057 issued 5-26-98.
|
INSP - Final | 5/21/1998 | 5/22/1998 | 5/22/1998 | A | PASS |
|
|
|
05/22/98 333 - card signed for perm
|
INSP-Final Inspection | 5/21/1998 | 5/22/1998 | 5/22/1998 | A | PASS |
Rick Jackson
|
|
|
charlie/###-#### occ approved
|
Code Occupancy Approval | | | 5/22/1998 | | PASS |
|
|
|
Perm sign off. Project met conditions of DRH97-0232.
|
Permanent occupancy | | | 5/21/1998 | | PEND |
|
|
|
###-####-charlie ray
|
90 day tracking............. | | 2/3/1998 | 5/4/1998 | | |
|
|
|
|
INSP - Concrete | 4/16/1998 | 4/16/1998 | 4/16/1998 | P | PASS |
|
|
|
04/16/98 333 - fdn ok
|
INSP - Foundation | 4/8/1998 | 4/9/1998 | 4/9/1998 | P | PASS |
|
|
|
04/09/98 333 - fdn ok
|
INSP - Foundation | 4/7/1998 | 4/7/1998 | 4/7/1998 | P | PASS |
|
|
|
04/07/98 333 - ftg ok
|
Issue PAID IN FULL permit | | | 3/30/1998 | | |
|
|
|
|
Telephone call | | | 3/26/1998 | | PASS |
|
|
|
talked to david moe said he will be in to pick up this week
|
Telephone call | | | 3/18/1998 | | PASS |
|
|
|
talked to teresa morris said would be in friday to pick up plans
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/26/1998 | | PASS |
|
|
|
issue
|
Print Occupancy Form | | | 2/26/1998 | | |
|
|
|
|
Telephone call | | | 2/26/1998 | | |
|
|
|
talked to jackie and gave her $ amount
|
Inspection Record Card- Bld | | | 2/26/1998 | | |
|
|
|
|
Telephone call | | | 2/26/1998 | | |
|
|
|
|
Plan assigned to (PRP) | 2/4/1998 | | 2/26/1998 | | PASS |
|
|
|
02/26/98 10:52:49 PRP - this action updated by action script from <<>> in Case No. BLD98-0252
|
Routing - PLAN CHECK | 2/20/1998 | | 2/26/1998 | | PASS |
|
|
|
issued
|
Routing - FIRE | 2/12/1998 | | 2/20/1998 | | PASS |
|
|
|
|
Routing - PLAN CHECK | 2/9/1998 | | 2/11/1998 | | PASS |
|
|
|
forward to fire.
|
Plan Reviewer's activity | | | 2/11/1998 | | PASS |
|
|
|
reviewed plans, Specifications, and Engineering Calculations for compliance to UBC. Structure is for storing machanical equipment on pallets out of direct exposure to weather, all is non-combustible except pallets and/or plastic wrappings. Storage Classification should be a S2 but Openings between new structure and existing B are over allowed therefore requiring review as an addition to existing B, Type VN. Addition does not make total over allowed, therefore can be a S1, Type VN with no occupancy separation per UBC Chapter 3, and Table 3B. The exterior wall adjacent to the "Alley" is of CMU wall to 14' Height with no openings and qualifies as a one-hour fire resistive wall per Table 7B.
|
Print Pending Permit.LaserJet4 | | | 2/11/1998 | | PASS |
|
|
|
files
|
Routing - PLANNING | 2/6/1998 | | 2/6/1998 | | PASS |
|
|
|
X-REF: DRH97-0232. APPROVED BY MGS.
|
Routing - PUBLIC WORKS | 2/3/1998 | | 2/6/1998 | | PASS |
|
|
|
|
Plan assigned to (JCM) | 2/3/1998 | | 2/4/1998 | | PASS |
John Menard
|
|
|
|
Plan routing begun/NEW & ADDTN | | | 2/3/1998 | | |
|
|
|
|
Plans ACCEPTED BY PLAN CHECK | | | 2/3/1998 | | PEND |
|
|
|
REQUIRES A SOILS REPORT (SOIL BEARING PRESSURE IS OVER 1500 PSF). MAY REQUIRE DRAINAGE PLANS AND CALCS. I HAVE A CALL INTO BRIAN M. AM SENDING TO PW FOR HIM TO LOOK AT NEEDS TO CALL OUT ELEC. VALUE
|
Gay Receipt For Partial Pay | | | 2/3/1998 | | |
|
|
|
|
Recd Pcfee & Taken To Pln CK | | | 2/3/1998 | | |
|
|
|
|
Plan assigned to (MYS) | 2/3/1998 | | 2/3/1998 | | |
Marlene Southard
|
|
|
|
Application received | | | 2/3/1998 | | |
|
|
|
|
Received Certificate of Value | | | 2/3/1998 | | PEND |
|
|
|
NEEDS TO CALL OUT ELEC. VALUE. I PUT A CALL INTO SAM AND LEFT A MESSAGE.
|